 When the following symptoms are found

Check the points described below before asking repair servicing.

Symptom

Cause

It is not a failure.

Outdoor unit

•  White misty cold air or 

water is out.

•  Fan of the outdoor unit stops automatically and performs defrost 

operation.

•  Sometimes, noise of air 

leak is heard.

•  Solenoid valve works when defrost operation starts or 

fi

nishes.

Indoor unit

•  “Swish” sound is heard 

sometimes.

•  When the operation has started, during the operation, or 

immediately after the operation has stopped, a sound such as water 

fl

ows may be heard, and the operation sound may become larger for 

2 or 3 minutes immediately after the operation has started.

They are 

fl

owing sound of refrigerant or draining sound of 

dehumidi

fi

er.

•  Slight clacking sound is 

heard.

•  This is sound generated when heat exchanger, etc. expand and 

contract slightly due to change of temperature.

•  Discharge air smells.

•  Various smell such as one of wall, carpet, clothes, cigarette, or 

cosmetics adhere to the air conditioner.

• “

” indication is lit.

•  When cooling operation cannot be performed because another 

indoor unit performs heating operation.

• “

” indication is lit.

•  When stopping the fan to prevent cool air blow at starting heating.

•  Sound or cool air is output 

from the stand by indoor 

unit.

•  Since refrigerant is 

fl

owed temporarily to prevent stay of oil or 

refrigerant in the stand by indoor unit, sound of 

fl

owing refrigerant, 

may be heard or white steam when other indoor unit operates in 

Heat mode, and cold air in Cool mode may be blow-out.

•  When power of the air conditioner is turned 

on, “Ticktock” sound is heard.

•  Sound is generated when the expansion valve operates when power 

has been turned on.

•  LCD blurs when it is touched.

•  LCD may temporarily blur by static electricity.

•  Fan and louvers of the indoor unit moves 

when the unit is not operated.

•  Intermittent operation of the fan with louvers open is sometimes 

carried out for the refrigerant recovery control of unoperated unit.

Check again.

Stops automatically.

•  Is the timer “OFF”?

Does not operate.

•  Is it a power failure?

•  Is the power switch turned off?

•  Is the power fuse or breaker blown?

•  Has the protective device operated? (The operation lamp goes on.)

•  Is the timer “ON”? (The operation lamp goes on.)

•  Are Cool and Heat selected simultaneously?

(“

” indication is lit on the display of the remote controller.)

•  Is outdoor temperature out of operation temperature range?

Air is not cooled or warmed suf

fi

ciently.

•  Is the air intake or air discharge of the outdoor unit obstructed?

•  Are any door or window open?

•  Is the air 

fi

lter clogged with dust?

•  Is discharge louver of the indoor unit set at appropriate position?

•  Is air selection set to “Low” “Med.”, and is the operation mode set 

to “Fan”?

•  Is the setup temp. the appropriate temperature?

•  Are Cool and Heat selected simultaneously?

(“

” indication is lit on the display of the remote controller.)

•  Is outdoor temperature out of operation temperature range?

 

CAUTION

If any of the following conditions occur, turn off the main power supply switch and immediately contact the dealer:

•  Switch operation does not work properly.

•  The main power fuse often blows out, or the circuit breaker is often activated.

•  A foreign matter or water fall inside the air conditioner.

•  When the air conditioner does not operate even after the cause of the protective device activation has been 

removed.

•  Any other unusual conditions are observed.

 

 Con

fi

 rmation and check

If a problem occurs with the air 

conditioner, the OFF timer indicator 

alternately shows the check code 

and the indoor Unit No. in which the 

problem occurred.

Check code

The indoor Unit No. in which 
the problem occurred.

 

 Troubleshooting history and con

fi

 rmation

You can check the troubleshooting history with the following procedure if a problem occurs with the air conditioner.
(The troubleshooting history records up to 4 incidents.)
You can check it during operation or when operation is stopped.
•  If you check the troubleshooting history during OFF timer operation, the OFF timer will be canceled.

