– 57 –
Check code
Display of receiving unit
Typical
problem
site
Description of
proplem
Outdoor 7-segment display
TCC-LINK
central control
or main remote
control
display
Indicator light block
Sub-code
Flash
F13
T
L
A
3
1
F
Trouble in temperature
sensor built into indoor
IPM
(TH)
Temperature sensor built into indoor
IPM
(TH)
has been open/short-circuited.
H01
01: Compressor 1
02: Compressor 2
03: Compressor 3
n
w
o
d
k
a
e
r
b
r
o
s
s
e
r
p
m
o
C
1
0
H
Inverter current (Idc) detection circuit detects
overcurrent.
H02
01: Compressor 1
02: Compressor 2
03: Compressor 3
H02
Compressor trouble
(lockup)
Compressor lockup is detected
H03
01: Compressor 1
02: Compressor 2
03: Compressor 3
H03
Current detection circuit
trouble
Abnormal current is detected while inverter
compressor is turned off.
P04
01: Compressor 1
02: Compressor 2
03: Compressor 3
T
L
A
4
0
P
Activation of high-pressure
SW
High-pressure SW is activated.
P07
01: Compressor 1
02: Compressor 2
03: Compressor 3
T
L
A
7
0
P
Heat sink overheating
trouble
Temperature sensor built into
IPM
(TH) detects
overheating
or has been short-circuited.
P22
#0:Element short circuit
#1:Position detection circuit trouble
#3:Motor lock trouble
#4:Motor current trouble
#C:TH Sensor temperature trouble
#D:TH Sensor short circuit/release
trouble
#E:Vdc voltage trouble
∗
Put in Fan IPDU No. in [#] mark
Outdoor fan IPDU detects trouble.
Outdoor fan IPDU trouble
T
L
A
2
2
P
P26
T
L
A
6
2
P
Activation of
IPM
short-circuit protection
Short-circuit protection for compressor motor
driver circuit components is activated (momentary
overcurrent).
P29
T
L
A
9
2
P
Compressor position
detection circuit trouble
Compressor motor position detection trouble is
detected.
01: Compressor 1
02: Compressor 2
03: Compressor 3
01: Compressor 1
02: Compressor 2
03: Compressor 3
01: Compressor 1
02: Compressor 2
03: Compressor 3
Operation Timer Ready
(Check code detected by IPDU featuring in SMMS-e and SMMS-i outdoor unit)
Note:
The above check codes are examples only, and different check codes may be displayed depending on
the outdoor unit configuration