– 48 –
CODE No.
Data name
Display format
Unit
Remote control display example
Indoor unit data *
3
Outdoor unit individual data 1 *
4
System
data
00
01
02
03
04
05
06
08
F3
0A
0B
0C
0D
Room temperature(Use to control)
Room temperature(Remote control)
Indoor suction air temperature (TA)*
1
Indoor coil temperature (TCJ)*
1
Indoor coil temperature (TC2)*
1
Indoor coil temperature (TC1)*
1
Indoor discharge air temperature (TF)*
2
Indoor PMV opening
Filter sign time
No. of connected indoor units
Total capacity of connected indoor units
No. of connected outdoor units
Total capacity of connected outdoor units
×1
×1
×1
×1
×1
×1
×1
×1/10
×1
×1
×10
×1
×10
°C
°C
°F
°F
°F
°F
°F
pls
h
unit
ton
unit
ton
[0027] = 27°C
[0080] = 80°F
[0150] = 1500pls
[2500] = 2500h
[0048] = 48units
[0215] = 21.5ton
[0003] = 3units
[0160] = 16ton
CODE No.
Data name
Display format
Unit
Remote control display example
U1
10
11
12
13
15
16
17
18
19
1A
1C
1D
1E
1F
U2
20
21
22
23
25
26
27
28
29
2A
2C
2D
2E
2F
U3
30
31
32
33
35
36
37
38
39
3A
3C
3D
3E
3F
High-pressure sensor detention pressure (Pd)
Low-pressure sensor detention pressure (Ps)
Compressor 1 discharge temperature (TD1)
Compressor 2 discharge temperature (TD2)
Outdoor coil temperature (TE1)
Outdoor coil temperature (TE2)
Outdoor coil temperature (TG1)
Outdoor coil temperature (TG2)
Outside ambient temperature (TO)
Suction temperature (TS1)
Suction temperature (TS3)
Temperature at liquid side (TL1)
Temperature at liquid side (TL2)
Temperature at liquid side (TL3)
×10
×10
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
×1
psi
psi
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
[4350] = 435 psi
[0080]= 80 °F
Outdoor unit individual data 2 *
4
CODE No.
Data name
Display format
Unit
Remote control display example
U1
50
51
52
U2
60
61
62
U3
70
71
72
PMV1 opening
PMV3 opening
PMV4 opening
[0500] = 500pls
[0058] = 58 mode
[0080] = 8 ton
[0010]=Heating recovery controlled
[0010]=Pressure release controlled
[0001]=Discharge temperature release controlled
[0100]=U2 outdoor unit release controlled
[0024] = 24 oF
[0642] = 64.2rps
[0135] = 13.5A
×1
×1
×1
pls
pls
pls
56
57
59
5A
5B
5D
5E
5F
90
91
92
93
66
67
69
6A
6B
6D
6E
6F
–
–
–
–
76
77
79
7A
7B
7D
7E
7F
–
–
–
–
Compressor 1 revolutions
Compressor 2 revolutions
Outdoor fan mode
Compressor IPDU 1 heat sink temperature
Compressor IPDU 2 heat sink temperature
Outdoor fan IPDU 1 heat sink temperature
Outdoor fan IPDU 2 heat sink temperature
Outdoor unit capacity
Heating/cooling recovery controlled
Pressure release
Pressure release
Follower unit release (U2/U3 outdoor units)
×10
×10
×1
×1
×1
×1
×1
×10
0:Normal
0:Normal
1:Release controlled
rps
rps
mode
°F
°F
°F
°F
ton
54 64 74
1 fan model : Compressor 2 and Outdoor fan 1 current (I2)
2 fan model : Compressor 2 and Outdoor fan 2 current (I2)
×10
A
53 63 73
1 fan model : Compressor 1 curent (I1)
2 fan model : Compressor 1 and Outdoor fan 1 current (I1)
×10
A
< Based on the SMMS-e >
*1 The Outside Air Unit uses the revised sensor data, therefore the data below are not correctly displayed
because they are revised sensor data.
Indoor suction air temperature (TA)
Indoor coil temperature (TCJ)
Indoor coil temperature (TC2)
Indoor coil temperature (TC1)
*2 Only a part of indoor unit types is installed with the discharge air temperature sensor. This temperature is
not displayed for other types.
*3 When the units are connected to a group, data of the header indoor unit only can be displayed.
*4 The indications, U1, U2, U3 indicate the following outdoor units, respectively. For the indication data of each
outdoor unit, check CODE No.
U1...outdoor unit (Header unit)
U2...outdoor unit (Follower unit 1)
U3...outdoor unit (Follower unit 2)