16
8.2 I/O Point Map
NPT
1
NPA
2
Units
Point Description
Range / Value
AI
1
Hz
Output frequency
0.00
∼
400.00
AI
2
%
Output current
0
∼
255
AI
3
%
Output voltage
0.0
∼
232.0
AI
4
%
Input voltage
0.0
∼
255.0
AI
5
%
IV terminal analog input value
0.00
∼
100.00
AI
6
%
RR terminal analog input value
0.00
∼
100.00
AI
7
%
RX terminal analog input value
-100.00
∼
100.00
AI
8
kW
Input power
0.0
∼
6553.4
AI
9
kW
Output power
-3276.8
∼
3276.7
AI
10
kWh
System energy (KWh)
0
∼
999.9
AI
11
MWh
System energy (MWh)
0
∼
65534
AI
12
--
Present fault
0
∼
82
AI
13
--
Past fault #1 (newest)
0
∼
82
AI
14
--
Past fault #2
0
∼
82
AI
15
--
Past fault #3
0
∼
82
AI
16
--
Past fault #4 (oldest)
0
∼
82
BI
1
--
Run / stop status
0=stopped
1=running
BI
2
--
Forward / reverse status
0=reverse
1=forward
BI
3
--
Acceleration/deceleration #1/#2
selection status
0=accel/decel #1
1=accel/decel #2
BI
4
--
Compulsory DC injection braking
mode status
0=inactive
1=active
BI
5
--
Coast stop command status
0=normal
1=coast to stop
BI
6
--
Emergency off status
0=normal
1=emergency off
BI
7
--
Fault status
0=EIII not faulted
1=EIII faulted
BI
8
--
Feedback control enable status
0=feedback invalid
1=feedback valid
BI
9
--
“F” input terminal status
0=terminal-CC open
1=terminal-CC shorted
BI
10
--
“R” input terminal status
0=terminal-CC open
1=terminal-CC shorted
BI
11
--
“S1” input terminal status
0=terminal-CC open
1=terminal-CC shorted
BI
12
--
“S2” input terminal status
0=terminal-CC open
1=terminal-CC shorted
BI
13
--
“S3” input terminal status
0=terminal-CC open
1=terminal-CC shorted
BI
14
--
“S4” input terminal status
0=terminal-CC open
1=terminal-CC shorted
Содержание E3