-3. Check Procedure to Search Cause of Compressor
Oil Shortage
Are there
any miswiring or incorrect
connection of TK1 and TK
2
sensor in the unit that has
replaced compressor?
Are the
characteristics of the TK1
or
TK2,
sensors of the unit that has
replaced compressor correct?
(To next page)
No
No
Correct the miswiring or connection.
TK1: CN531 TK2: CN532
Yes
Yes
With the compressor(s) disconnected,
check the oil circuit in accordance
with the procedure described below.
Replace the
troubled
sensor.
- 204 -