13. APPENDIX
Wired Remote Controller (RB-RWS21-E) setup
1. Test run setup
<Procedure> Perform setting while the air conditioner stops.
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.Setting louver position
Field setting menu(1/2)
Return
Set
1
Push the [
MENU] button to display the menu
screen.
2
Push and hold the [
MENU] button and the
[
] button at the same time to display the
“Field setting menu”.
→
Push and hold the buttons for more than 4 seconds.
3
Push the [
CANCEL] button to return.
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.Setting louver position
Field setting menu(1/2)
Return
Set
Return
Test mode start.
No
Yes
Test mode
Test
(1)
Room A
12:00
Mode
Fan Speed
Cool
Test
(2)
Room A
12:00
Return
Test mode stop.
No
Yes
Test mode
(3)
1
Push the [
] / [
] button to select
“1. Test mode” on the “Field setting menu” screen,
then push the “
Set” [ F2] button.
→
Pushing the “
Yes
Yes” [ F1] button sets the
test mode and the screen returns to the “Field setting
menu” screen.
Push [
CANCEL] twice, the screen (2) appears.
2
Push the [
ON / OFF] button to start the test
mode. The screen
(1)
shown in the left appears.
(The screen
(2)
appears when the operation is
stopped.)
→
Perform the test mode in the “Cool” or “Heat” mode.
→
Temperature setting cannot be adjusted during the test
mode.
→
Check codes are displayed as usual.
3
When the test mode is finished, push the
[
] / [
] button to select “1. Test mode”
on the “Field setting menu” screen, then push the
“
Set” [ F2] button.
The screen
(3)
appears.
→
Pushing the “
Yes
Yes” [ F1] button stops the
test mode screen and continues the normal operation.
NOTE
The test mode stops after 60 minutes.