GX7R ASD Quick Start Guide
5
Conductor Routing and Grounding
Precautions
•
Use separate metal conduits for routing the input power, output power, and control circuits.
•
A separate ground cable shall be run inside the conduit with the input power, output power, and
control circuits.
•
DO NOT
connect
CC
to earth ground.
•
Use the
CC
terminal as the return for analog input terminals
VI
,
RX
, and
RR
.
•
Use the
CC
terminal as the return for output terminals
FP
,
PP
, and
P24
.
•
Use the negative terminal of the
AM
,
FM
, and
II
terminals as the return for these analog I/O
signals.
•
Always ground the unit to prevent electrical shock and to help reduce electrical noise.
•
It is the responsibility of the ASD installer/maintenance personnel to provide proper grounding and
branch circuit protection in accordance with the
NEC
and any applicable local codes.
Neither Metal Conduit Nor Building Beams Are
Acceptable Grounds.
Power Connections Precautions
C O N T A C T W I T H E N E R G I Z E D W I R I N G W I L L C A U S E
S E V E R E I N J U R Y O R L O S S O F L I F E .
•
Turn off and lock-out/tag-out all power sources before connecting the power wiring to the
equipment.
•
Ensure that all power sources are turned off and isolated in accordance with established lock-out/
tag-out procedures before connecting the 3-phase power source wiring to the ASD input terminals
and connect the ASD output terminals to a motor of the correct voltage and type for the application
(refer to the NEC Article 300 – Wiring Methods and Article 310 – Conductors For General
Wiring). Size the branch circuit conductors in accordance with the NEC Table 310.16.
•
Ensure that the 3-phase input power is
NOT
connected to the output of the ASD. This will damage
the ASD and may cause injury to personnel.
•
If multiple conductors are used in parallel for the input or output power, each parallel set shall have
its own conduit and not share its conduit with other parallel sets (i.e., place U1, V1, W1, and a
ground wire in one conduit and U2, V2, W2 and a ground wire in another; refer to the NEC Article
300.20 and Article 310.4). National and local electrical codes shall be referenced if three or more
power conductors are run in the same conduit (refer to the NEC Article 310 adjustment factors).
Note:
National and local codes shall be referenced when running more than three
conductors in the same conduit.
WARNING
DANGER
Содержание GX7R ASD
Страница 1: ...GX7R ASD Quick Start Guide TOSHIBA GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Страница 2: ...GX7R ASD Quick Start Guide DN 68986 002 September 2014 ...
Страница 76: ...68 GX7R ASD Quick Start Guide Figure 23 480 Volt 30 100 HP GX7R ASD ...
Страница 77: ...GX7R ASD Quick Start Guide 69 Figure 24 480 Volt 125 150 HP GX7R ASD ...