- 31 -
°
C
15
20
25
30
40
k
Ω
16.1
12.6
10.0
8.0
5.2
°
C
-12
0
25
50
k
Ω
62.29
32.82
10.0
3.59
No.
Parts Name
Type
Specifications
1
Indoor unit fan motor
SMF-230-45A
Output (Rated) 45W, 6 pole, 1 phase, 230V, 50 Hz
2
Running capacitor for
EVM45M305UF
AC 450V, 3
µ
F
indoor fan motor
3
Transformer (Indoor unit)
ST-9586
187 ~ 264V
4
Geared motor
MT8-3-3
AC 240V, 3W
5
Relay
LY2F
AC240V, 2ab
6
Drain pump
PAD-416A23TF
AC230V, 0.2A
7
Float switch
FS-085-003B
AC230V, 0.5A
8
Sensor for room
Maximum input
temperature
38 mA
9
Indoor unit sensor for
DTN-C103J40
Maximum input
heat-exchanger temp.
34 mA
4.11
RAV-182U-PE, RAV-242U-PE
°
C
15
20
25
30
40
k
Ω
16.1
12.6
10.0
8.0
5.2
°
C
-12
0
25
50
k
Ω
62.29
32.82
10.0
3.59
No.
Parts Name
Type
Specifications
1
Indoor unit fan motor
SMF-230-90-4A
Output (Rated) 90W, 6 pole, 1 phase, 230V, 50 Hz
2
Running capacitor for
EVM45M305UF
AC 450V, 3
µ
F
indoor fan motor
3
Transformer (Indoor unit)
ST-9586
187 ~ 264V
4
Geared motor
MT8-3-3
AC 240V, 3W
5
Relay
LY2F
AC240V, 2ab
6
Drain pump
PAD-416A23TF
AC230V, 0.2A
7
Float switch
FS-085-003B
AC230V, 0.5A
8
Sensor for room
Maximum input
temperature
38 mA
9
Indoor unit sensor for
DTN-C103J40
Maximum input
heat-exchanger temp.
34 mA
4.12
RAV-362U-PE
°
C
15
20
25
30
40
k
Ω
16.1
12.6
10.0
8.0
5.2
°
C
-12
0
25
50
k
Ω
62.29
32.82
10.0
3.59
No.
Parts Name
Type
Specifications
1
Indoor unit fan motor
SMF-230-90-4A
Output (Rated) 90W, 6 pole, 1 phase, 200V, 50 Hz
2
Running capacitor for
EEP2G405HQA114
AC 400V, 4
µ
F
indoor fan motor
3
Transformer (Indoor unit)
ST-9586
187 ~ 264V
4
Geared motor
MT8-3-3
AC 240V, 3W
5
Relay
LY2F
AC240V, 2ab
6
Drain pump
PAD-416A23TF
AC230V, 0.2A
7
Float switch
FS-085-003B
AC230V, 0.5A
8
Sensor for room
Maximum input
temperature
38 mA
9
Indoor unit sensor for
DTN-C103J40
Maximum input
heat-exchanger temp.
34 mA
4.13
RAV-462U-PE
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807