NOTE
• Make sure that the setting is appropriate so that liquid can be charged.
• A cylinder with siphon enables liquid to be charged without the cylinder turned upside down.
NOTE
• Because R410A is HFC mixed refrigerant, charging with gas changes the charged refrigerant composition,
causing the equipment characteristics to change.
[Cylinder with siphon]
[Cylinder without siphon]
Gauge manifold
Outdoor unit
Refrigerant
cylinder
Electronic balance
Gauge manifold
Outdoor unit
Refrigerant
cylinder
Electronic balance
Siphon pipe