(3)
Only the indoor motor fan does not operate
<Primary check>
(For 18K)
1. Is it possible to detect the power supply voltage (AC220–240V) between
Q
and
R
on the terminal block?
2. Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned
on, to prevent a cold air from blowing in.)
Start to operate
indoor unit in cooling
operation at airflow
level “LOW”.
Turn off indoor unit and
remove connector from motor.
Then start to operate indoor
unit with remote controller.
Turn off indoor unit and remove
connector from motor.
Then push [ ] button
on remote controller to stop
flashing lamp on indoor unit.
Change airflow level
to “HIGH”.
Start to operate the
indoor unit in except
heating operation.
At this time, is it possible
to detect DC 1V or more
between
5
+ and
3
–
of motor connector(CN36)?
(Check this condition within
15 seconds after
starting unit.)
Start to operate the
indoor unit in except
heating operation.
At this time, is it possible to
detect DC 1V or more between
5
+ and
3
– of motor
connector (CN36)?
Is it possible to detect
DC 311–340V between
1
+ and
3
– of motor
connector (CN36)?
(Motor connection condition)
Is it possible to detect DC 15V
between
4
+ and
3
– of
motor connector (CN36)?
Is it possible to detect
DC 15V between
4
+
and
3
– of motor
connector(CN36)?
Does indoor
fan operate?
B
A
Replace main
P.C. board.
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
Turn off power
supply once, and
turn it on again.
Is it possible to detect
DC 1V or more between
5
+ and
3
– of motor
connector (CN36)?
Does fan motor
continue to operate?
Replace indoor
fan motor.
YES
YES
NO
NO
Does check
operation LED flash?
Does check connecting
cable or power supply
cord complely?
Reconnecting the
in terconnection cable
and terminal block
NO
NO
YES
Does check
5V at display unit?
Replace
display unit
Does check 5V
at main P.C board?
NO
NO
YES
YES
YES
Is fuse (F02)
of indoor control
board blown?
NO
YES
FILE NO. SVM-19001
- 92 -
Содержание RAS-18J2AVG-E
Страница 19: ...4 2 Outdoor Unit RAS 05 07 10 13J2AVG E C L C L 280 400 Unit mm FILE NO SVM 19001 19 280 300 ...
Страница 22: ...RAS B16J2KVG E RAS 16J2AVG E FILE NO SVM 19001 22 ...
Страница 23: ...RAS 18J2KVG E RAS 18J2AVG E FILE NO SVM 19001 23 ...
Страница 137: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...