Q9 ASD Installation and Operation Manual
199
Over-Current
ASD Output Current Greater than F601
Setting.
• Phase-to-phase short (U/T1, V/T2, or W/T3).
• Defective IGBT (U/T1, V/T2, or W/T3).
• ASD output to the motor is connected incorrectly.
• ASD is attempting to start into a spinning motor
after a momentary power loss.
• Motor/machine jammed.
• Mechanical brake engaged while the ASD is
starting or while running.
• Acceleration/deceleration time is too short.
• Voltage Boost setting is too high.
• V/f setting adjustment required.
• Load fluctuations.
• ASD is operating at an elevated temperature.
• ASD/Motor improperly matched.
• ASD current exceeds 320% or 340% of the rated
FLA on ASDs that are greater than 100 HP or
that are 100 HP or less, respectively, during
acceleration.
*Over-Heat
Over-Heating.
• ASD is operating at an elevated temperature.
• ASD is too close to heat-generating equipment.
• Cooling fan vent is obstructed.
• Cooling fan is inoperative.
• Internal thermistor is disconnected.
Over-Torque
Torque Requirement in Excess of the
Setting of F616 or F617 for a Time Longer
than the Setting of F618.
• ASD is improperly matched to the application.
• Parameter
setting is too low.
• Obstructed load.
Part Replace
Part Replacement Alarm.
• Part Replacement Alarm at
timed out.
Run-Time Counter
User-Set Run-Time Counter Exceeded.
• Type Reset required; select Clear run timer.
Soft Stall
Overload Soft Stall Active.
• Soft Stall selection adjustment required (
Thermal Err
Option Thermal Sensor Threshold
Exceeded.
• User-set thermal threshold setting of
exceeded.
Under-Current
Output Current of the ASD is Below the
Level Defined at F611.
.
• Parameter
adjustment required.
Note:
* Reset ignored if active.
Table 11. Alarms (Continued)
EOI Display
Fault Description
Possible Cause
Содержание Q9 Series
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 217: ...Q9 ASD Installation and Operation Manual 207 Figure 28 See Table 13 and 14 for Actual Dimensions ...
Страница 218: ...208 Q9 ASD Installation and Operation Manual Figure 29 See Table 13 and 14 for Actual Dimensions ...
Страница 219: ...Q9 ASD Installation and Operation Manual 209 Figure 30 See Table 14 for Actual Dimensions ...
Страница 220: ...210 Q9 ASD Installation and Operation Manual Figure 31 See Table 13 and 14 for Actual Dimensions ...