5
Installation space
• Make space for installation and service. (Make space to the electrical parts box cover side for service.)
• When installing the unit inside the ceiling, be sure to create a check port.
The check port is required when the unit is installed and serviced. (Check port: 450 × 450 or more)
• Keep a clearance of 50mm or more between the top panel of the unit and the ceiling.
• The length of a connection pipe to the indoor unit should be 2 m to 10 m.
Installation space
RBM-PMV0361E, RBM-PMV0901E
3
SELECTION OF INSTALLATION PLACE
RBM-PMV0901E (When attached joint is used)
500 or more
200 or more
50 or more
50 or more
50 or more
50 or mor
50 or more
200 or more
200 or more
200 or more
73
55
73
55
Box cover
Check port
450 × 450