107
Toshiba
Function code table
FC
Item
Details
First shipment
01
Water heat exchanger capacity
0012: 802XWH**-E
0017: 1402XWH**-E
Depends on type
02
Cooling/Non-cooling switching
0000: Cooling
0001: No cooling
0001: No cooling
07
Hot water HP operation mode upper time limit
0000: 0 mins
-
0120: 120 mins
0030: 30 mins
08
Hot Water Boost operation time
0003: 30 mins
-
0018: 180 mins
0006: 60 mins
09
Hot Water Boost set temperature
0040: 40°C
-
0080: 80°C
0075: 75°C
0A
Anti bacteria set temperature
0070: 70°C
-
0080: 80°C
0075: 75°C
0B
Anti bacteria holding time
0000: 0 mins
-
0060: 60 mins
0030: 30 mins
0C
Mixing valve drive time
0003: 30 secs
-
0024: 240 secs
0006: 60 secs
18
Upper limit of cooling set temperature
0018: 18°C
-
0030: 30°C
0025: 25°C
19
Lower limit of cooling set temperature
0010: 10°C
-
0018: 18°C
0010: 10°C
1A
Upper limit of heating (ZONE1) set temperature
0037: 37°C
-
0055: 55°C
0055: 55°C
1B
Lower limit of heating (ZONE1) set temperature
0020: 20°C
-
0037: 37°C
0020: 20°C
1C
Upper limit of heating (ZONE2) set temperature
0037: 37°C
-
0055: 55°C
0055: 55°C
1D
Lower limit of heating (ZONE2) set temperature
0020: 20°C
-
0037: 37°C
0020: 20°C
1E
Upper limit of hot water set temperature
0060: 60°C
-
0080: 80°C
0075: 75°C
1F
Lower limit of hot water set temperature
0040: 40°C
-
0060: 60°C
0040: 40°C
20
Hot water HP start temperature
0020: 20°C
-
0045: 45°C
0038: 38°C
21
Hot water HP stop temperature
0040: 40°C
-
0050: 50°C
0045: 45°C
22
Priority mode Hot water supply/Heating switching
temperature
-0020: -20°C
-
0020: 20°C
0000: 0°C
23
Priority mode Boiler/Heat pump switching temperature -0020: -20°C
-
0020: 20°C
-0010: -10°C
24
Outside air temperature for hot water temperature
correction start
-0020: -20°C
-
0010: 10°C
0000: 0°C
25
Hot water temperature correction value
0000: 0K
-
0015: 15K
0003: 3K
26
Night set back change temperature range
0003: 3K
-
0020: 20K
0005: 5K
27
Set temperature shift with heating Auto
-0005: -5K
-
0005: 5K
0000: 0K
29
Outside air temperature T1 temperature
-0015: -15°C
-
0000: 0°C
-0010: -10°C
2B
Outside air temperature T3 temperature
0000: 0°C
-
0015: 15°C
0010: 10°C
2C
Set temperature A with outside air temperature of -
20°C
0020: 20°C
-
0055: 55°C
0040: 40°C
2D
Set temperature B with outside air temperature of T1
0020: 20°C
-
0055: 55°C
0035: 35°C
2E
Set temperature C with outside air temperature of 0°C
0020: 20°C
-
0055: 55°C
0030: 30°C
2F
Set temperature D with outside air temperature of T3
0020: 20°C
-
0055: 55°C
0025: 25°C
30
Set temperature E with outside air temperature of 20°C
0020: 20°C
-
0055: 55°C
0020: 20°C
31
Zone2 ratio with Zone1 as Auto
0000: 0%
-
0100: 100%
0080: 80°C
33
Heater control down time
0000: 5 mins
0002: 15 mins
0001: 10 mins
0003: 20 mins
0001: 10 mins
34
Heater control up time
0000: 10 mins
0002: 30 mins
0001: 20 mins
0003: 40 mins
0000: 10 mins
3A
Frost protection function Yes/No
0000: No
0001: Yes
0001: Yes
3B
Frost protection set temperature
0010: 10°C
-
0020: 20°C
0015: 15°C
3C
Water 2-way energization (logical reverse) control
0000: No
0001: Yes (Reverse)
0000: No
3E
Heating HP/Boiler priority switching when using boiler
0000: Priority on HP
0001: Priority on boiler
0000: Priority on HP
+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 107 Monday, October 5, 2009 2:09 PM