background image

– 13 –

6

Refrigerant piping

Refrigerant piping

1. Use the following item for the refrigerant piping.

Material : Seamless phosphorous deoxidized 
copper pipe.
Wall thickness : 0.8 mm or more (C1120T-0)

2. Flare nut and flare works are also different from 

those of the conventional refrigerant.
Take out the flare nut attached to the main unit of the 
air conditioner, and use it.

REQUIREMENT

When the refrigerant pipe is long, provide support 
brackets at intervals of 2.5 - 3 m to clamp the refrigerant 
pipe. Otherwise, abnormal sound may be generated.

CAUTION

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1. Remove dust and moisture from the inside of the 

connecting pipes.

2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes by using 

VACUUM PUMP.

4. Check the gas leakage. (Connected points)

Pipe size

Permissible piping length and 
height difference

They vary according to the outdoor unit.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Flaring

• Cut the pipe with a pipe cutter.

Remove burrs completely. 
Remaining burrs may cause gas leakage.

• Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of 
refrigerant R22, the flare tools newly manufactured 
for R410A are recommended.
However, the conventional 
tools can be used by adjusting 
projection margin of the 
copper pipe.

Projection margin in 
flaring: B (Unit: mm)

Rigid (Clutch type)

Flaring dia. meter size: A (Unit: mm)

* In case of flaring for R410A with the 

conventional flare tool, pull it out approx.

0.5 mm more than that for R22 to adjust 
to the specified flare size.

The copper pipe gauge is useful for 

adjusting projection margin size.

Model 

name

MMU-

AP005, AP007 

AP009, AP012 

type

AP015, AP018 

type

Pipe size

Gas side

9.5 mm

12.7 mm

Liquid side

6.4 mm

6.4 mm

Outer dia. of copper pipe

R410A tool 

used

Conventional 

tool used

R410A

R410A

6.4, 9.5

0 - 0.5

1.0 - 1.5

12.7

Outer dia. of copper pipe

A

+0

–0.4

R410A

6.4

9.1

9.5

13.2

12.7

16.6

B

A

Tightening connection

CAUTION

CAUTION

Do not apply excessive torque. Otherwise, the nut may 
crack depending on the conditions.

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) Use a torque wrench, tighten the 
flare pipe connecting sections which connect the 
indoor and outdoor units of the specified tightening 
torque.
Incorrect connections may cause not only a gas leak, 
but also a trouble of the refrigeration cycle.
Align the centres of the connecting pipes and tighten 
the flare nut as far as possible with your fingers. Then 
tighten the nut with a spanner and torque wrench as 
shown in the figure.

REQUIREMENT

Tightening with an excessive torque may crack the nut 
depending on installation conditions.
Tighten the nut within the specified tightening torque.

Piping with outdoor unit

Shape of valve differs according to the outdoor unit.
For details of installation, refer to the Installation 
Manual of the outdoor unit.

Leak check test, evacuation 
and other procedure

For leak check test, evacuation, addition of refrigerant, 
and gas leak check, refer to the Installation Manual 
attached to the outdoor unit.

REQUIREMENT

Do not supply power to the indoor unit until the leak 
check test and evacuation are completed. (If the indoor 
unit is powered on, the pulse motor valve is fully closed, 
which extends the time for vacuuming.)

Open the valve fully

Open the valve of the outdoor unit fully.
For details, refer to the Installation Manual attached to 
the outdoor unit.

Heat insulation process

Apply heat insulation for the pipes separately at liquid 
side and gas side.
For the heat insulation to the pipes at gas side, use the 
material with heat-resisting temperature 120 °C or 
higher.
Apply the attached heat insulation to the pipe 
connecting section of the indoor unit securely without 
gap.

REQUIREMENT

• Apply the heat insulation to the pipe connecting 

section of the indoor unit securely up to the root 
without exposure of the pipe. (The pipe exposed to the 
outside may causes water leak.)

• Wrap heat insulator with its slits facing up (ceiling 

side).

Unit: N•m

Outer dia. of copper pipe

Tightening torque

6.4 mm

14 - 18 (1.4 to 1.8 kgf•m)

9.5 mm

34 - 42 (3.4 to 4.2 kgf•m)

12.7 mm

49 - 61 (4.9 to 6.1 kgf•m)

Work using double spanner

Indoor unit

Union

Heat insulation 

pipe 

(Accessory)

Flare nut

Heat insulator 

of the pipe

Wrap the pipe with the attached heat insulator 

without any gap between the indoor unit.

The seam must be faced upward 

(ceiling side).

Banding band 

(locally 

procured)

25-EN

26-EN

Содержание MMU-AP0057MH-E

Страница 1: ...h Indoor Unit Model name Compact 4 way Cassette type MMU AP0057MH E MMU AP0077MH E MMU AP0097MH E MMU AP0127MH E MMU AP0157MH E MMU AP0187MH E AIR CONDITIONER MULTI TYPE Installation Manual For commercial use ...

Страница 2: ...ation Manual attached to the outdoor unit ADOPTION OF R410A REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of installation place 7 4 Installation 9 5 Drain piping 11 6 Refrigerant piping 13 7 Electrical connection 14 8 Applicable controls 16 9 Test run 19 10 Maintenance 20 11 Troubleshooting 21...

Страница 3: ... or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba C...

Страница 4: ...ferent from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the OF...

Страница 5: ...ce any combustion appliance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough...

Страница 6: ... the power is turned on without first conducting these checks If there is any kind of trouble such as check code display has appeared smell of burning abnormal sounds the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner do not touch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take s...

Страница 7: ... water dust former refrigerant or refrigerating oil enter the refrigerating cycle during installation work To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the R410A refrigerant For conne...

Страница 8: ...ng places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas hot spring The unit should be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is used or place near machines in a factory Oil adhering to the heat exchanger and resin part turbo fan in the indoor unit may reduce the performance g...

Страница 9: ... 200 200 15 or more 271 or more 1000 or more 271 or more 1000 or more 1000 or more An obstacle 15 or more 1 400 or more 560 or more 3 Check port 450 2 Check port 450 1000 or more Ceiling height Unit m When the height of the ceiling exceeds the distance of the item Standard 4 way in below table the warm air is difficult to reach the floor It is necessary to change the setup value of the high ceilin...

Страница 10: ...nel external dimension 620 13 to 20 13 to 20 Ceiling open dimension 580 to 594 Panel external dimension 620 External view Unit mm 23 5 0 146 191 95 147 105 55 235 105 235 320 214 256 93 40 132 173 257 70 Ø162 53 193 154 146 8 3 12 184 156 ØA Ceiling open dimension 580 to 594 Bottom face of ceiling Wiring entry for remote control Unit external dimension 575 Refrigerant pipe connecting port Gas side...

Страница 11: ...ccording to size in the unit external view as shown below Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Indoor unit Panel fixing screw Installation pattern Accessory Installation pattern attachment hole New concrete slab Install the bolts with insert brackets or anchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in a...

Страница 12: ... le s s 5 Drain piping CAUTION CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the following materials for piping and heat insulating at site Flexible hose U...

Страница 13: ...36 mm or less Underside of ceiling Indoor unit 300 mm or less Rising up 850 mm or less After the electric work has finished pour water during COOL mode operation If the electric work has not yet finished pull out the float switch connector CN34 Red from the electrical control box and check draining by plugging the single phase 220 240 V power to the terminal blocks R L and S N If doing so the drai...

Страница 14: ...f R410A is higher than that of R22 Approx 1 6 times Use a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak but also a trouble of the refrigeration cycle Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers Then...

Страница 15: ...e power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Arrange the power supply circuit breaker and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used Power supply wire specification Cab...

Страница 16: ...ovided for the control wire and remote controller wire Do not connect the high voltage circuit 1 Loosen the two screws and remove the cover of electrical control box by sliding in the direction of the arrow 2 Connect the power supply wire communication wires and remote controller wire to the terminal block of the electrical control box 3 Tighten the screws of the terminal block and fix the wires w...

