background image

Toshiba

– 5 –

Digital Input / Output Relay Interface

Installation Manual

5

Connection of power cables / earth wires / 

communication cables

CAUTION

• The RS-485 communication cable has polarity. Connect A to A, and B to B. If connected with incorrect polarity, the 

unit will not work.

Power cables / earth wires / communication cables

Connect power cables, earth wires, and communication cables to the specified terminals on the terminal block.

REQUIREMENT

Disconnect the appliance from the main power supply.

This appliance must be connected to the main power supply by a circuit breaker or switch with a contact separation 
of at least 3 mm.

Fasten the screws to the terminal with torque of 0.5 Nm.

LN

 

B
A

SG

RS-485

 

DI

1

D

I6

DI

2

DI

4

DI

3

D

I7
DI

8

DI

5

1 2 3 4

LED1

LED2

LED3

LED4

LED5

SW1

SW2

SW3

SW4

SW6

SW7

12V 
GND 
DO1 
DO2 
DO3 
DO4

LED6

LED7

LED8

LED9

1.38"

(35)

1.38"

(35)

1.38"

(35)

0.24" (6)

0.39" (10)

2.17"

(55)

0.39" (10)

+ -+

 -+

 -+

 -+

 -+

 -+

 -+

 -

0.24" (6)

Power supply

120 VAC, 60 Hz

Length of stripped 

power cable

Length of stripped 

communication cable

Digital input

contacts

Smart BMS

Manager

Digital

output

load

Length of stripped digital 

Input / Output connector wire

Insert the wire by pushing 

the lever with a 

screwdriver. Check that the 

wire is inserted securely.

When inserting two RS-485 

communication cables into a single 

terminal for connection to another 

interface, crimp them using the 

attached pin terminal.

Secure each cable with a 

cable clamp.

Connect the earth 

wire to the earth 

terminal on the 

chassis.

To connect 2 cables, change the 

preset cable clamp to the 

provided one and fix the cables 

with the cable clamp as shown in 

the figure.

Remove the grommet from the power 

supply wire hole. Attach the conduit 

pipe to the plate with a lock nut.

Use 1/2 inch conduit pipe.

Lock nut

Conduit pipe

Power supply wire 

hole (Ø7/8” (22.2))

5-EN

+00DE93229101-1_01EN.book  Page 5  Friday, October 4, 2013  2:40 PM

Содержание BMS-IFDD03UL

Страница 1: ...DIGITAL INPUT OUTPUT RELAY INTERFACE Installation Manual Model name BMS IFDD03UL Toshiba 00DE93229101 1_01EN book Page 1 Friday October 4 2013 2 40 PM ...

Страница 2: ...on 4 4 Installation 4 5 Connection of power cables earth wires communication cables 5 6 Setting 8 7 Test run 9 Thank you very much for purchasing this TOSHIBA Carrier Digital Input Output Relay Interface Please read this manual carefully beforehand for proper installation of the relay interface 1 EN 00DE93229101 1_01EN book Page 1 Friday October 4 2013 2 40 PM ...

Страница 3: ... treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actual contents of the obligation indicated by a pic...

Страница 4: ...pply 120 VAC 60 Hz Power consumption 5 W Operating temperature humidity 32 to 104 F 0 to 40 C 10 to 90 RH no condensation Storage temperature 4 to 140 F 20 to 60 C Chassis material Galvanized sheet metal 0 8 t Dimensions 2 59 H x 7 59 W x 9 68 D inch 66 H x 193 W x 246 D mm Mass 2 98 lb 1 35 kg Digital input Input type Photo coupler insulation Input points 8 points Input registance 3 k ohm Input O...

Страница 5: ...xposed to rain outdoors under eaves etc Installation space and maintenance space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be adjacent to surrounding objects No Item Quantity Remarks 1 Digital Input Output Relay Interface 1 2 Installation Manual 1 3 Screw 4 5 32 x 0 47 M4 x 12 mm tapping screws 4 Pin...

Страница 6: ... LED8 LED9 1 38 35 1 38 35 1 38 35 0 24 6 0 39 10 2 17 55 0 39 10 0 24 6 Power supply 120 VAC 60 Hz Length of stripped power cable Length of stripped communication cable Digital input contacts Smart BMS Manager Digital output load Length of stripped digital Input Output connector wire Insert the wire by pushing the lever with a screwdriver Check that the wire is inserted securely When inserting tw...

Страница 7: ...sulated and left open Connection of external digital inputs Input circuit examples are shown below electrically isolated using a photo coupler CAUTION Output sink current has polarity When they are connected to inappropriate input terminal the unit may not operate properly Connection of external digital outputs Output circuit examples are shown below open collector output electrically isolated usi...

Страница 8: ...ication You can set the Digital Input Output Relay Interface address independently from the Energy Monitoring Relay Interface address CAUTION The SW1 setting is read when the power is turned on Push the reset switch SW6 after changing the address Set the RS 485 terminator resistor on an Energy Monitoring Relay Interface Set SW7 as 120 ohm on a Digital Input Output Relay Interface with address SW1 ...

Страница 9: ...set switch after the address setting to read the set value SW7 RS 485 terminator resistor select switch Terminator resistor of RS 485 must be set on Energy Monitoring Relay Interface When Digital Input Output Relay Interface is used without Energy Monitoring Relay Interface set it 120 ohm on Digital Input Output Relay Interface with address SW1 1 and set it Open on the other Interfaces L N B A SG ...

Страница 10: ... the test switch Their output status is indicated by each LED Checking procedure 1 Set the operation mode switch SW2 to 3 in the same way as the external input check and then push the reset switch SW6 to enter the test mode 2 When the bit of the test switch SW3 is set to ON the external output turns ON when set to OFF the external output turns OFF Bits 1 to 4 of SW3 correspond to output terminals ...

Страница 11: ...unication status When RS 485 communication with Smart BMS Manager is normal LED2 will blink LED Normal operation Abnormal operation LED1 Power indicator ON OFF LED2 RS 485 communication status indicator Blinking OFF LED3 Not used OFF LED4 Test indicator OFF LED5 Test indicator OFF 10 EN 00DE93229101 1_01EN book Page 10 Friday October 4 2013 2 40 PM ...

Страница 12: ...DE93229101 1 Toshiba 00DE93229101 1_01EN book Page 13 Friday October 4 2013 2 40 PM ...

Отзывы: