Q9 ASD Installation and Operation Manual
81
V/f 5-Point Setting Voltage 2
No Path — Direct Access Only
The V/f 5-Point Setting Voltage 2 establishes the output voltage level that is to
be associated with the frequency setting of
(V/f 5-Point Setting Frequency
2).
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
and
for additional information on this setting.
Direct Access Number — F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (
)
V/f 5-Point Setting Frequency 3
No Path — Direct Access Only
The V/f 5-Point Setting Frequency 3 sets the frequency to be associated with the
voltage setting of parameter
(V/f 5-Point Setting Voltage 3).
and
for additional information on this setting.
Direct Access Number — F194
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
V/f 5-Point Setting Voltage 3
No Path — Direct Access Only
The V/f 5-Point Setting Voltage 3 establishes the output voltage level that is to
be associated with the frequency setting of
(V/f 5-Point Setting Frequency
3).
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
and
for additional information on this setting.
Direct Access Number — F195
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (
)
V/f 5-Point Setting Frequency 4
No Path — Direct Access Only
The V/f 5-Point Setting Frequency 4 sets the frequency to be associated with the
voltage setting of parameter
(V/f 5-Point Setting Voltage 4).
and
for additional information on this setting.
Direct Access Number — F196
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
V/f 5-Point Setting Voltage 4
No Path — Direct Access Only
The V/f 5-Point Setting Voltage 4 establishes the output voltage level that is to
be associated with the frequency setting of
(V/f 5-Point Setting Frequency
4).
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
and
for additional information on this setting.
Direct Access Number — F197
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (
)
Содержание Q9 Series
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 217: ...Q9 ASD Installation and Operation Manual 207 Figure 28 See Table 13 and 14 for Actual Dimensions ...
Страница 218: ...208 Q9 ASD Installation and Operation Manual Figure 29 See Table 13 and 14 for Actual Dimensions ...
Страница 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...
Страница 220: ...210 Q9 ASD Installation and Operation Manual Figure 31 See Table 13 and 14 for Actual Dimensions ...