Procedure

Description of operation

1

Push the OFF timer button for over 10 seconds and 
the indicators appear as an image indicating the 
troubleshooting history mode has been entered. 
If [   Service check] is displayed, the mode enters in 
the troubleshooting history mode.
•  [01: Order of troubleshooting history] appears in the 

temperature indicator.

•  The OFF timer indicator alternately shows the [check 

code] and the [indoor Unit No. ] in which the problem 
occurred.

2

Each time the setting button is pushed, the recorded 
troubleshooting history is displayed in sequence.
The troubleshooting history appears in order from [01] 
(newest) to [04] (oldest).

 

CAUTION

In the troubleshooting history mode, DO NOT push the 
Menu button for over 10 seconds, doing so deletes the 
entire troubleshooting history of the indoor unit.

3

1

2

3

After you have 

fi

nished checking, push the ON/OFF 

button to return to the regular mode.
•  If the air conditioner is operating, it remains operated 

even after the ON/OFF button has been pushed. To 
stop its operation, push the ON/OFF button again.

– 17 –

33-EN 

34-EN

Содержание MMY-MUP0801HT8JP-E

Страница 1: ...E MMY MUP1001HT8P E MMY MUP1201HT8P E MMY MUP1401HT8P E MMY MUP1601HT8P E MMY MUP1801HT8P E MMY MUP2001HT8P E MMY MUP2201HT8P E MMY MUP2401HT8P E MMY MUP0801HT8JP E MMY MUP1001HT8JP E MMY MUP1201HT8JP E MMY MUP1401HT8JP E MMY MUP1601HT8JP E MMY MUP1801HT8JP E MMY MUP2001HT8JP E MMY MUP2201HT8JP E MMY MUP2401HT8JP E English ...

Страница 2: ...tters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to work at heights has been trained in matters relating...

Страница 3: ...ould result in slight injury 2 or damage 3 to property if the product is handled improperly 1 Serious bodily harm indicates loss of eyesight injury burns electric shock bone fracture poisoning and other injuries which leave aftereffect and require hospitalization or long term treatment as an outpatient 2 Slight injury indicates injury burns electric shock and other injuries which do not require ho...

Страница 4: ...is work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and or electrical leaks After the installation work has been completed have the installer explain about the circuit breaker positions In the event that error has occurred in the air conditioner set the circuit breaker to the OFF position and contact a service person If you instal...

Страница 5: ...nt Be sure to stop running the air conditioner and turn off the breaker before cleaning Otherwise injury may result as the fan is rotating at high speed inside the unit Repairs When you have noticed that some kind of error such as when an error display has appeared there is a smell of burning abnormal sounds are heard the air conditioner fails to cool or heat or water is leaking has occurred in th...

Страница 6: ...m the unit Prevent any liquid from falling into the remote controller Do not spill juice water or any kind of liquid Do not wash the air conditioner Doing so may result in electric shock Check whether the installation base and other equipment have become deteriorated after being used for a long time Leaving them such condition may result in the unit s falling down and causing injury Do not leave f...

Страница 7: ... HP For details on these models read the owner s manuals that come with the indoor units Console MML UP NHP For details on these models read the owner s manuals that come with the indoor units Hot Water Module MMW UP LQ For details on these models read the owner s manuals that come with the indoor units 2 Part names Outdoor unit Air discharge Warm air comes out when cooling and cool air when heati...

Страница 8: ...ype MMU UP YHP Air intake grille Air in the room is taken in through here Discharge louver Controls discharge air directions Earth screw Equipped on the electrical control box Air filter Filters out dust Inside the return air grille MMU UP SH Discharge louver Controls discharge air directions Earth screw Equipped on the electrical control box Air intake grille Air in the room is taken in through h...

