50-EN
49-EN
– 25 –
Check code
Wireless remote controller
Check code name
Judging device
Wired remote
controller display
Outdoor unit 7-segment display
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
P29
P29
01: Comp. 1 side
02: Comp. 2 side
ALT
Comp, position detective circuit system error
IPDU
P31
—
—
ALT
Other indoor unit error
(Group follower indoor unit error)
Indoor unit
*1 Number of IPDU
01: Compressor 1 error
02: Compressor 2 error
03: Compressor 1 and 2 error
08: Fan 1 error
09: Compressor 1, Fan 1 error
0A: Compressor 2, Fan 1 error
0B: Compressor 1 and 2, Fan 1 error
11: Compressor 1, Fan 2 error
12: Compressor 2, Fan 2 error
13: Compressor 1 and 2, Fan 2 error
18: Fan 1 and 2 error
19: Compressor 1, Fan 1 and 2 error
1A: Compressor 2, Fan 1 and 2 error
1B: All
Error detected by
ТСС
-LINK central control device
Check code
Wireless remote controller
Check code name
Judging device
Central control
device indication
Outdoor unit 7-segment display
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
C05
—
—
—
Sending error in
ТСС
-LINK central control device
TCC-LINK
C06
—
—
—
Receiving error in
ТСС
-LINK central control device
TCC-LINK
C12
—
—
—
Batch alarm of general-purpose equipment control interface
General-purpose equipment,
l/F
P30
Differs according to error contents of unit with occurrence of alarm
Group control follower unit error
TCC-LINK
—
—
(L20 is displayed.)
Duplication addresses of indoor units in
ТСС
-LINK central control
device
ТСС
-LINK: TOSHIBA Carrier Communication Link.