67
4.
SPECIFICATIONS OF ELECTRICAL PARTS
No
PARTS NAME
TYPE
SPECIFICATIONS
Compressor
Outdoor Unit fan motor
Running capacitor for
outdoor fan motor (x2)
Magnetic contactor (Supplier:TOGAMI)
High pressure switch
Solenoid coil
Crankcase heater
Outdoor Unit for heat
exchanger temperature
Transformer for Outdoor Unit
Fuse
Sensor for cooling operation in low
ambient temperature
Reverse Phase Protector
Sensor for delivery
pipe temperature
Bimetal Thermostat
1
2
3
4
5
6
7
8
9
10
11
12
13
14
RAV-364AH8-1-PE
˚
C
-12
10
k
Ω
67.5
21.3
ZR48K3E-TFD-522
SMF-230-63N-2
SMF-230-39N-2
CLK-35J
ACB-2TB04W
CHV-AC240V
FT-67
CS-12A
Output (rated) 3.
88
kW, 2 pole, 380/415V, 3 Phase, 50Hz
Winding resistance 3.66
Ω
at 25˚C
Output (rated) 63W, 6 pole, 230V, 1 Phase, 50Hz
Winding Resistance: Common Run (Blk-Red) 79.4
Ω
at 25˚C
Common Start (Blk-Whi) 106
Ω
at 25˚C
Output (rated) 39W, 6 pole, 230V, 1 Phase, 50Hz
Winding Resistance: Common Run (Blk-Red) 97.1
Ω
at 25˚C
Common Start (Blk-Whi) 97.5
Ω
at 25˚C
AC 400V, 4µF
AC 440V, 50Hz
Tripping pressure 30kgf/cm
2
G
Resetting pressure 23kgf/cm
2
G
AC 220-240V
AC 240V, 28W
Maximum input
15.5mA
AC 187-264V
T5A
Maximum input
15.5mA
380/415, 3 Phase, 50Hz
Tripping temperature: 110°C
Resetting temperature: 90°C
˚
C
-12
10
k
Ω
67.5
21.3
˚
C
23
100
k
Ω
57.0
3.4
67
4.34
Top
Lower
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807