Indoor remote
controller
status
Outdoor
unit
7-segment
display
s
e
r
u
s
a
e
m
r
e
t
n
u
o
C
e
s
u
a
C
No response
L08
Line addresses and indoor addresses of all the connected
indoor units are not set.
Set up addresses.
There is no header unit of group control.
Set up a group address.
E19
-00
Alternate
blinking
:
r
e
d
r
o
e
h
t
n
I
(
.
n
i
a
g
a
r
e
w
o
p
e
h
t
n
o
n
r
u
T
.
n
o
d
e
n
r
u
t
t
o
n
s
i
r
e
w
o
p
t
i
n
u
r
o
o
d
n
I
indoor
outdoor)
Indoor/outdoor communication line is not correctly connected
to the U1/U2 terminal of the
outdoor
unit ( Fig. 1). (Indoor/
outdoor cannot communicate before address setup.)
Correct wiring
There is no of outdoor
terminator resistor
, or there
are two or more resistances (before address setup).
Check SW30 bit 2 of the
outdoor
unit.
No connection between multiple refrigerant
lines: SW30 bit 2 is on.
Connection between multiple refrigerant
lines: SW30 bit 2 of the connected
outdoor
unit is turned on only for one line.
E20
-01
Alternate
blinking
Address setup is performed under the condition of
connecting multiple refrigerant lines ( Fig.
2
).
Correct wiring
Indoor remote
controller
status
Outdoor
unit
7-segment
display
s
e
r
u
s
a
e
m
r
e
t
n
u
o
C
e
s
u
a
C
No response
None
The communication line is not connected between indoor
and outdoor (the unit that does not respond to the indoor
remote controller).
Improve
the wiring.
Line address and indoor address are not set (the unit that
does not respond to the indoor remote controller).
Set up the address.
The power of the header unit of the group is not turned on in
indoor group control (the unit that does not respond to the
indoor remote controller).
Turn on the power.
Group address is set to the follower unit for individual control
(the unit that does not respond to the indoor remote
controller).
Set the group address to “0” in the case of
individual control.
No display on the
indoor remote
controller (no line
is output.)
None
The power is not turned on (the unit that is not displayed on
the indoor remote controller).
Turn on the power.
The indoor remote controller is not connected with a wire (the
unit that is not displayed on the indoor remote controller).
Improve
the wiring.
Miswiring of the indoor remote controller (the unit that is not
displayed on the indoor remote controller)
Improve
the wiring.
Indoor remote controller communication circuit
trouble
(the
unit that is not displayed on the indoor remote controller)
If 220-240 V is incorrectly applied to the indoor remote
controller terminal, the remote controller communication
circuit fails.
Remove the
quick connect
terminal
connected to indoor remote controller
terminals A/B, and check the voltage. If
voltage is not applied (normally 15 to 18 V),
replace the PC board.
ON
1
2
SW30
7-5-2. Operation from the indoor remote controller is not accepted,
and a check code is displayed on the 7-segment display of the
interface PC board of the
outdoor
unit.
7-5-3. There is no display of a check code on the 7-segment display
on the interface PC board of the
outdoor
unit, although there
is indoor unit that is not accepting operation from the indoor
remote controller.
- 97 -