Equipment selection procedure
2-2. Combination conditions for indoor unit and outdoor unit
Indoor unit can connect 80 % to 130 % of Outdoor unit capacity.
2-2-1. For indoor unit, the capacity code is decided for each capacity rank.
NOTE:
Capacity rank : Correspondence to Btu/h. Capacity code : Correspondence to Horsepower.
*1 : Capacity code of 005 type is the same as 007 type.
2-2-2. For outdoor unit, maximum No. of connectable indoor units and total
capacity code of indoor units are decided.
Capacity rank type
005(*1)
007
008
009
010
012
014
015
017
018
020
024
027
030
036
048
056
Capacity
code
Equivalent to
HP
0.8
0.8
0.9
1.0
1.1
1.25
1.5
1.7
1.85
2.0
2.25
2.5
3.0
3.2
4.0
5.0
6.0
Outdoor unit
Capacity code of outdoor unit
No. of connectable indoor units
Total capacity code of indoor units
MCY-MHP0404HT*
4
2 to 6
3.2 to 5.2
MCY-MHP0504HT*
5
2 to 6
4.0 to 6.5
MCY-MHP0604HT*
6
2 to 6
4.8 to 7.8