Q9 ASD Installation and Operation Manual
197
Alarms and Trips
Alarms
An Alarm is an indication that there is a system operating limit that is being exceeded and that a Fault
may be imminent (not all ongoing alarms result in a fault) or to provide an indication that an operator error
has occurred. An Alarm may be associated with an output terminal to notify the operator of the condition
remotely, close a contact, or to engage a brake. At the least, an Alarm will cause an alarm code to appear
on the EOI display
The active alarm may be displayed on the Alarm screen — some alarms are displayed on the Frequency
Command screen. Press the Mode key if the alarm is displayed on the Frequency Command screen to
scroll to the Alarm screen.
lists the Alarm codes that may be displayed during operation of the Q9 ASD. Each alarm code
listed is accompanied by a description and a possible cause. In the event that the source of the malfunction
cannot be determined, contact your Toshiba Sales Representative for further information on the condition
and for an appropriate course of action.
In the event that multiple alarms are activated only the first to be detected will be displayed.
Table 11. Alarms
EOI Display
Fault Description
Possible Cause
4-20 mA
4-20 Signal Loss.
• Misconnection, poor connection, or broken wire.
• Improper programming at
and associated
parameters.
*ASD Overload
Load Requirement in Excess of the
Capability of the ASD.
• Carrier frequency is too high.
• Excessive load.
• Acceleration time is too short.
• DC damping rate is too high.
• Motor is starting into a spinning load after a
momentary power failure.
• ASD is improperly matched to the application.
Comm Error
Communication Error Interruption.
• Improperly programmed ASD.
• Improper communications settings.
• Improperly connected cables.
Comm Error 2
Communication Error.
Damp
Damper Closed.
• Improper configuration/programming for Damper
Control at discrete input terminals.
Note:
* Reset ignored if active.
Содержание Q9 Series
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 217: ...Q9 ASD Installation and Operation Manual 207 Figure 28 See Table 13 and 14 for Actual Dimensions ...
Страница 218: ...208 Q9 ASD Installation and Operation Manual Figure 29 See Table 13 and 14 for Actual Dimensions ...
Страница 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...
Страница 220: ...210 Q9 ASD Installation and Operation Manual Figure 31 See Table 13 and 14 for Actual Dimensions ...