Страница 17: ...face circuit board While the automatic addresses are being set up no remote controller operations can be performed Setup takes up to 10 minutes usually about 5 minutes When the power is turned on after automatic address setup It takes up to 10 minutes usually about 3 minutes for the outdoor unit to start operating after the power has been turned on Before the air conditioner was shipped from the f...

Страница 18: ...g to 0001 or 0003 is possible however setting to 0000 requires a setting data change to 0000 using the wired remote controller separately sold with the normal switch setting factory default To restore the factory defaults To return the DIP switch settings to the factory defaults set SW501 1 and SW501 2 to OFF connect a separately sold wired remote controller and then set the data of CODE No 5d to ...

Страница 19: ...ing cooling mode 5 Determine the setting by pushing button When the setting has been determined lights up 6 Push button to complete the setting Cancelling louver lock Set the wind direction to 0000 of the louver lock setup procedure above When the setting is canceled goes out Other operations are the same as those in Locking the louvers No swing Remote controller sensor The temperature sensor of t...

Страница 20: ...he status returns to a normal 2 4 3 1 5 Wireless remote controller RBC AX32UW series 1 Turn on the power of the air conditioner When power is turned on for the first time after installation it takes approx 5 minutes until the remote controller becomes available In the case of subsequent power on it takes approx 1 minute until the remote controller becomes available Execute a test run after the pre...

Страница 21: ...ter away from the grille and remove 8 1 7 Hook Fall preventive strap 4 Cleaning with water or vacuum cleaner If dirt is heavy clean the air filter using tepid water with a neutral detergent or just water After cleaning with water dry the air filter sufficiently in a shaded place 5 Mount the air filter 6 Close the air intake grille Check that the fall preventive strap of the air intake grille is at...

Страница 22: ...ures when abnormal sound is generated Filter Indoor Dust dirt breakage Wash the filter with water when it is contaminated Replace it when it is damaged Fan Indoor Vibration balance Dust dirt appearance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are ...

Страница 23: ...nication trouble between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 Communication circuit trouble between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side ...

Страница 24: ...H03 01 Comp 1 side 02 Comp 2 side Current detect circuit system trouble IPDU H05 H05 TD1 sensor miswiring I F H06 H06 Low pressure protective operation I F H07 H07 Oil level down detective protection I F H08 H08 01 TK1 sensor trouble 02 TK2 sensor trouble 04 TK4 sensor trouble 05 TK5 sensor trouble Oil level detective temp sensor trouble I F H15 H15 TD2 sensor miswiring I F H16 H16 01 TK1 oil circ...

Страница 25: ... unit address ALT Indoor unit overflow trouble Indoor unit P12 ALT Indoor unit fan motor trouble Indoor unit P13 P13 ALT Outdoor liquid back detection trouble I F P15 P15 01 TS condition 02 TD condition ALT Gas leak detection I F P17 P17 ALT Discharge temp TD2 trouble I F P19 P19 Detected outdoor unit number ALT 4 way valve inverse trouble I F P20 P20 ALT High pressure protective operation I F P22...

Страница 26: ...ouble 1B All Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending trouble in TCC LINK central control device TCC LINK C06 Receiving trouble in TCC LINK central control device TCC LINK C12 Batch alarm of general purpose equipm...

Страница 27: ...RPORATION 336 Tadehara Fuji shi Shizuoka ken 416 8521 JAPAN TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMU AP0057MH E MMU AP0077MH E MMU AP0097MH E MMU AP0127MH E MMU AP0157MH E MMU AP0187MH E Commercial name Super Modular Multi System Air Conditioner Super Heat Recov...

Страница 28: ... STANDARD 0001 HIGH CEILING 2 0002 HIGH CEILING 3 0003 High ceiling setup CODE NO 5d NO CHANGE 0000 STANDARD 0001 HIGH CEILING 2 0002 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE...

Страница 29: ...EB99813301 ...

Отзывы: