  Floor standing cabinet type

1

Push down the upper part of the air intake 
grille slightly, and then pull it toward you to 
remove it.

2

Take out the air 

fi

lter inside the air intake 

grille.

3

Vacuum dust or brush clean.

•  If heavily stained, it is more effective to wash in 

lukewarm water mixed with neutral detergent.

•  After washing, rinse it well, and dry it in the 

shade.

•  Reinstall the cleaned air 

fi

lter.

‹

  Floor standing concealed type

1

Push down hook of the air 

fi

lter on the front 

panel (Lower side).

2

Pull the air 

fi

lter toward you to remove it.

Front panel 

(Lower)

Air 

fi

lter knob

3

Vacuum dust or brush clean.

•  If heavily stained, it is more effective to wash in 

lukewarm water mixed with neutral detergent.

•  After washing, rinse it well, and dry it in the 

shade.

•  Reinstall the cleaned air 

fi

lter.

 

 Cleaning the indoor unit and 

remote controller

• Ask quali

fi

ed service person to clean the indoor units 

for the models listed in the warning on the top of this 
chapter.

•  Wipe with a dry, soft cloth.

Do not use acidic or alkaline detergents.

•  If heavily stained, wipe off dirt with a cloth soaked in 

lukewarm water.
(Do not use water to wipe the remote controller)

•  Do not use benzine, thinner, scouring powder, 

chemical cloth, etc. as those may cause deformation 
or breakage.

 

 If unused for over a month

•  Leave the fan on for half a day or so to dry the 

inside.

•  Turn off the main power switch.
•  Clean the air 

fi

lter and then attach it.

 

 Periodic inspection

•  After being used for a long period of time, the parts 

may deteriorate or malfunction, or the drainage 
may worsen, due to heat, moisture, dust, or general 
usage.

•  In addition to the maintenance, it is recommended 

that you have a inspection (charges apply) 
performed by the dealer where you purchased the 
unit, etc.

 

CAUTION

• 

Perform high-pressure cleaning for the heat 
exchanger.

If commercially available detergent (strong alkaline 
or acid cleaning agent) is used, the surface treatment 
of the heat exchanger will deteriorate, which may 
degrade the self cleaning performance. For details, 
contact our sales department or the dealer where 
you purchased the unit.

 

 Before the cooling season

Ask a quali

fi

ed service person to clean the drain 

pan

 

CAUTION

Clean the drain pan

Without cleaning, the drain pan may be 

fi

lled with

waste, and water may over

fl

ow onto the ceiling or 

fl

oor.

If you do not plan to use the unit for more 
than 1 month

(1)  Operate “Fan” mode.

Run the fan for about half a 
day to dry the inside fully.

(2)  Stop the air conditioner 

and turn off the main power 
switch.

Checks before operation

(1)  Check that the air 

fi

lters are installed.

(2)  Check that the air discharge or intake is not 

blocked.

(3)  Turn on the main power switch.

– 16 –

31-EN 

32-EN

Содержание MMY-MUP0801HT8JP-E

Страница 1: ...E MMY MUP1001HT8P E MMY MUP1201HT8P E MMY MUP1401HT8P E MMY MUP1601HT8P E MMY MUP1801HT8P E MMY MUP2001HT8P E MMY MUP2201HT8P E MMY MUP2401HT8P E MMY MUP0801HT8JP E MMY MUP1001HT8JP E MMY MUP1201HT8JP E MMY MUP1401HT8JP E MMY MUP1601HT8JP E MMY MUP1801HT8JP E MMY MUP2001HT8JP E MMY MUP2201HT8JP E MMY MUP2401HT8JP E English ...

Страница 2: ...tters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to work at heights has been trained in matters relating...

Страница 3: ...ould result in slight injury 2 or damage 3 to property if the product is handled improperly 1 Serious bodily harm indicates loss of eyesight injury burns electric shock bone fracture poisoning and other injuries which leave aftereffect and require hospitalization or long term treatment as an outpatient 2 Slight injury indicates injury burns electric shock and other injuries which do not require ho...

Страница 4: ...is work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and or electrical leaks After the installation work has been completed have the installer explain about the circuit breaker positions In the event that error has occurred in the air conditioner set the circuit breaker to the OFF position and contact a service person If you instal...

Страница 5: ...nt Be sure to stop running the air conditioner and turn off the breaker before cleaning Otherwise injury may result as the fan is rotating at high speed inside the unit Repairs When you have noticed that some kind of error such as when an error display has appeared there is a smell of burning abnormal sounds are heard the air conditioner fails to cool or heat or water is leaking has occurred in th...

Страница 6: ...m the unit Prevent any liquid from falling into the remote controller Do not spill juice water or any kind of liquid Do not wash the air conditioner Doing so may result in electric shock Check whether the installation base and other equipment have become deteriorated after being used for a long time Leaving them such condition may result in the unit s falling down and causing injury Do not leave f...

Страница 7: ... HP For details on these models read the owner s manuals that come with the indoor units Console MML UP NHP For details on these models read the owner s manuals that come with the indoor units Hot Water Module MMW UP LQ For details on these models read the owner s manuals that come with the indoor units 2 Part names Outdoor unit Air discharge Warm air comes out when cooling and cool air when heati...

Страница 8: ...ype MMU UP YHP Air intake grille Air in the room is taken in through here Discharge louver Controls discharge air directions Earth screw Equipped on the electrical control box Air filter Filters out dust Inside the return air grille MMU UP SH Discharge louver Controls discharge air directions Earth screw Equipped on the electrical control box Air intake grille Air in the room is taken in through h...

Страница 9: ... H Discharge louver Controls discharge air directions Earth screw Air intake grille Air in the room is taken in through here Air filter Filters out dust Inside the return air grille Floor Standing Concealed Type MML UP BH Drain funnel with strainer Accessory to be attached at the site Air filter Filters out dust Inside the return air grille Front panel lower Air discharge Earth screw Equipped on t...

Страница 10: ...ral control blinks when the ON OFF MODE or TEMP button on the remote controller is pushed and the buttons do not function Settings that can be configured on the remote controller differ depending on the mode of the central control For details read the Owner s Manual of the central remote controller 3 Setting indicator Indicates that the model is being checked automatically after a breaker is throw...

Страница 11: ...cted Auto cannot be selected at the Fan mode FIX is displayed for models capable of the fan speed setting If you do not push any button for 30s the fan speed mode finishes If you do not push any button for 30s the operation mode finishes 4 Select the temperature Push the setting button to adjust the temperature The temperature setting range is 18 0 C to 29 0 C The temperature can be set in steps o...

Страница 12: ...ooling The louver can be adjusted to four steps Point the louver horizontally If pointing downward dew may form on the surface of the air discharge port and may drop down Initial 1 2 3 4 Swing Operation mode Available directions COOL DRY 1 2 3 4 T For fan The louver can be adjusted to six steps Select a wind direction Auto swing The SWING indicator is displayed and the louver begins swinging Repea...

Страница 13: ...rd in COOL mode water droplets may form on the surface of the cabinet or louver and drop down When the horizontal louver is pointing horizontally in HEAT mode the air may not warm up the room evenly Floor standing type Vertical adjustment T When cooling Move the louver manually and point it horizontally to send cool air across the entire room T When heating Move the louver manually and point it do...

Страница 14: ...areas near oceans etc Hot springs emitting sulfidizing gas etc Heavily acidic or alkaline places e g place disinfection solution is frequently sprayed at Special maintenance or parts are required for use in the above places For details contact the dealer where you purchased the product Leave an enough space around the air intake and discharge of the outdoor unit so that the ventilation is not rest...

Страница 15: ... intake or air discharge of the outdoor unit is blocked When strong wind blows continuously against the air discharge of the outdoor unit During heating When dust or dirt is excessively adhered to the air filter of the indoor unit When the air discharge of the indoor unit is blocked NOTE When the protective device activates turn off the power switch remove the cause and then restart running Coolin...

Страница 16: ... Dry bulb temp Room temperature 21 C to 32 C Dry bulb temp 15 C to 24 C Wet bulb temp CAUTION Room relative humidity less than 80 If the air conditioner operates in excess of this figure the surface of the air conditioner may cause dewing Heating operation Outdoor temperature 25 C to 15 5 C Wet bulb temp Room temperature 15 C to 28 C Dry bulb temp If air conditioner is used outside of the above co...

Страница 17: ...deformation or breakage If unused for over a month Leave the fan on for half a day or so to dry the inside Turn off the main power switch Clean the air filter and then attach it Periodic inspection After being used for a long period of time the parts may deteriorate or malfunction or the drainage may worsen due to heat moisture dust or general usage In addition to the maintenance it is recommended...

Страница 18: ...y Is the air intake or air discharge of the outdoor unit obstructed Are any door or window open Is the air filter clogged with dust Is discharge louver of the indoor unit set at appropriate position Is air selection set to Low Med and is the operation mode set to Fan Is the setup temp the appropriate temperature Are Cool and Heat selected simultaneously indication is lit on the display of the remo...

Страница 19: ...EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMY MUP0801HT8P E MMY MUP1001HT8P E MMY MUP1201HT8P E MMY MUP1401HT8P E MMY MUP1601HT8P E MMY MUP1801HT8P E MMY MUP2001HT8P E MMY MUP2201HT8P E MMY MUP2401HT8P E MMY MUP0801HT8JP E MMY MUP1001HT8JP E MMY MUP1201HT8JP E MMY MUP1401HT8JP E MMY MUP1601HT8...

Страница 20: ...1141002201 ...

Отзывы: