Periodic Maintenance

• For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air 

conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended. 
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof 
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor 
unit at least once every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner’s expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, 
and even compressor failure.

Inspection before maintenance

Following inspection must be carried out by a qualified installer or qualified service person.

* Refer to the Service Manual for how to remove.

Maintenance List

Parts

Inspection method

Heat exchanger*

Open the air intake grille to remove the bell mouth and the fan, and then check the heat exchanger 

if there is any clogging or damages.

Fan motor

Check if any abnormal noise can be heard.

Fan

Open the air intake grille and check the fan if there are any waggles, damages or adhesive dust.

Filter

Open the air intake grille and check if there are any stains or breaks on the filter.

Drain pan*

Remove the panel, the bell mouth and the drain pan, and then check if there is any clogging, 

abnormal smell or drain water pollution.

Part

Unit

Check (visual / auditory)

Maintenance

Heat exchanger

Indoor / outdoor

Dust / dirt clogging, scratches

Wash the heat exchanger when it is 

clogged.

Fan motor

Indoor / outdoor

Sound

Take appropriate measures when 

abnormal sound is generated.

Filter

Indoor

Dust / dirt, breakage

• Wash the filter with water when it is 

contaminated.

• Replace it when it is damaged.

Fan

Indoor

• Vibration, balance
• Dust / dirt, appearance

• Replace the fan when vibration or 

balance is terrible.

• Brush or wash the fan when it is 

contaminated.

Air intake / discharge 

grilles

Indoor / outdoor

Dust / dirt, scratches

Fix or replace them when they are 

deformed or damaged.

Drain pan

Indoor

Dust / dirt clogging, drain 

contamination

Clean the drain pan and check the 

downward slope for smooth drainage.

Ornamental panel, 

louvres

Indoor

Dust / dirt, scratches

Wash them when they are contaminated 

or apply repair coating.

Exterior

Outdoor

• Rust, peeling of insulator
• Peeling / lift of coat

Apply repair coating.

11

Troubleshooting

Confirmation and check

When a problem occurred in the air conditioner, the 
check code and indoor UNIT No. appear on the display 
part of the remote controller.
The check code is only displayed during the operation.
If the display disappears, operate the air conditioner 
according to the following “Confirmation of check code” 
for confirmation.

Confirmation of check code

When a problem occurred on the air conditioner, the 
check code can be confirmed with the following 
procedure. (The check code is stored in memory up to 
4 check codes.)
The check code can be confirmed from both operating 
status and stop status.

1

When 

 and 

 buttons are pushed 

simultaneously for 4 seconds or more, the 
following display appears.

If 

 is displayed, the mode enters in the check 

code mode.
• [

01

: Order of check code] is displayed in CODE 

No..

• [Check code] is displayed in CHECK.
• [Indoor unit address in which a problem 

occurred] is displayed in Unit No..

2

Every pushing of 

 button used to set 

temperature, the check code stored in 
memory is displayed in order.

The numbers in CODE No. indicate CODE No. 
[

01

] (latest) 

 [

04

] (oldest).

REQUIREMENT

Do not push 

 button because all the check code of the 

indoor unit will be deleted.

3

After confirmation, push 

 button to return 

to the usual display.

Check code

Indoor UNIT No. in which 

a problem occurred

3

2

1

Содержание MMU-AP0057MH-E

Страница 1: ...h Indoor Unit Model name Compact 4 way Cassette type MMU AP0057MH E MMU AP0077MH E MMU AP0097MH E MMU AP0127MH E MMU AP0157MH E MMU AP0187MH E AIR CONDITIONER MULTI TYPE Installation Manual For commercial use ...

Страница 2: ...ation Manual attached to the outdoor unit ADOPTION OF R410A REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 7 4 Installation 9 5 Drain piping 11 6 Refrigerant piping 13 7 Electrical connection 14 8 Applicable controls 16 9 Test run 19 10 Maintenance 20 11 Troubleshooting 21...

Страница 3: ... or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba C...

Страница 4: ...ferent from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the OF...

Страница 5: ...ce any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough...

Страница 6: ... the power is turned on without first conducting these checks If there is any kind of trouble such as check code display has appeared smell of burning abnormal sounds the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner do not touch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take s...

Страница 7: ... water dust former refrigerant or refrigerating oil enter the refrigerating cycle during installation work To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the R410A refrigerant For conne...

Страница 8: ...ng places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas hot spring The unit should be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a factory Oil adhering to the heat exchanger and resin part turbo fan in the indoor unit may reduce the performance g...

Страница 9: ... 200 200 15 or more 271 or more 1000 or more 271 or more 1000 or more 1000 or more An obstacle 15 or more 1 400 or more 560 or more 3 Check port 450 2 Check port 450 1000 or more Ceiling height Unit m When the height of the ceiling exceeds the distance of the item Standard 4 way in below table the warm air is difficult to reach the floor It is necessary to change the setup value of the high ceilin...

