111
–
No.
Part name
Compressor
Procedure
1) Perform work of item 1 of
and
,
,
,
.
2) Extract refrigerant gas.
3) Remove the partition board.
(ST1TØ4 ×
10
L 3 pcs.)
4) Remove the sound-insulation material.
5) Remove terminal cover of the compressor,
and disconnect lead wire of the compressor
from the terminal.
6) Remove pipe connected to the compressor
with a burner.
• Take care to keep the 4-way valve away
from naked flames. (Otherwise, it may
malfunction.)
7) Remove the fixing screw of the bottom plate
and heat exchanger. (ST1TØ4 ×
10
L 1 pc.)
8) Remove the fixing screw of the bottom plate
and valve fixing plate.
(ST1TØ4 ×
10
L 1 pc.)
9) Pull upward the refrigeration cycle.
10) Remove BOLT (3 pcs.) fixing the compres-
sor to the bottom plate.
* Precautions when assembling the com-
pressor.
Tighten the compressor bolts using a
tightening torque of 4.9 N•m.
Remarks
Reactor
1) Perform work of item 1 of
, and
.
2) Remove screws fixing the reactor
s
.
(ST1TØ4 ×
10
L
4
pcs.)
Reactor
Partition
Compressor
Valve
board
fixing
plate
Revised-1