28
Side blow VRF Data book
5
Outdoor unit
5-1. Specifications
(*1) Rated conditions Cooling : Indoor 27 degC Dry Bulb / 19 degC Wet Bulb, Outdoor 35 degC Dry Bulb.
Heating : Indoor 20 degC Dry Bulb, Outdoor 7 degC Dry Bulb / 6 degC Wet Bulb.
The standard pipe means that equivalent piping length of 7.5 m and standard 0 m piping height difference.
(*2) The source voltage must not fluctuate more than ±10%.
(*3) The amount dose not consider extra piping length and indoor unit type.
Refrigerant must be added on site in accordance with the actual piping length and indoor unit type.
(*4) Discharge temp. sensor / Suction temp. sensor / High-pressure sensor / Low-pressure sensor / Compressor case thermostat / PC board fuse
(*5) Select wire size base on the large value of MCA.
MCA : Minimum Circuit Amps
(*6) MOCP Maximum Overcurrent Protection (Amps)
Outdoor unit model name
MCY-MHP0404HT-E
MCY-MHP0504HT-E
MCY-MHP0604HT-E
Outdoor unit type
Inverter
Inverter
Inverter
Capacity code
HP
4
5
6
Cooling Capacity
(*1)
kW
12.1
14.0
15.5
Heating Capacity
(*1)
kW
12.5
16.0
18.0
Electrical
characteristics
(Nominal) (*1)
Power supply
(*2)
1phase 50Hz 220 / 230 / 240V
1phase 50Hz 220 / 230 / 240V
1phase 50Hz 220 / 230 / 240V
Cooling
Running current
A
13.9 / 13.3 / 12.8
16.7 / 16.0 / 15.4
20.6 / 19.7 / 18.9
Power consumption
kW
2.88
3.50
4.35
Power factor
%
94
95
96
EER
4.20
4.00
3.56
Heating
Running current
A
13.3 / 12.8 / 12.2
18.0 / 17.3 / 16.5
21.3 / 20.4 / 19.5
Power consumption
kW
2.73
3.81
4.50
Power factor
%
93
96
96
COP
4.58
4.20
4.00
Starting Current
A
Soft start
Soft start
Soft start
Dimension
Unit
Height
mm
1,235 1,235 1,235
Width
mm
990 990 990
Depth
mm
390 390 390
Packing
Height
mm
1,350 1,350 1,350
Width
mm
1,102 1,102 1,102
Depth
mm
552 552 552
Total Weight
Unit
kg
116
116
116
Packed unit
kg
124
124
124
Appearance (Color)
Silky shade
(Munsell 1Y8.5/0.5)
Silky shade
(Munsell 1Y8.5/0.5)
Silky shade
(Munsell 1Y8.5/0.5)
Compressor
Type
Hermetic twin rotary compressor Hermetic twin rotary compressor Hermetic twin rotary compressor
Motor output
kW
3.75
3.75
3.75
Fan unit
Fan
Propeller fan (Quantity 2)
Propeller fan (Quantity 2)
Propeller fan (Quantity 2)
Motor output
W
100 + 100
100 + 100
100 + 100
Air volume
m
3
/h
6,030 6,210 6,410
Heat exchanger
Finned tube
Finned tube
Finned tube
Refrigerant R410A (Charged refrigerant amount (kg))
(*3)
3.9
3.9
3.9
Protective devices
(*4)
Electrical
specifications
Unit
MCA (*5)
A
23.5
26.5
28.0
MOCP (*6)
A
32.0
32.0
32.0
Refrigerant
piping
Connecting port
diameter
Gas side (main pipe)
mm
15.9
15.9
19.1
Liquid side (main pipe) mm
9.5
9.5
9.5
Connecting
method
Gas side
Flare
Flare
Flare
Liquid side
Flare
Flare
Flare
Max. No. of connected indoor units
6
6
6
Sound pressure level
Cooling dB(A)
50
51
52
Heating
dB(A)
52
54
55
Operation temperature range
Cooling
CDB
-5 to 43
-5 to 43
-5 to 43
Heating
CWB
-20 to 15
-20 to 15
-20 to 15