2. SPACIFICATIONS
Outside Air Unit
* The setting temperature is 60 - 80 °F.
* Height difference between Outside Air Units must be within 1.97"(0.5 m).
Note 1
: Rated conditions
Cooling : Outdoor air temperature 91 °F DB/82 °F WB setting temperature 64 °F
Heating : Outdoor air temperature 32 °F DB/26 °F WB setting temperature 77 °F
Note 2
: * When supply air temperature is “setting tempe 5.4 °F” or less, Outside Air Unit operates as
FAN mode.
Note 3
: * When supply air temperature is “setting temperature - 5.4 °F” or over, Outside Air Unit operates as
FAN mode.
Model name
MMD-
AP0481HF2UL
AP0721HF2UL
AP0961HF2UL
Cooling capacity
(Note1)
kBtu/h
48.0
72.0
96.0
Heating capacity
(Note1)
kBtu/h
30.0
47.0
59.0
Sound pressure level
208V(H / M / L)
dB(A)
44/43/36
47/46/40
47/45
(H/L)
230V(H / M / L)
dB(A)
46/45/42
48/47/46
50/49
(H/L)
Operation
range for SMMS-i
Cooling (Note 2)
°F
41 - 109
Heating (Note 3)
°F
23 - 109
Operation
range for SMMS-e
Cooling (Note 2)
°F
41 - 115
Heating (Note 3)
°F
23 - 109
Connecting
pipe
Gas pipe
In
5/8"
7/8"
Liquid pipe
In
3/8"
1/2"
Drain pipe
In
VP25
(Polyvinyl chloride tube : External Dia.1-1/4 internal Dia.1)
Externalstatic
pressure
208V(H / M / L)
In WG
0.75/0.55/0.16
0.84/0.74/0.24
0.67/0.41
(H/L)
230V(H / M / L)
In WG
1.06/0.86/0.50
1.08/1.00/0.65
1.01/0.85
(H/L)
Air flow limit
Lower limit
cfm
445
693
866
Upper limit
cfm
700
1088
1360
External static pressure
(factory default)
208V/230V
In WG
0.55/0.86
0.74/1.00
0.41/0.85
Standard air flow
cfm
636
989
1237
Motor
W
160
160x2
Heat exchanger
Finned tube
Soundproof / Heat-insulationg material
Non-flammable insulation
Air filter
Field supply
Control
Wired remote control
Fan
Centrifugal fan
Main unit weight
lbs
212
349
Running current
A
1.58/1.56
3.00/2.88
3.32/3.17
Power consumption
kW
0.31/0.34
0.56/0.58
0.64/0.66
Starting current
A
3.90/3.20
7.70/6.30
8.50/6.90
Electical
characteristics
Power supply
230V (208/230V) 1phase
Width
In
35.4"
55"
Depth
In
49.8"
Outer
dimension
Height
In
19.5"