– 41 –
(Example of 2-lines cabling)
(Real line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by connecting singly the
wired remote control without remote control inter-unit cable.
Group address
Individual
: 0000
Header unit : 0001
Follower unit : 0002 In case of group control
Outdoor
Outdoor
Indoor
Indoor
Indoor
Indoor
Indoor
Header unit
Follower
unit
Line address 1
Indoor unit address 1
Group address 1
1
2
2
1
3
2
2
1
2
2
2
2
<Operation procedure>
1 2 3 4 5 6
1
7 8 9 10 11
END
END
11
2, 5, 8
3, 6, 9
4, 7, 10
TEMP.
ON / OFF
SET
TIME
TEST
FILTER
RESET
CL
SAVE
SWING/FIX
VENT
UNIT LOUVER
CODE No.
UNIT No.
R.C.
R
No.
TIMER SET
MODE
FAN
SET DATA
TEST
SETTING
00 0 1
A LL
10
Address setup (Manual setting from Wired remote control)
In case that addresses of the indoor units will be determined prior to piping work after wiring work
• Set an indoor unit per a remote control.
• Turn on power supply.
1
Push + + buttons
simultaneously for 4 seconds or more.
2
(Line address)
Using the temperature setup
/
buttons, set
12
12
12
12
12
to the CODE No.
3
Using timer time
/
buttons, set
the line address.
4
Push button. (OK when display goes
on.)
5
(Indoor unit address)
Using the temperature setup
/
buttons, set
13
13
13
13
13
to the CODE No.
6
Using timer time
/
buttons, set 1
to the line address.
7
Push button. (OK when display goes
on.)
8
(Group address)
Using the temperature setup
/
buttons, set
14
14
14
14
14
to the CODE No.
9
Using timer time
/
buttons, set
0000
0000
0000
0000
0000
to Individual,
0001
0001
0001
0001
0001
to
Header unit and
0002
0002
0002
0002
0002
to follower unit.
10
Push button.
(OK when display goes on.)
11
Push button.
Setup completes.
(The status returns to the usual stop status.)
Note 1)
When setting the line address from the remote control, do not use Address 29 and 30.
As they are addresses which cannot be set to the outdoor unit, if they are set, the check code [E04] (Indoor/
Outdoor communication circuit trouble) is issued.
Note 2)
When an address was manually set from the remote control and the central control over the refrigerant lines is
carried out, perform the following setting for the Header unit of each line.
• Set the line address for every line using SW13 and 14 on the interface P.C. board of the Header unit in each
line.
• Except the least line address No., turn off SW30-2 on the interface P.C. board of the Header units in the lines
connected to the identical central control.
(Draw the terminal resistances of indoor/outdoor and central control line wirings together.)
• For each refrigerant line, connect the relay connector between Header unit [U1U2] and [U3U4] terminals.
• After this, set the central control address.
(For setting of the central control address, refer to the Installation manual for the central control equipment.)