Optional Connector Specifications of Indoor P.C. Board
Function
Ventilation output
HA
CHK
Oper
ation chec
k
DISP
Exhibition mode
Connector No.
CN32
CN61
CN71
CN72
CN521
Pin No.
1
2
1
2
3
4
5
6
1
2
1
2
1
2
Specifications
DC12V
Output (Open collector)
ON/OFF input
0V
Remote controller prohibited input
Oper
ation output (Open collector)
DC12V
W
a
rning output (Open collector)
0V
0V
12V
5V
Remarks
Setting at shipment:
Inter
loc
k of ON b
y
indoor unit oper
ation, with OFF b
y stop oper
ation
∗
The single operation setting b
y F
AN b
utton on the remote controller is perf
or
med on the remote
controller (DN [31] = 0000
→
0001)
HA ON/OFF input (J01:
YES/NO=Pulse (At shipment from f
actor
y) /Static input selection)
P
e
rmission/Prohibition of remote controller oper
ation stop is perf
or
med b
y input.
1
2
3
4
5
Transmission
Receive
0V
Connected Application control kit (TCB-PCUC1E)
Oper
ation ON (Ans
w
er bac
k
of HA)
W
ar
ning output ON
This chec
k is used to chec
k indoor oper
ation.
(P
erf
or
ms operation of indoor f
an
“H”
, Louv
er hor
iz
ontal
and Dr
ain pump ON without comm
unication with outdoor and remote controller)
Communication is a
vailab
le b
y indoor unit and remote controller only
.
Option control kit
FILE NO. SVM-18038
- 38 -