background image

Toshiba

– 9 –

Digital Input / Output Relay Interface

Installation Manual

7

Test run

Before starting test run

Turn on the power of the Digital Input / Output Relay Interface after all cable connections and settings are 
completed. Turn on power of the air conditioning control system.

Test run

Confirming external input connection

• In the test mode, when the external inputs connected to the input terminals DI-1 to DI-8 are ON, the respective 

LEDs will goes on so you can confirm the connection.

Confirming procedure:

1

Set the operation mode switch SW2 to “3”, and push the reset switch SW6 to enter the test mode.

2

Unless SW4 is pushed, the respective input status of DI-1 to DI-4 is indicated by LED2 to LED5.

3

When SW4 is pushed, the respective input status of DI-5 to DI-8 is indicated by LED2 to LED5.

(*) To return to the normal operation, reset SW2 to “zero (0)” and push SW6.

Checking external output connection

• In the test mode, you can set output terminals DO1 to DO4 to ON or OFF with the test switch. Their output status 

is indicated by each LED.

Checking procedure:

1

Set the operation mode switch SW2 to “3” in the same way as the external input check, and then 
push the reset switch SW6 to enter the test mode.

2

When the bit of the test switch SW3 is set to ON, the external output turns ON; when set to OFF, 
the external output turns OFF. Bits 1 to 4 of SW3 correspond to output terminals DO1 to DO4.

The respective output status of output terminals DO1 to DO4 is indicated by LED6 to LED9.
The LEDs light with the output ON, and goes off with the output OFF.
(*)To return to normal operation, reset SW2 to “zero (0)” and push SW6.

LED2

LED3

LED4

LED5

SW4 OFF

Displays DI-1 input 

status.

Displays DI-2 input 

status. 

Displays DI-3 input 

status.

Displays DI-4 input 

status.

SW4 ON

Displays DI-5 input 

status.

Displays DI-6 input 

status.

Displays DI-7 input 

status.

Displays DI-8 input 

status.

Input ON: LED lights
Input OFF: LED turns off

LED6

LED7

LED8

LED9

Displays DO1 output status. Displays DO2 output status. Displays DO3 output status. Displays DO4 output status.
Output ON: LED lights
Output OFF: LED turns off

9-EN

+00DE93229101-1_01EN.book  Page 9  Friday, October 4, 2013  2:40 PM

Содержание BMS-IFDD03UL

Страница 1: ...DIGITAL INPUT OUTPUT RELAY INTERFACE Installation Manual Model name BMS IFDD03UL Toshiba 00DE93229101 1_01EN book Page 1 Friday October 4 2013 2 40 PM ...

Страница 2: ...on 4 4 Installation 4 5 Connection of power cables earth wires communication cables 5 6 Setting 8 7 Test run 9 Thank you very much for purchasing this TOSHIBA Carrier Digital Input Output Relay Interface Please read this manual carefully beforehand for proper installation of the relay interface 1 EN 00DE93229101 1_01EN book Page 1 Friday October 4 2013 2 40 PM ...

Страница 3: ... treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actual contents of the obligation indicated by a pic...

Страница 4: ...pply 120 VAC 60 Hz Power consumption 5 W Operating temperature humidity 32 to 104 F 0 to 40 C 10 to 90 RH no condensation Storage temperature 4 to 140 F 20 to 60 C Chassis material Galvanized sheet metal 0 8 t Dimensions 2 59 H x 7 59 W x 9 68 D inch 66 H x 193 W x 246 D mm Mass 2 98 lb 1 35 kg Digital input Input type Photo coupler insulation Input points 8 points Input registance 3 k ohm Input O...

Страница 5: ...xposed to rain outdoors under eaves etc Installation space and maintenance space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be adjacent to surrounding objects No Item Quantity Remarks 1 Digital Input Output Relay Interface 1 2 Installation Manual 1 3 Screw 4 5 32 x 0 47 M4 x 12 mm tapping screws 4 Pin...

Страница 6: ... LED8 LED9 1 38 35 1 38 35 1 38 35 0 24 6 0 39 10 2 17 55 0 39 10 0 24 6 Power supply 120 VAC 60 Hz Length of stripped power cable Length of stripped communication cable Digital input contacts Smart BMS Manager Digital output load Length of stripped digital Input Output connector wire Insert the wire by pushing the lever with a screwdriver Check that the wire is inserted securely When inserting tw...

Страница 7: ...sulated and left open Connection of external digital inputs Input circuit examples are shown below electrically isolated using a photo coupler CAUTION Output sink current has polarity When they are connected to inappropriate input terminal the unit may not operate properly Connection of external digital outputs Output circuit examples are shown below open collector output electrically isolated usi...

Страница 8: ...ication You can set the Digital Input Output Relay Interface address independently from the Energy Monitoring Relay Interface address CAUTION The SW1 setting is read when the power is turned on Push the reset switch SW6 after changing the address Set the RS 485 terminator resistor on an Energy Monitoring Relay Interface Set SW7 as 120 ohm on a Digital Input Output Relay Interface with address SW1 ...

Страница 9: ...set switch after the address setting to read the set value SW7 RS 485 terminator resistor select switch Terminator resistor of RS 485 must be set on Energy Monitoring Relay Interface When Digital Input Output Relay Interface is used without Energy Monitoring Relay Interface set it 120 ohm on Digital Input Output Relay Interface with address SW1 1 and set it Open on the other Interfaces L N B A SG ...

Страница 10: ... the test switch Their output status is indicated by each LED Checking procedure 1 Set the operation mode switch SW2 to 3 in the same way as the external input check and then push the reset switch SW6 to enter the test mode 2 When the bit of the test switch SW3 is set to ON the external output turns ON when set to OFF the external output turns OFF Bits 1 to 4 of SW3 correspond to output terminals ...

Страница 11: ...unication status When RS 485 communication with Smart BMS Manager is normal LED2 will blink LED Normal operation Abnormal operation LED1 Power indicator ON OFF LED2 RS 485 communication status indicator Blinking OFF LED3 Not used OFF LED4 Test indicator OFF LED5 Test indicator OFF 10 EN 00DE93229101 1_01EN book Page 10 Friday October 4 2013 2 40 PM ...

Страница 12: ...DE93229101 1 Toshiba 00DE93229101 1_01EN book Page 13 Friday October 4 2013 2 40 PM ...

Отзывы: