17
NPT
1
NPA
2
Units
Point Description
Range / Value
BI
15
--
“RES” input terminal status
0=terminal-CC open
1=terminal-CC shorted
BI
16
--
“ST” input terminal status
0=terminal-CC open
1=terminal-CC shorted
BI
17
--
“FL” output contacts status
0=FLB-FLC shorted
1=FLA-FLC shorted
BI
18
--
“RCH” output status
0=RCH OFF
1=RCH ON
BI
19
--
“LOW” output contacts status
0=LOWA-LOWC open
1=LOWA-LOWC shorted
AO
1
Hz
Frequency command
0.00 Hz
∼
400.00 Hz
AO
2
Sec
Acceleration time #1
0.01
∼
600.00 / 0.1
∼
6000.0
AO
3
Sec
Deceleration time #1
0.01
∼
600.00 / 0.1
∼
6000.0
AO
4
%
Stall protection current level
10
∼
215
AO
5
--
Command mode selection
0
∼
4
AO
6
--
Frequency mode selection
0
∼
4
AO
7
--
Proportional gain
0.01
∼
2.55
AO
8
--
Integral gain
0.01
∼
360.00
AO
9
Hz
PID lower limit frequency
0
∼
FH
AO
10
%
PID deviation upper limit
0
∼
50
AO
11
%
PID deviation lower limit
0
∼
50
AO
12
Sec
Loss of comm. timeout time
0.100
∼
60.000
AO
13
--
Loss of comm. timeout action
0
∼
4
BO
1
--
Run / stop command
0=stop
1=run
BO
2
--
Forward / reverse selection
0=reverse
1=forward
BO
3
--
Acceleration/deceleration #1/#2
selection
0=accel/decel #1
1=accel/decel #2
BO
4
--
Compulsory DC injection braking
mode selection
0= no compuls ory braking
1=compulsory DC inj. braking
below DC injection starting
frequency (
dbF
in
Gr.Pr
)
BO
5
--
Gate block (coast stop) command
0=no gate block
1=gate block
BO
6
--
Emergency off command
0=no action
1=emergency off
BO
7
--
Fault reset command
0=no action
1=reset
BO
8
--
Feedback control enable selection
0=feedback valid
1=feedback invalid
BO
9
--
Feedback control selection
0=no feedback
1=PID feedback control
BO
10
--
PID deviation limit selection
0=PID deviation limit disabled
1=PID deviation limit enabled
[NOTE 1]:
NPT = Network Point Type.
[NOTE 2]:
NPA = Network Point Address.