(2)Clearing
check code
by using switches on the interface board of the
outdoor
unit
Using the switches on the interface P.C. board of the
outdoor
unit, this function is to clear the currently
detected
check code
for each refrigerant circuit system without resetting the power supply.
Check codes
in both outdoor and indoor units are once cleared, and
check code
detection is performed again.
(3)Clearing
check code
by resetting power
This function is provided to clear
check code
in a system by resetting the power of all the outdoor and the indoor
units.
As same as the clearing method by the interface P.C. board,
check codes
of both the outdoor and the
indoor units are once cleared, and
check code
detection is performed again.
<Method>
(1)
Be sure to reset power of both the outdoor and the indoor units.
(2)
Turn on the power of the indoor unit prior to the power of the outdoor unit.
(If the power is turned on in reverse order, a check code [E19] (No. of
troubled
outdoor
unit)
is
output.)
NOTE)
After power reset, it requires usually 3 minutes to power-on due to the initial communication of the
system. In some cases, it requires max. 10 minutes.
7-segment display
[A]
[B]
[ E r ] [ ]
7-segment display
[A]
[B]
[ E r ] [ C L ]
Set the rotary switches on the interface P.C. board of
the
outdoor
unit as follows.
Set SW01/SW02/SW03 to [2/16/1]
Press the push-switch SW04 on the same board for
5 seconds or more.
[ C L] is displayed in 7-segment display [B] on the
board (for 5 seconds), and
Check code
is completely
cleared.
7-segment display [A]
7-segment display [B]
SW04
SW05
SW01 SW02 SW03
<Rotary switches>
Interface P.C. board
- 114 -