10-4. Outdoor Unit
10-4-1. Installation place
�
Do not use the supplied drain nipple for draining water.
Drain the water from all the drain holes directly.
hood and plate.
�
Do not use a double-stacked design.
�
To protect the outdoor unit from snow accumulation,
install a holding frame, and attach a snow protection
Snow protection plate
Snow protection hood
At least
50 cm
Snow accumulation line
Holding frame
Front
Anchor
bolts
Install at least 50 cm
above the snow
accumulation line.
Fig. 10-4-1
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
•
•
•
10-4-2. Precautions about Installation in Regions
with Snowfall and Cold Temperatures
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
•
A place full of machine oil.
•
A saline-place such as the coast.
•
A place full of sulfide gas.
•
A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
Fig. 10-4-2
CAUTION
When the outdoor unit is installed in
a place where the drain water might cause
any problems, Seal the water leakage
point tight
l
y
using
a silicon adhesive or
caulking compound.
Strong
wind
FILE NO. SVM-19001
- 66 -
Model
RAS-05, 07, 10,
13J2AVG-E
RAS-16, 18J2AVG-E
Chargeless
Up to 15 m
Up to 15 m
Maximum length
Additional
refrigerant charging
16 - 20 m (20 g / 1 m)
• The allowable height of outdoor unit installation site.
Model
RAS-05, 07, 10,
13J2AVG-E
RAS-16, 18J2AVG-E
• A place where the drain water does not raise any
problems
15 m
20 m
-
Maximum height
12 m
12 m
•
A place which provides the spaces around the
outdoor unit as shown in the diagram
•
A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration
•
A place where the operation noise and discharged
air do not disturb your neighbors
•
A place which is not exposed to a strong wind
•
A place free of a leakage of combustible gases
•
A place which does not block a passage
•
When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
•
The allowable length of the connecting pipe.
Precautions for adding refrigerant
• Use a scale having a precision with at least 10 g
per index line when adding the refrigerant.
Do not use a bathroom scale or similar instrument.
• Use liquid refrigerant when refilling the refrigerant.
Since the refrigerant is in liquid form, it can fill quickly.
Therefore, perform the filling operation
carefully and insert the refrigerant gradually.
Содержание RAS-18J2AVG-E
Страница 19: ...4 2 Outdoor Unit RAS 05 07 10 13J2AVG E C L C L 280 400 Unit mm FILE NO SVM 19001 19 280 300 ...
Страница 22: ...RAS B16J2KVG E RAS 16J2AVG E FILE NO SVM 19001 22 ...
Страница 23: ...RAS 18J2KVG E RAS 18J2AVG E FILE NO SVM 19001 23 ...
Страница 137: ...144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND ...