Digital Input / Output Relay Interface
Installation Manual
6
Setting
The following settings are necessary to use Digital Input / Output Relay Interfaces.
• SW1 Address set switch
When two or more Digital Input / Output Relay Interfaces are used, set a different address for each unit
to avoid address duplication.
Assign addresses in ascending order.
CAUTION
•
When the SW1 setting has been changed, push the reset switch SW6. The new address setting is read.
•
Address of Digital Input / Output Relay Interface can be set independently from Energy Monitoring Relay
Interface.
• SW2 Operation mode set switch
• SW3 Test switch
• SW4 Test switch
These switches are not used during normal operation. Set zero (0) or “all
OFF”.
• SW6 Reset switch
When performing an address setting with SW1, push this reset switch after the address setting to read
the set value.
• SW7 RS-485 terminator resistor select switch
Terminator resistor of RS-485 must be set on Energy Monitoring Relay Interface.
When Digital Input / Output Relay Interface is used without Energy Monitoring Relay Interface, set it
[120 ohm] on Digital Input / Output Relay Interface with address SW1=1 and, set it [Open] on the other
Interfaces.
L
N
BA
S
G
RS-485
DI
1
DI
6
DI
2
DI
4
DI
3
DI
7
DI
8
DI
5
1 2 3 4
LED1
LED2
LED3
LED4
LED5
SW1
SW2
SW3
SW4
SW6
SW7
12 V
GND
DO1
DO2
DO3
DO4
LED6
LED7
LED8
LED9
+ -
+ -
+ -
+ -
+ -
+ -
+ -
+ -
SW1
Address set switch
1-8
Address
0, 9-F
Not used
SW2
Operating mode set switch (0 usually)
SW3
Test switch (all OFF usually)
SW4
Test switch
SW6
Reset switch
SW7
RS-485 terminator resistor select switch
120 ohm
Open
LED1
Power indicator
LED2
RS-485 communication status indicator
LED3
Not used
LED4
Test indicator
LED5
Test indicator
LED6 -LED9
Digital output indicator
ON
ON