– 25 –
FILE NO. SVM-03010(1)
5-3. RAS-24UKP-E-1 / RAS-24UA-E-1
RAS-24UKP-AR-1 / RAS-24UA-AR-1
* SASO Standard’s condition
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
Standard
0.4
11.0
High
27/19
35/24
Cooling
High temperature
0.7
12.0
High
32/23
52/31*
Low temperature
0.3
1.0
Low
21/15
21/15
Fan speed
(indoor)
50 Hz
Standard
pressure P
(MPaG)
Evaporator
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PH280X3-4MS
Accumulator
Cooling
O.D.:15.88 mm
O.D.:6.35 mm
Cooling
Gas container connection (Reinstall etc.)
Packed valve
(
∅
6.35)
Packed valve
(
∅
15.88)
0.39 m
(Connecting pipe)
∅
15.88
0.49 m
(Connecting pipe)
∅
6.35
T
P
Refrigerant
R22 1.63 kg
Mark ( ) means check points of Gas Leak
Capillary tube
∅
0.8x400
s
Capillary tube
∅
2.4x1400
s
Surface temp. of heat
exchanger interchanging
pipe T (°C)