Страница 9: ... H Discharge louver Controls discharge air directions Earth screw Air intake grille Air in the room is taken in through here Air filter Filters out dust Inside the return air grille Floor Standing Concealed Type MML UP BH Drain funnel with strainer Accessory to be attached at the site Air filter Filters out dust Inside the return air grille Front panel lower Air discharge Earth screw Equipped on t...

Страница 10: ...ral control blinks when the ON OFF MODE or TEMP button on the remote controller is pushed and the buttons do not function Settings that can be configured on the remote controller differ depending on the mode of the central control For details read the Owner s Manual of the central remote controller 3 Setting indicator Indicates that the model is being checked automatically after a breaker is throw...

Страница 11: ...cted Auto cannot be selected at the Fan mode FIX is displayed for models capable of the fan speed setting If you do not push any button for 30s the fan speed mode finishes If you do not push any button for 30s the operation mode finishes 4 Select the temperature Push the setting button to adjust the temperature The temperature setting range is 18 0 C to 29 0 C The temperature can be set in steps o...

Страница 12: ...ooling The louver can be adjusted to four steps Point the louver horizontally If pointing downward dew may form on the surface of the air discharge port and may drop down Initial 1 2 3 4 Swing Operation mode Available directions COOL DRY 1 2 3 4 T For fan The louver can be adjusted to six steps Select a wind direction Auto swing The SWING indicator is displayed and the louver begins swinging Repea...

Страница 13: ...rd in COOL mode water droplets may form on the surface of the cabinet or louver and drop down When the horizontal louver is pointing horizontally in HEAT mode the air may not warm up the room evenly Floor standing type Vertical adjustment T When cooling Move the louver manually and point it horizontally to send cool air across the entire room T When heating Move the louver manually and point it do...

Страница 14: ...areas near oceans etc Hot springs emitting sulfidizing gas etc Heavily acidic or alkaline places e g place disinfection solution is frequently sprayed at Special maintenance or parts are required for use in the above places For details contact the dealer where you purchased the product Leave an enough space around the air intake and discharge of the outdoor unit so that the ventilation is not rest...

Страница 15: ... intake or air discharge of the outdoor unit is blocked When strong wind blows continuously against the air discharge of the outdoor unit During heating When dust or dirt is excessively adhered to the air filter of the indoor unit When the air discharge of the indoor unit is blocked NOTE When the protective device activates turn off the power switch remove the cause and then restart running Coolin...

Страница 16: ... Dry bulb temp Room temperature 21 C to 32 C Dry bulb temp 15 C to 24 C Wet bulb temp CAUTION Room relative humidity less than 80 If the air conditioner operates in excess of this figure the surface of the air conditioner may cause dewing Heating operation Outdoor temperature 25 C to 15 5 C Wet bulb temp Room temperature 15 C to 28 C Dry bulb temp If air conditioner is used outside of the above co...

Страница 17: ...deformation or breakage If unused for over a month Leave the fan on for half a day or so to dry the inside Turn off the main power switch Clean the air filter and then attach it Periodic inspection After being used for a long period of time the parts may deteriorate or malfunction or the drainage may worsen due to heat moisture dust or general usage In addition to the maintenance it is recommended...

Страница 18: ...y Is the air intake or air discharge of the outdoor unit obstructed Are any door or window open Is the air filter clogged with dust Is discharge louver of the indoor unit set at appropriate position Is air selection set to Low Med and is the operation mode set to Fan Is the setup temp the appropriate temperature Are Cool and Heat selected simultaneously indication is lit on the display of the remo...

Страница 19: ...EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMY MUP0801HT8P E MMY MUP1001HT8P E MMY MUP1201HT8P E MMY MUP1401HT8P E MMY MUP1601HT8P E MMY MUP1801HT8P E MMY MUP2001HT8P E MMY MUP2201HT8P E MMY MUP2401HT8P E MMY MUP0801HT8JP E MMY MUP1001HT8JP E MMY MUP1201HT8JP E MMY MUP1401HT8JP E MMY MUP1601HT8...

Страница 20: ...1141002201 ...

Отзывы: