8-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
1. When pushing
TEST
button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display.
Then push
ON / OFF
button.
• “TEST” is displayed on LC display during operation of Test Run.
• During Test Run, temperature cannot be adjusted but air volume can be selected.
• In heating and cooling operation, a command to fix the Test Run frequency is output.
• Detection of error is performed as usual. However, do not use this function except case of Test Run
because it applies load on the unit.
2. Use either heating or cooling operation mode for [TEST].
NOTE :
The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after
operation has stopped.
3. After a Test Run has finished, push
TEST
button again and check that [TEST] on LC display has gone off.
(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote
controller.)
<Wireless remote controller>
1. When TEMPORARY button is pushed for 10 seconds or more, “Pi!” sound is heard and the operation changes
to test run. After approx. 3 minutes, a cooling operation starts forcedly.
Check cool air starts blowing. If the operation does not start, check wiring again.
2.To stop a test operation, push TEMPORARY button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor units in test run.
TEMPORARY button
8. SETUP AT LOCAL SITE AND OTHERS
8-1. Indoor Unit
FILE NO. SVM-18038
- 64 -
Содержание RAV-RM1101CTP Series
Страница 15: ...1 CONSTRUCTION VIEWS EXTERNAL VIEWS 1 1 Indoor Unit RAV RM401CTP RAV RM561CTP FILE NO SVM 18038 15 ...
Страница 16: ...RAV RM801CTP FILE NO SVM 18038 16 ...
Страница 17: ...RAV RM1101CTP RAV RM1401CTP FILE NO SVM 18038 17 ...
Страница 105: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...