CAUTION

Strictly comply with the following rules to prevent damage of the indoor units and human injury.

 

y

Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)

 

y

Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use 
buffering cloth or other material to not damage the unit.

 

y

To move the indoor unit, hold the hooking brackets (4 positions) only.

  Do not apply force to the other parts (such as refrigerant pipe, drain pan, foamed parts, or resin parts).

 

y

Carry the package by four or more persons, and do not bundle it with plastic band at positions other than 
speci

fi

ed.

 

y

To install vibration isolation material to hanging bolts, con

fi

rm that it does not increase the unit vibration.

 

„

External dimensions

 

(Unit: mm)

Unit external dimension 1400

1296 (Outside)

101

95

Hole for hanging bolt 
(4-Ø12×30)

324 

(Outside)

84

448

90

90

90

27

Hanging bolt mounting pitch

1465

34

45

45

21

510

778

900

Hanging bolt  mounting pitch

810

321

221

Refrigerant pipe 
connecting port 
(Liquid side)

Refrigerant pipe 
connecting port 
(Gas side)

Drain pipe connecting port
(Gravitational drainage)

74

4

Installation

 

„

Installation of hanging bolt

 

y

Consider the piping / wiring after the unit is hung to 
determine the location of the indoor unit installation 
and orientation.

 

y

After the location of the indoor unit installation has 
been determined, install hanging bolts.

 

y

For the dimensions of the hanging bolt pitches, refer 
to the external view.

 

y

When a ceiling already exists, lay the drain pipe, 
refrigerant pipe, control wires, and remote controller 
wires to their connection locations before hanging 
the indoor unit.

Procure hanging bolts washer and nuts for installing 
the indoor unit (these are not supplied).

Hanging bolt

M10 or W3/8

4 pieces

Nut

M10 or W3/8

12 pieces

Washer

M10

8 pieces

Installation of hanging bolt

Use M10 hanging bolts (4 pcs, locally procured).
Matching to the existing structure, set pitch according 
to size in the unit external view as shown below.

New concrete slab

Install the bolts with insert brackets or anchor bolts.

(Pipe hanging

anchor bolt)

(Blade type 

bracket)

(Slide type

bracket)

Anchor bolt

Rubber

Steel 

fl

 ame structure

Use existing angles or install new support angles.

Hanging bolt

Hanging bolt

Support angle

Existing concrete slab

Use a hole-in anchors, hole-in plugs, or a hole-in bolts.

 

„

Installation of indoor unit

Treatment of ceiling

The ceiling differs according to structure of building.
For details, consult your constructor or interior 

fi

nish

contractor.
In the process after the ceiling board has been 
removed, it is important to reinforce ceiling foundation
(frame) and to keep horizontal level of installed ceiling
correctly in order to prevent vibration of ceiling board.

 

y

Attach the nuts and the M10 

fl

at washers to the 

hanging bolt.

 

y

Put washers at up and down of the hanging bracket 
of the indoor unit to hang down the indoor unit.

 

y

Check that four sides are horizontal with a level 
gauge. (Horizontal degree: Within 5 mm)

M10 

fl

 at washer

M10 

fl

 at washer

Hanging bolt

(W3/8 or M10)

Nut

(W3/8 or M10)

Nut

(W3/8 or M10)

REQUIREMENT

 

y

Hang the unit in a horizontal position.

  When unit is hanged to slant, it may cause 

over

fl

ow of drainage.

 

y

Install the unit within the dimension according to 
the 

fi

gure below.

 

y

Use level gauge to con

fi

rm whether the unit is 

hang horizontally.

Front view

0 to 5 mm

0 to 5 mm

Side view

Set the air intake and air discharge 

sides are within 5 mm with each other.

Set the drain pipe connecting port side 

within 5 mm lower than opposite side.

Содержание MMD-AP0726HP-E

Страница 1: ...AIR CONDITIONER MULTI TYPE Installation Manual Indoor Unit Model name For commercial use English Concealed Duct High Static Pressure Type MMD AP0726HP E MMD AP0966HP E 1116950195 1 ...

Страница 2: ... made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporat...

Страница 3: ...rom heat Center of gravity Unit mm Use forklift to carry in the air conditioner units and use winch or hoist at installation of them 665 220 435 Center of gravity Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric ...

Страница 4: ... by mistake 1 Precautions for safety Only a qualified installer 1 or qualified service person 1 is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you d...

Страница 5: ...tion Installation Suction duct length must be longer than 850 mm When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in injury Follow the instructions in the Installation Man...

Страница 6: ... earth wire Grounding work Incomplete grounding causes an electric shock Do not connect earth wires to gas pipes water pipes and lightning conductor or telephone earth wires After completing the repair or relocation work check that the earth wires are connected properly Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations ...

Страница 7: ...pe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupture injury or other trouble CAUTION New refrigerant air conditioner installation This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer T...

Страница 8: ...hens where food oils are used Blocked filters may cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result y Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to de...

Страница 9: ...rature 24 C wet bulb temperature Air volume Low air volume operation time 4 hours Installation space Unit mm Reserve sufficient space required for installation or service work 1 1 1 1 1 If there are enough space under the unit more than 1000mm the service door Ceiling opening is not necessary Space required for installation and servicing Ceiling 200 or more 25 1450 25 2500 or more Floor surface Se...

Страница 10: ...nit Procure hanging bolts washer and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Washer M10 8 pieces Installation of hanging bolt Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the unit external view as shown below New concrete slab Install the bolts with inser...

Страница 11: ... at intervals of 1 5 to 2 meters to prevent flapping y Install the collective piping as shown in the following figure y Do not provide any air vents Otherwise the drain water will spout causing water to leak y Do not allow any force to be applied to the connection area with the drain pipe Heat insulator Downward slope 1 50 to 1 100 or more Support bracket As long as possible VP 30 Arched shape Tra...

Страница 12: ...k remove the access panel and pour water then conduct the drain check Access plate Pour into the drain pan Heat insulating process y As shown in the figure cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit tightly y Cover the drain pipe tightly with a heat insulator procured locally so that it overlaps with the attached heat insulator of the...

Страница 13: ...h Air Flow m h Air Flow m h Standard Air Flow 3800 m h Standard Air Flow 3800 m h Standard Air Flow 4800 m h Standard Air Flow 4800 m h Mid 83Pa Mid 83Pa Mid 83Pa Mid 83Pa Mid 50Pa Mid 50Pa Mid 50Pa Mid 50Pa Mid 150Pa 117Pa Mid 150Pa 117Pa Mid 150Pa 117Pa Mid 150Pa 117Pa Mid 183Pa Mid 183Pa Mid 183Pa Mid 183Pa Mid 217Pa Mid 217Pa Mid 217Pa Mid 217Pa Mid 250Pa Mid 250Pa Mid 250Pa Mid 250Pa Low Low ...

Страница 14: ... conditioner to fail or to leak Overview of duct connection NOTE Parts except air conditioner unit are to be locally procured Canvas joint Canvas joint Silencer chamber Air inlet Air filter Silencer chamber Air supply port Check port Air Conditioner Arrangement Unit mm Referring to the following dimensions manufacture duct at the local site Thickness of plate 0 8 mm 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0...

Страница 15: ...per pipe gauge is useful for adjusting projection margin size A Tightening connection CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Unit N m Outer dia of copper pipe Tightening torque 12 7 mm dia 50 to 62 5 0 to 6 2 kgf m q Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torq...

Страница 16: ...ctric wiring with the high temperature part of the pipe It causes the coating melted REQUIREMENT y For power supply wiring strictly conform to the Local Regulation in each country y For wiring of power supply of the outdoor units follow the Installation Manual of each outdoor unit y After connecting wires to the terminal blocks provide a trap and fix wires with the cord clamp y Run the refrigerant...

Страница 17: ...ng L L1 L2 Ln In case of wired type only Up to 500 m In case of wireless type included Up to 400 m Total wire length of remote controller inter unit wiring L1 L2 Ln Up to 200 m CAUTION The remote controller wire Communication line and AC 208 240 V wires cannot be parallel to contact each other and cannot be stored in the same conduits If doing so it may cause troubles on the control system due to ...

Страница 18: ...is part into the inside of the lower plate Remote controller wiring Strip off approx 9 mm the wire to be connected Wiring diagram A B A B Terminal block for remote controller wiring of indoor unit Remote controller wire Locally procured Remote controller unit Terminal block R L S N 10 10 20 30 Earth wire Power supply wire System interconnection wire and remote controller wires 2 mm or less See the...

Страница 19: ...utton to clear the display content and repeat the procedure from the beginning No operation of the remote controller is accepted for a while after button is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit Display content varies with the indoor unit model 2 Each time button is ...

Страница 20: ...n procedure 1 2 3 4 5 6 y For the CODE No in Procedure 3 specify 06 y For the SET DATA in Procedure 4 select the SET DATA of shift value of detection temperature to be set up from the following table SET DATA Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C Remote controller sensor The temperature sensor of the indoor unit senses...

Страница 21: ...for cases other than the test run because it applies an excessive load to the devices Wired remote controller 2 4 3 1 5 1 Push button for 4 seconds or more TEST is displayed on the display part and the selection of mode in the test mode is permitted 2 Push button 3 Select the operation mode with button Cool or Heat y Do not run the air conditioner in a mode other than Cool or Heat y The temperatur...

Страница 22: ...rmal sound is generated Filter sold separately Indoor Dust dirt breakage y Wash the filter with water when it is contaminated y Replace it when it is damaged Fan Indoor y Vibration balance y Dust dirt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them ...

Страница 23: ...rror between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units l F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side l F E08 E08 Dupl...

Страница 24: ... pressure sensor miswiring Pd Ps l F F22 F22 ALT TD3 sensor error l F F23 F23 ALT Ps sensor error l F F24 F24 ALT Pd sensor error l F F29 SIM Indoor unit other error Indoor unit H01 H01 01 Comp 1 side 02 Comp 2 side Compressor break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side Current detect circuit system error IPDU H04 H04 Com...

Страница 25: ...LT Discharge temp TD1 error l F P04 Р04 01 Comp 1 side 02 Comp 2 side ALT High pressure SW system operation IPDU P05 Р05 00 01 Comp 1 side 02 Comp 2 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp l F P07 Р07 01 Comp 1 side 02 Comp 2 side ALT Heat sink overheat error IPDU l F P10 Р10 Detected indo...

Страница 26: ...ressor 1 and 2 Fan 2 error 18 Fan 1 and 2 error 19 Compressor 1 Fan 1 and 2 error 1A Compressor 2 Fan 1 and 2 error 1B All Error detected by ТСС LINK central control device Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending...

Страница 27: ...name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law Complies with the provisions of the following harmonized standard EN 378 2 2008 A2 2012 Declaration of incorpor...

Страница 28: ...r unit installed room m3 Concentration limit kg m3 The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m q NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device e g charged amount 10 kg e g charged amount 15 kg Outdoor unit Indoor unit Room A Room B Room C Room D...

Страница 29: ...ressure CODE NO 5d NO CHANGE STANDARD 0000 STATIC 1 0001 STATIC 2 0002 STATIC 3 0003 STATIC 4 0004 STATIC 5 0005 STATIC 6 0006 External static pressure CODE NO 5d NO CHANGE STANDARD 0000 STATIC 1 0001 STATIC 2 0002 STATIC 3 0003 STATIC 4 0004 STATIC 5 0005 STATIC 6 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respecti...

Страница 30: ...1116950195 1 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...

Отзывы: