Q9 ASD Installation and Operation Manual
173
My Function Time Data 1
Program
My Function Data
This parameter is used to set the response delay of the My Function Time Data 1
terminal.
The applied discrete input signal must be present at the input terminal of the
Q9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will be
ignored.
Direct Access Number — F928
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 2
Program
My Function Data
This parameter is used to set the response delay of the My Function Time Data 2
terminal.
The applied discrete input signal must be present at the input terminal of the
Q9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will be
ignored.
Direct Access Number — F929
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 3
Program
My Function Data
This parameter is used to set the response delay of the My Function Time Data 3
terminal.
The applied discrete input signal must be present at the input terminal of the
Q9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will be
ignored.
Direct Access Number — F930
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 4
Program
My Function Data
This parameter is used to set the response delay of the My Function Time Data 4
terminal.
The applied discrete input signal must be present at the input terminal of the
Q9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will be
ignored.
Direct Access Number — F931
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 5
Program
My Function Data
This parameter is used to set the response delay of the My Function Time Data 5
terminal.
The applied discrete input signal must be present at the input terminal of the
Q9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will be
ignored.
Direct Access Number — F932
Parameter Type — Numerical
Factory Default — 0.01
Changeable During Run — Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
Содержание Q9 Series
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 217: ...Q9 ASD Installation and Operation Manual 207 Figure 28 See Table 13 and 14 for Actual Dimensions ...
Страница 218: ...208 Q9 ASD Installation and Operation Manual Figure 29 See Table 13 and 14 for Actual Dimensions ...
Страница 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...
Страница 220: ...210 Q9 ASD Installation and Operation Manual Figure 31 See Table 13 and 14 for Actual Dimensions ...