57
1600XP/XPi Series Installation and Operation Manual – 60616-012
Display
Meaning
Action
EEUPERR
EEPROM updating Error.
Call Toshiba for service.
EPO
EPO circuit is active.
Reset EPO switch to start.
FIERRST
Frequency Input Error Start – Input frequency
could not be detected and UPS starts up with
default EEPROM setup.
Ensure correct input frequency is
selected in UPS settings.
FLT
A fault has occurred.
See Fault records.
FWUPERR
Firmware Update Error.
Call Toshiba for service.
INIT
Initialization – UPS is inatilizing.
No action needed.
INV
Inverter mode.
Inverter is running (it can be On-
Line, Battery Test, or Backup)
LANSD
UPS goes to Shutdown triggered from customer
supplied LAN SD circuit.
Deactivate LAN shutdown signal to
reset.
LB
Low Battery – The battery level has dropped low
(about 90% or less) during operation. Continued
operation in this mode will deplete battery and
cause output shut down.
Immediately shut down the load
equipment in an orderly fashion and
then press the STOP key.
PFAIL
Input power failure.
No action needed.
RMTSD
Remote shutdown occurred.
Disconnect LAN signal to reset.
RO2EEERR
ROM to EE Loading Error.
Call Toshiba for service.
SYNC
Synchronous mode.
Input and output are synchronized.
TIMEDSD
UPS is counting down prior to shutdown.
Immediately shut down the load
equipment in an orderly fashion and
then press the STOP key.
WRN
A warning has occurred.
See Warning record.
24. Preventive Maintenance/Parts Replacement
24.1 Preventive Maintenance
Toshiba 1600XP/1600XPi Series of uninterruptible power systems have been designed to provide years of
trouble-free operation requiring a minimum of preventive maintenance.
The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the
air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the installation site
is very dusty, use a vacuum cleaner to periodically remove dust accumulations around and from the unit.
CAUTION
Only a qualified Toshiba representative should be allowed to perform any
routine maintenance or service on this equipment other than those preventive
maintenance details which are described directly above this caution.
Содержание 1600XP SERIES
Страница 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 114: ...C2 1600XP XPi Series Installation and Operation Manual 60616 012 3 6 6 kVA Dimensions w Optional MBS ...
Страница 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Страница 116: ...C4 1600XP XPi Series Installation and Operation Manual 60616 012 14 22 kVA Dimensions w Optional MBS ...
Страница 131: ...E1 1600XP XPi Series Installation and Operation Manual 60616 012 Appendix E External Battery Cabinets Matching Outlines ...
Страница 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 139: ......