9-5. Operation check by PC board switch
9-5-1. Operation check mode
This mode allows to check the operations of the water 2-way valve, water 3-way valve, mixing valve, and circulating
pump.
Operation check mode
(1) Preparation
• Turn all of the remote controls "OFF" for the hot water supply and heating.
• Turn off the hydro unit and the outdoor unit.
• Remove the front panel of the hydro unit.
(2) Operation check
1) Turn on the hydro unit and the outdoor unit.
2) Set SW06_2 to "ON".
3) Rotate switch SW01 to position "1" and press tactile switch SW07 for 5 sec. or longer.
4) Rotating the rotary SW01 allows to check each operation.
5) Set the DIP SW06 "OFF" to finish.
Rotary
switch
Check contents
Remark
1
None
2
2WV_W
Alive for approx. 2 sec, not alive for 3
sec
3
3WV_W
4
Mixing valve
Alive for 30 sec in the forward direction
Alive for 30 sec in the reverse direction
5
Built-in AC pump
Alive / not alive for 20 sec
6
Extended AC pump 1
Alive / not alive for 20 sec
7
(Extended AC pump 2)
Alive / not alive for 20 sec
Reserved
8
Water heat exchange backup
heater
Repeat heater 1, heater 2, and OFF
every 20 sec
The built-in AC pump operates.
9
Hot water cylinder heater
Alive / not alive for 10 sec
10
Backup heater
Alive / not alive for 10 sec
The built-in AC pump and external AC pump
operate.
11
Check the alarm output.
Output for 10 sec / no output for 10 sec
12
Check the boiler output.
Output for 10 sec / no output for 10 sec
13
Check the defrost output.
Output for 10 sec / no output for 10 sec
14
Check the operation output.
Output for 10 sec / no output for 10 sec
15
Built-in AC pump continuous
operation
Continuously alive
Do not operate the AC pump alive
continuously without any water in hydro unit.