- 43 -
7. OUTLINE OF CONTROL CIRCUIT
1
Operation
change-over
Operation mode is changed over according to operation mode select instruction
from the remote controller.
2
Controlling room
temperature
2-1
Adjusting range
°
C
2-2
Operating point is compressor:
off
2-3
Operating temperature accuracy:
±
1
°
C
2-4
Differential:
1 deg.
In cooling
18 ~ 29
18 ~ 29
Stopping air conditioner
Performing cooling operation
Performing fan only operation
OUTLINE OF CONTROL
REMOTE
CONTROLLER
INSTRUCTION
Stop
Cool
Fan only
NO.
ITEM
OUTLINE OF SPECIFICATIONS
REMARKS
3
3-1
[HIGH], [MED], [LOW] and [AUTO] are available.
3-2
In the auto fan, the fan speed is changed by the difference between Ta
and Ts, as shown below.
Fan speed control
Ts = setting
temperature
- Cooling -
4
If remote controller's ON/OFF switch is pressed 5 seconds continuously, the unit
goes into test run mode, and cooling operation is performed with the indoor fan in
the [HIGH].
Test Operation
Display L
Remote controller setting temperature
Operating temperature