Страница 10: ...nel external dimension 620 13 to 20 13 to 20 Ceiling open dimension 580 to 594 Panel external dimension 620 External view Unit mm 23 5 0 146 191 95 147 105 55 235 105 235 320 214 256 93 40 132 173 257 70 Ø162 53 193 154 146 8 3 12 184 156 ØA Ceiling open dimension 580 to 594 Bottom face of ceiling Wiring entry for remote control Unit external dimension 575 Refrigerant pipe connecting port Gas side...

Страница 11: ...ccording to size in the unit external view as shown below Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Indoor unit Panel fixing screw Installation pattern Accessory Installation pattern attachment hole New concrete slab Install the bolts with insert brackets or anchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in a...

Страница 12: ... le s s 5 Drain piping CAUTION CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the following materials for piping and heat insulating at site Flexible hose U...

Страница 13: ...36 mm or less Underside of ceiling Indoor unit 300 mm or less Rising up 850 mm or less After the electric work has finished pour water during COOL mode operation If the electric work has not yet finished pull out the float switch connector CN34 Red from the electrical control box and check draining by plugging the single phase 220 240 V power to the terminal blocks R L and S N If doing so the drai...

Страница 14: ...f R410A is higher than that of R22 Approx 1 6 times Use a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers Then...

Страница 15: ...e power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cab...

Страница 16: ...ovided for the control wire and remote controller wire Do not connect the high voltage circuit 1 Loosen the two screws and remove the cover of electrical control box by sliding in the direction of the arrow 2 Connect the power supply wire communication wires and remote controller wire to the terminal block of the electrical control box 3 Tighten the screws of the terminal block and fix the wires w...

Страница 17: ...face circuit board While the automatic addresses are being set up no remote controller operations can be performed Setup takes up to 10 minutes usually about 5 minutes When the power is turned on after automatic address setup It takes up to 10 minutes usually about 3 minutes for the outdoor unit to start operating after the power has been turned on Before the air conditioner was shipped from the f...

Страница 18: ...g to 0001 or 0003 is possible however setting to 0000 requires a setting data change to 0000 using the wired remote controller separately sold with the normal switch setting factory default To restore the factory defaults To return the DIP switch settings to the factory defaults set SW501 1 and SW501 2 to OFF connect a separately sold wired remote controller and then set the data of CODE No 5d to ...

Страница 19: ...ing cooling mode 5 Determine the setting by pushing button When the setting has been determined lights up 6 Push button to complete the setting Cancelling louver lock Set the wind direction to 0000 of the louver lock setup procedure above When the setting is canceled goes out Other operations are the same as those in Locking the louvers No swing Remote controller sensor The temperature sensor of t...

Страница 20: ...he status returns to a normal 2 4 3 1 5 Wireless remote controller RBC AX32UW series 1 Turn on the power of the air conditioner When power is turned on for the first time after installation it takes approx 5 minutes until the remote controller becomes available In the case of subsequent power on it takes approx 1 minute until the remote controller becomes available Execute a test run after the pre...

Страница 21: ...ter away from the grille and remove 8 1 7 Hook Fall preventive strap 4 Cleaning with water or vacuum cleaner If dirt is heavy clean the air filter using tepid water with a neutral detergent or just water After cleaning with water dry the air filter sufficiently in a shaded place 5 Mount the air filter 6 Close the air intake grille Check that the fall preventive strap of the air intake grille is at...

Страница 22: ...ures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace it when it is damaged Fan Indoor Vibration balance Dust dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are ...

Страница 23: ...nication trouble between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 Communication circuit trouble between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side ...

Страница 24: ...H03 01 Comp 1 side 02 Comp 2 side Current detect circuit system trouble IPDU H05 H05 TD1 sensor miswiring I F H06 H06 Low pressure protective operation I F H07 H07 Oil level down detective protection I F H08 H08 01 TK1 sensor trouble 02 TK2 sensor trouble 04 TK4 sensor trouble 05 TK5 sensor trouble Oil level detective temp sensor trouble I F H15 H15 TD2 sensor miswiring I F H16 H16 01 TK1 oil circ...

Страница 25: ... unit address ALT Indoor unit overflow trouble Indoor unit P12 ALT Indoor unit fan motor trouble Indoor unit P13 P13 ALT Outdoor liquid back detection trouble I F P15 P15 01 TS condition 02 TD condition ALT Gas leak detection I F P17 P17 ALT Discharge temp TD2 trouble I F P19 P19 Detected outdoor unit number ALT 4 way valve inverse trouble I F P20 P20 ALT High pressure protective operation I F P22...

Страница 26: ...ouble 1B All Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending trouble in TCC LINK central control device TCC LINK C06 Receiving trouble in TCC LINK central control device TCC LINK C12 Batch alarm of general purpose equipm...

Страница 27: ...RPORATION 336 Tadehara Fuji shi Shizuoka ken 416 8521 JAPAN TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMU AP0057MH E MMU AP0077MH E MMU AP0097MH E MMU AP0127MH E MMU AP0157MH E MMU AP0187MH E Commercial name Super Modular Multi System Air Conditioner Super Heat Recov...

Страница 28: ... STANDARD 0001 HIGH CEILING 2 0002 HIGH CEILING 3 0003 High ceiling setup CODE NO 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 2 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE...

Страница 29: ...EB99813301 ...

Отзывы: