Check method (The following check code table explain in SMMS-e.)

On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation
is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the following table.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.

 

y

In case of check from indoor remote controller: See “Wired remote controller display” in the list.

 

y

In case of check from outdoor unit: See “Outdoor unit 7-segment display” in the list.

 

y

In case of check from indoor unit with a wireless remote controller: See “Sensor block display of receiving unit” in the list.

 : Lighting,    : Flashing,    : Goes off

IPDU: Intelligent Power Drive Unit

ALT: Flashing is alternately when there are two 

fl

ashing LED.

SIM: Simultaneous 

fl

ashing when there are two 

fl

ashing LED.

Check code

Wireless remote controller

Check code name

Judging device

Wired remote 

controller display

Outdoor unit 7-segment display

Sensor block display of receiving unit

Auxiliary code

Operation

Timer

Ready

Flash

E01

Communication error between indoor unit and remote controller 
(Detected at remote controller side)

Remote controller

E02

Remote controller transmission error

Remote controller

E03

Communication error between indoor unit and remote controller 
(Detected at indoor unit side)

Indoor unit

E04

Communication circuit error between indoor/outdoor unit (Detected 
at indoor unit side)

Indoor unit

E06

E06

No. of indoor units in which sensor has been normally received

Decrease of No. of indoor units

l/F

E07

Communication circuit error between indoor/outdoor unit (Detected 
at outdoor unit side)

l/F

E08

E08

Duplicated indoor unit addresses

Duplicated indoor unit addresses

Indoor unit • l/F

E09

Duplicated master remote controllers

Remote controller

Е

10

Communication error between indoor unit MC

Indoor unit

E12

E12

01: Indoor/Outdoor units communication 
02: Outdoor/Outdoor units communication

Automatic address start error

l/F

E15

E15

No indoor unit during automatic addressing

l/F

E16

E16

00: Capacity over 
01 ~: No. of connected units

Capacity over / No. of connected indoor units

l/F

E18

Communication error between header and follower units Indoor unit

Indoor unit

E19

E19

00: No header
02: Two or more header units

Outdoor header units quantity error

l/F

E20

E20

01: Outdoor unit of other line connected 
02: Indoor unit of other line connected

Other line connected during automatic address

l/F

E21

E21

02: No header unit
00: Multiple number of header units

Error in number of heat storage master units

l/F

E22

E22

Reduction in number of heat storage units

l/F

E23

E23

Sending error in communication between outdoor units 
Error in number of heat storage units (trouble with reception)

l/F

E25

E25

Duplicated follower outdoor addresses

l/F

E26

E26

No. of outdoor units which received signal normally

Decrease of No. of connected outdoor units

l/F

E28

E28

Detected outdoor unit number

Follower outdoor unit error

l/F

E31

E31

Number of IPDU (*1)

IPDU communication error

l/F

Содержание MMD-AP0726HP-E

Страница 1: ...AIR CONDITIONER MULTI TYPE Installation Manual Indoor Unit Model name For commercial use English Concealed Duct High Static Pressure Type MMD AP0726HP E MMD AP0966HP E 1116950195 1 ...

Страница 2: ... made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporat...

Страница 3: ...rom heat Center of gravity Unit mm Use forklift to carry in the air conditioner units and use winch or hoist at installation of them 665 220 435 Center of gravity Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric ...

Страница 4: ... by mistake 1 Precautions for safety Only a qualified installer 1 or qualified service person 1 is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work Wear protective gloves and safety work clothing during installation servicing and removal Do not touch the aluminium fin of the unit You may injure yourself if you d...

Страница 5: ...tion Installation Suction duct length must be longer than 850 mm When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in injury Follow the instructions in the Installation Man...

Страница 6: ... earth wire Grounding work Incomplete grounding causes an electric shock Do not connect earth wires to gas pipes water pipes and lightning conductor or telephone earth wires After completing the repair or relocation work check that the earth wires are connected properly Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations ...

Страница 7: ...pe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupture injury or other trouble CAUTION New refrigerant air conditioner installation This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer T...

Страница 8: ...hens where food oils are used Blocked filters may cause the air conditioner s performance to deteriorate condensation to form the plastic parts to be damaged and other such problems to result y Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to de...

Страница 9: ...rature 24 C wet bulb temperature Air volume Low air volume operation time 4 hours Installation space Unit mm Reserve sufficient space required for installation or service work 1 1 1 1 1 If there are enough space under the unit more than 1000mm the service door Ceiling opening is not necessary Space required for installation and servicing Ceiling 200 or more 25 1450 25 2500 or more Floor surface Se...

Страница 10: ...nit Procure hanging bolts washer and nuts for installing the indoor unit these are not supplied Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Washer M10 8 pieces Installation of hanging bolt Use M10 hanging bolts 4 pcs locally procured Matching to the existing structure set pitch according to size in the unit external view as shown below New concrete slab Install the bolts with inser...

Страница 11: ... at intervals of 1 5 to 2 meters to prevent flapping y Install the collective piping as shown in the following figure y Do not provide any air vents Otherwise the drain water will spout causing water to leak y Do not allow any force to be applied to the connection area with the drain pipe Heat insulator Downward slope 1 50 to 1 100 or more Support bracket As long as possible VP 30 Arched shape Tra...

Страница 12: ...k remove the access panel and pour water then conduct the drain check Access plate Pour into the drain pan Heat insulating process y As shown in the figure cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit tightly y Cover the drain pipe tightly with a heat insulator procured locally so that it overlaps with the attached heat insulator of the...

Страница 13: ...h Air Flow m h Air Flow m h Standard Air Flow 3800 m h Standard Air Flow 3800 m h Standard Air Flow 4800 m h Standard Air Flow 4800 m h Mid 83Pa Mid 83Pa Mid 83Pa Mid 83Pa Mid 50Pa Mid 50Pa Mid 50Pa Mid 50Pa Mid 150Pa 117Pa Mid 150Pa 117Pa Mid 150Pa 117Pa Mid 150Pa 117Pa Mid 183Pa Mid 183Pa Mid 183Pa Mid 183Pa Mid 217Pa Mid 217Pa Mid 217Pa Mid 217Pa Mid 250Pa Mid 250Pa Mid 250Pa Mid 250Pa Low Low ...

Страница 14: ... conditioner to fail or to leak Overview of duct connection NOTE Parts except air conditioner unit are to be locally procured Canvas joint Canvas joint Silencer chamber Air inlet Air filter Silencer chamber Air supply port Check port Air Conditioner Arrangement Unit mm Referring to the following dimensions manufacture duct at the local site Thickness of plate 0 8 mm 0 0 1 0 0 1 0 0 1 0 0 1 0 0 1 0...

Страница 15: ...per pipe gauge is useful for adjusting projection margin size A Tightening connection CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Unit N m Outer dia of copper pipe Tightening torque 12 7 mm dia 50 to 62 5 0 to 6 2 kgf m q Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torq...

Страница 16: ...ctric wiring with the high temperature part of the pipe It causes the coating melted REQUIREMENT y For power supply wiring strictly conform to the Local Regulation in each country y For wiring of power supply of the outdoor units follow the Installation Manual of each outdoor unit y After connecting wires to the terminal blocks provide a trap and fix wires with the cord clamp y Run the refrigerant...

Страница 17: ...ng L L1 L2 Ln In case of wired type only Up to 500 m In case of wireless type included Up to 400 m Total wire length of remote controller inter unit wiring L1 L2 Ln Up to 200 m CAUTION The remote controller wire Communication line and AC 208 240 V wires cannot be parallel to contact each other and cannot be stored in the same conduits If doing so it may cause troubles on the control system due to ...

Страница 18: ...is part into the inside of the lower plate Remote controller wiring Strip off approx 9 mm the wire to be connected Wiring diagram A B A B Terminal block for remote controller wiring of indoor unit Remote controller wire Locally procured Remote controller unit Terminal block R L S N 10 10 20 30 Earth wire Power supply wire System interconnection wire and remote controller wires 2 mm or less See the...

Страница 19: ...utton to clear the display content and repeat the procedure from the beginning No operation of the remote controller is accepted for a while after button is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit Display content varies with the indoor unit model 2 Each time button is ...

Страница 20: ...n procedure 1 2 3 4 5 6 y For the CODE No in Procedure 3 specify 06 y For the SET DATA in Procedure 4 select the SET DATA of shift value of detection temperature to be set up from the following table SET DATA Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C Remote controller sensor The temperature sensor of the indoor unit senses...

Страница 21: ...for cases other than the test run because it applies an excessive load to the devices Wired remote controller 2 4 3 1 5 1 Push button for 4 seconds or more TEST is displayed on the display part and the selection of mode in the test mode is permitted 2 Push button 3 Select the operation mode with button Cool or Heat y Do not run the air conditioner in a mode other than Cool or Heat y The temperatur...

Страница 22: ...rmal sound is generated Filter sold separately Indoor Dust dirt breakage y Wash the filter with water when it is contaminated y Replace it when it is damaged Fan Indoor y Vibration balance y Dust dirt appearance y Replace the fan when vibration or balance is terrible y Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them ...

Страница 23: ...rror between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units l F E07 Communication circuit error between indoor outdoor unit Detected at outdoor unit side l F E08 E08 Dupl...

Страница 24: ... pressure sensor miswiring Pd Ps l F F22 F22 ALT TD3 sensor error l F F23 F23 ALT Ps sensor error l F F24 F24 ALT Pd sensor error l F F29 SIM Indoor unit other error Indoor unit H01 H01 01 Comp 1 side 02 Comp 2 side Compressor break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side Current detect circuit system error IPDU H04 H04 Com...

Страница 25: ...LT Discharge temp TD1 error l F P04 Р04 01 Comp 1 side 02 Comp 2 side ALT High pressure SW system operation IPDU P05 Р05 00 01 Comp 1 side 02 Comp 2 side ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp l F P07 Р07 01 Comp 1 side 02 Comp 2 side ALT Heat sink overheat error IPDU l F P10 Р10 Detected indo...

Страница 26: ...ressor 1 and 2 Fan 2 error 18 Fan 1 and 2 error 19 Compressor 1 Fan 1 and 2 error 1A Compressor 2 Fan 1 and 2 error 1B All Error detected by ТСС LINK central control device Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending...

Страница 27: ...name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of the Machinery Directive Directive 2006 42 EC and the regulations transposing into national law Complies with the provisions of the following harmonized standard EN 378 2 2008 A2 2012 Declaration of incorpor...

Страница 28: ...r unit installed room m3 Concentration limit kg m3 The concentration limit of R410A which is used in multi air conditioners is 0 3 kg m q NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device e g charged amount 10 kg e g charged amount 15 kg Outdoor unit Indoor unit Room A Room B Room C Room D...

Страница 29: ...ressure CODE NO 5d NO CHANGE STANDARD 0000 STATIC 1 0001 STATIC 2 0002 STATIC 3 0003 STATIC 4 0004 STATIC 5 0005 STATIC 6 0006 External static pressure CODE NO 5d NO CHANGE STANDARD 0000 STATIC 1 0001 STATIC 2 0002 STATIC 3 0003 STATIC 4 0004 STATIC 5 0005 STATIC 6 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respecti...

Страница 30: ...1116950195 1 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...

Отзывы: