background image

D6

1600XP/XPi Series Installation and Operation Manual – 60616-012

UPS 

ESTIMATED 

RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf

Rating

PF

Output 

Voltage

Rated I

Rated 

Load %

Output 

Watts

# Batt

# Strings Nominal

Runtime

8

0.85

240

33.33

0.10

680

24

1

288

86

8

0.85

240

33.33

0.20

1360

24

1

288

50

8

0.85

240

33.33

0.30

2040

24

1

288

33

8

0.85

240

33.33

0.40

2720

24

1

288

23

8

0.85

240

33.33

0.50

3400

24

1

288

16

8

0.85

240

33.33

0.60

4080

24

1

288

14

8

0.85

240

33.33

0.70

4760

24

1

288

11

8

0.85

240

33.33

0.80

5440

24

1

288

9

8

0.85

240

33.33

0.90

6120

24

1

288

8

8

0.85

240

33.33

1.00

6800

24

1

288

7

UPS 

ESTIMATED 

RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf

Rating

PF

Output 

Voltage

Rated I

Rated 

Load %

Output 

Watts

# Batt

# Strings Nominal

Runtime

8

0.85

240

33.33

0.10

680

24

4

288

300

8

0.85

240

33.33

0.20

1360

24

4

288

180

8

0.85

240

33.33

0.30

2040

24

4

288

120

8

0.85

240

33.33

0.40

2720

24

4

288

105

8

0.85

240

33.33

0.50

3400

24

4

288

82

8

0.85

240

33.33

0.60

4080

24

4

288

70

8

0.85

240

33.33

0.70

4760

24

4

288

60

8

0.85

240

33.33

0.80

5440

24

4

288

53

8

0.85

240

33.33

0.90

6120

24

4

288

48

8

0.85

240

33.33

1.00

6800

24

4

288

44

UPS 

ESTIMATED 

RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .85pf

Rating

PF

Output 

Voltage

Rated I

Rated 

Load %

Output 

Watts

# Batt

# Strings Nominal

Runtime

8

0.85

240

33.33

0.10

680

24

7

288

300

8

0.85

240

33.33

0.20

1360

24

7

288

300

8

0.85

240

33.33

0.30

2040

24

7

288

240

8

0.85

240

33.33

0.40

2720

24

7

288

165

8

0.85

240

33.33

0.50

3400

24

7

288

135

8

0.85

240

33.33

0.60

4080

24

7

288

120

8

0.85

240

33.33

0.70

4760

24

7

288

105

8

0.85

240

33.33

0.80

5440

24

7

288

90

8

0.85

240

33.33

0.90

6120

24

7

288

82

8

0.85

240

33.33

1.00

6800

24

7

288

72

Содержание 1600XP SERIES

Страница 1: ...UPS Part 60616 00112 July 2015 Manufactured in the USA Copyright 2014 TOSHIBA International Corporation All rights reserved 1600XP 1600XPi SERIES INSTALLATION AND OPERATION MANUAL SINGLE PHASE 3 6 6 8 10 14 18 22 KVA 1600XPi 1600XP ...

Страница 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...

Страница 3: ...ns in equipment or to provide for every possible contingency concerning installation operation or maintenance Should further information be required or if problems arise which are not covered sufficiently contact your Toshiba sales office The contents of this instruction manual shall not become a part of or modify any prior or existing agreement commitment or relationship The sales contract contai...

Страница 4: ...ified the warranty period for the UPS or UPS part is 36 months from the shipment date see Toshiba International Corporation bill of lading Unless otherwise specified the warranty period for a UPS battery is 24 months from the shipment date see Toshiba International Corporation bill of lading JOB NUMBER MODEL NUMBER SERIAL NUMBER APPLICATION SHIPMENT DATE INSTALLATION DATE INSPECTED BY ...

Страница 5: ...f their respective owners Toshiba International Corporation shall not be liable for direct indirect special or consequential damages resulting from the use of the information contained within this manual This manual is copyrighted No part of this manual may be photocopied or reproduced in any form without the prior written consent of Toshiba International Corporation Copyright 2015 Toshiba Interna...

Страница 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...

Страница 7: ...ock 208 240 VIN 120 280 240 VOUT 11 8 2 Terminal Block 240 VIN 100 200 VOUT 13 8 3 EPO and Remote Shutdown 14 8 4 Cable Size and Tightening Torque 14 8 5 Battery Cabinet Connections 14 9 Product Description 15 9 1 Application and Use 15 9 2 Output Rating 15 9 3 Power Backup 15 9 4 Power Conditioning 15 10 Operating Modes 16 10 1 Static Bypass Stop operation 16 10 2 On Line Run operation 16 10 3 Ba...

Страница 8: ...ble Alarm Functions 36 17 Screen Tab Settings 37 17 1 Changing UPS Parameter Settings 39 17 2 Settings Parameters 40 17 3 Recalibrate the Touchscreen 41 18 Communication Interfaces 42 18 1 Remote Contacts 42 18 2 UPS LAN Shutdown Signal Operation 43 18 3 RS 232C 43 18 4 RemotEye Network Card 44 18 5 Optional EMD 45 19 Optional MB Maintenance Bypass Units 46 19 1 Internal Maintenance Bypass 46 19 2...

Страница 9: ...dels 14 22 kVA A4 Appendix B 1600XP 1600XPi Command Parameter Table B 1 Appendix C 1600XP 1600XPi Dimensions and Weights C1 3 6 6 kVA Dimensions C1 3 6 6 kVA Dimensions w Optional MBS C2 8 10 kVA Dimensions C3 14 22 kVA Dimensions w Optional MBS C4 Appendix D Battery Backup Tables Internal External Battery Cabinets D1 3 6kVA UH3G2L036C61T H3BG2L036C61T D1 6kVA UH3G2L060C61T H3BG2L060C61T D3 8kVA U...

Страница 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...

Страница 11: ...his manual When symbols are used in this manual they will include important safety information that must be carefully followed Safety Alert Symbol indicates that a potential personal injury hazard exists Prohibited Symbol indicates DO NOT take action Mandatory Symbol indicates that the following instruction is required Ground Symbol indicates the location of the equipment grounding conductor Elect...

Страница 12: ...s 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause undesired operation Notice The FCC regulations provide that changes or modifications made to this device that are not approved by Toshiba International Corporation may void the authority granted to the user by the FCC to operate this equipment EMC Directive C...

Страница 13: ...ns sealed lead acid batteries Lack of preventative maintenance could result in batteries exploding and emitting gasses and or flame Annual preventative maintenance must be performed by an authorized trained technician WARNING CRITICAL FUSE SIZING Incorrect fuse replacem ent size may result in fire or inadequate equipm ent protection Re pla ce only with same type and rating of fuse 49455 SHEET Risk...

Страница 14: ...CKS FACTORY WIRED FOR 208V INPUT o 208 240V 208V 120V 240V 120V INPUT VOLTAGE JUMPER SELECTION EPO REMOTE INPUT OUTPUT FOR SINGLE HOT WIRE P N63093 Power Terminal Label P N 63109 There are no user serviceable parts behind cover Wait five minutes after disconnect ing the UPS to allow the internal capacitors to discharge completely Date of last recorded battery change Battery Cabinet Warning Label F...

Страница 15: ...es for these models are as follows BATTERY VOLTAGE 3 6 kVA 6 kVA 8 kVA 10 kVA 14 kVA 18 kVA 22 kVA 144 Vdc 216 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc 288 Vdc Servicing of the batteries should only be performed by a qualified factory authorized representative who is knowledgeable about batteries and the required precautions Keep unauthorized personnel away from batteries To arrange for battery replace...

Страница 16: ... any part of a grounded battery can result in electrical shock The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance CAUTION CAUTION CAUTION WARNING 3 1 Qualified Personnel Only Qualified personnel are those who have the skills and knowledge relating to the construction installation operation and maintenance of the electrical equipment and have re...

Страница 17: ...re the UPS in the original shipping container and place on a wood or metal pallet Storage temperature 4 104 F 20 40 C The optimum storage temperature is 70 F 21 C A higher ambient temperature will require recharging more frequently during storage Avoid storage locations that Are subject to extreme temperature changes or high humidity Are subject to high levels of dust or metal particles Are subjec...

Страница 18: ...level and upright position that is free of excessive vibration 3 Follow the instructions on the unpacking label affixed to the exterior of the UPS 4 Retain the shipping rails for use as permanent mounting of the UPS eries sult and or must be cian WARNING CRITICAL FUSE SIZING Incorrect fuse replacem ent size may result in fire or inadequate equipm ent protection Re pla ce only with same type and ra...

Страница 19: ...auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector A circuit breaker suitable as an isolation device per IEC 60947 2 Any other switching device in accordance with an IEC product standard that also meets the isolation requirements of IEC 60947 1 and is appropriate for on load switching of motors or other...

Страница 20: ... output of the UPS 4 DO NOT use the UPS to provide power to motors that require high starting current or with motors that require a long starting time such as vacuum cleaners and machine tools oversizing the UPS for lock rotor current would be required 5 DO NOT insert metal objects or combustible materials in the ventilation slots of the UPS 6 DO NOT place hang or paste any objects on the exterior...

Страница 21: ...1 and 12 with a jumper wire DO NOT jumper terminal 13 to 12 or 11 Factory Setting is 208 Vac Use the jumper wire provided by Toshiba DO NOT add any additional jumpers NOTE 2 If AC input power is 240 Vac rated short terminals 12 and 13 with a jumper wire DO NOT jumper terminal 11 to 12 or 13 Use the jumper wire provided by Toshiba DO NOT add any additional jumpers NOTE 3 EPO and Rmt Contacts functi...

Страница 22: ... 208 EPO2 EPO1 REMOTE2 COM 240 G X3 1 L2 G X1 X2 N 2 3 12 14 13 15 8 7 6 5 11 4 16 17 L1 Factory Installed N G Jumper Jumper 208 Vin Rmt Contacts EPO NO NO 120 V 240 V 120 V 208 V 32 V 88 V REMOTE1 208 EPO2 EPO1 REMOTE2 COM 240 G X3 1 L2 G X1 X2 N 2 3 12 14 13 15 8 7 6 5 11 4 16 17 L1 Factory Installed N G Jumper Jumper 240 Vin Rmt Contacts EPO NO NO 120 V 240 V 120 V 208 V 32 V 88 V 120 V 120 V G...

Страница 23: ...connections used for 208 Vin 100 200 Vout units Output Cabling for 100 Vout 200 Vout Connect load across Terminals 4 6 or 6 7 Connect load across terminals 4 7 DO NOT USE 100 V 100 V G X3 G X1 X2 N 3 8 7 6 5 4 Factory Installed N G Jumper 200 Vout G X3 G X1 X2 N 3 8 7 6 5 4 Factory Installed N G Jumper REMOTE1 208 EPO2 EPO1 REMOTE2 COM 240 G X3 1 L2 G X1 DO NOT USE N 2 3 12 14 13 15 8 7 6 5 11 4 1...

Страница 24: ... conductors for all Input Output and Ground wiring Item Terminal Number Cable Size AWG Tightening Torque lb in N m 3 6 kVA 6 kVA 8 kVA 10 kVA 14 18 kVA 22 kVA AC Input Lines 1 and 2 10 8 8 8 8 1 0 6 1 0 4 1 0 1 1 0 14 2 1 56 AC Output Lines 4 5 and 7 12 8 10 8 8 1 0 6 1 0 4 1 0 1 1 0 14 2 1 56 AC Output Neutral 6 12 8 10 8 8 1 0 6 1 0 4 1 0 1 1 0 14 2 1 56 Ground 3 and 8 12 8 10 8 8 1 0 6 1 0 4 1 ...

Страница 25: ...efficient unit The UPS unit ensures safe and reliable operation of critical office equipment All units feature an audible alarm which sounds if the battery voltage drops below a specified minimum during use This is an additional aid to help protect valuable office data banks All units allow for computer interfacing 9 2 Output Rating Toshiba 1600XP and 1600XPi Series 208 240V offers UPS models with...

Страница 26: ... s bypass circuit back to the inverter circuit after removing the overload if set to do so AutoXfer parameter Cmd ID 660 10 2 On Line Run operation The following illustration shows circuit power flow when the UPS is operating normally in the On Line mode The UPS rectifier including a boost chopper circuit converts AC input power to DC power The boost chopper circuit maintains a constant voltage wi...

Страница 27: ...ge 11 and terminal block location in Appendix C This safety feature enables quick shut down of the UPS s AC input breaker output and battery circuits Usually the emergency power off switch is installed in a central location that is easily accessible to personnel concerned with the operation of the UPS unit and the load equipment connected to it The EPO function is initiated by pressing the switch ...

Страница 28: ...age A1 The following illustration graphically shows the battery discharge process at full load conditions 10 6 Battery Low Voltage Tolerances Excessive discharge will cause the UPS battery voltage to drop The chart shown below lists the voltage level at which each UPS low voltage alarm will sound and at what level the low voltage condition will cause the unit to automatically shut down UPS Capacit...

Страница 29: ...atteries charge to their normal fully charged state In the third period a slight trickle current continues to flow into the batteries to keep them fully charged and floating at the normal Vdc level A full recharge usually requires 24 hours 90 recharge in 12 hours after a complete discharge The following chart shows the rated maximum and minimum battery voltages and the charge current for each of t...

Страница 30: ...2 Battery Test Startup must be set to Disable b Cmd 653 Enable Battery Test set to Enable to allow the battery test to be performed c Cmd 655 Battery Test Frequency should be set to 0 Daily Test d Cmd 654 Battery Test Condition Status should read Enable Battery Test OK to perform NOTE If Cmd 654 is Disable the user will have to power down and restart the unit to perform the battery test e Navigate...

Страница 31: ...s in BYPASS mode The mode lower right side of the display should display Bypass If it does not display Bypass press and momentarily hold the STOP button on the Main display NOTE The internal batteries recharge in both Bypass and On Line modes As soon as the input breaker is closed the internal batteries will begin recharging 10 With the UPS in bypass mode cycle power to the UPS as follows At the r...

Страница 32: ...kVA 0 18 18 UH31 BC 1825 H3B BC 1825 8 22 kVA 0 24 24 526 External Batt Strings in Parallel UH31 BC 0370 H3B BC 0370 3 6 kVA 0 3 6 UH31 BC 0650 H3B BC 0650 6 kVA 0 2 4 UH31 BC 1825 H3B BC 1825 8 22 kVA 0 3 6 527 External Battery Capacity in A hr All 0 9 9 1 These settings apply to 1600XP 1600XPi matching battery cabinets 2 For use with BC 1825 only Otherwise always Disable Table 11 2 Initial Batte...

Страница 33: ...t Panel Layout on page 24 lights green The UPS will now be supplying power in the On Line mode If the On Line LED is not illuminated push and hold the RUN key for approximately 3 seconds NOTICE When running the UPS for the first time charge the batteries for at least 24 hours input breaker on before operating the connected load Failure to do so will result in reduced battery backup time 11 4 Stopp...

Страница 34: ...ay Reset Switch When necessary the touchscreen display can be reset by using a thin probe such as a paper clip to press the display reset switch Display Contrast Adjustment The display is shipped with the display adjusted for optimum visibility If necessary use a trimmer adjustment tool to fine tune the display contrast for improved visibility DISPLAY CONTRAST ADJUSTMENT MIDDLE LEFT SIDE OF PANEL ...

Страница 35: ...s modification of the UPS operating parameters At the top of the display are four status indicators Load Battery Information UPS System Status and System Time At the top left of the display are a bank of four touch sensitive keys Home Pressing HOME key returns the display to the top menu of the currently selected tab Security Level Pressing the Security Level key activates the log in security scre...

Страница 36: ...P key and disappear from the RUN key Home Key Press to return to top menu of respective tab Security Level Key Press to open security login screen Event Alarm Mute Key Press to silence current event alarm Alarm Muted Key Alarm remains silenced until next event Touchscreen Enabled Key Press to disable lockout all touchscreen keys except this key Touchscreen Disabled Key Press to enable un lock touc...

Страница 37: ...ng see page 53 ASYN Warning Description Code For a detailed listing see page 54 On Line Current Operating Mode of the UPS For a detailed listing see page 56 13 4 Light Emitting Diodes LED The following table describes the front panel LED behaviors and the associated meaning LED Behavior Significance Meaning Green ON UPS is in On Line Backup or Battery Test mode Green OFF UPS in Bypass mode Green O...

Страница 38: ...a of the Input IN Output OUT Bypass BYP Battery BAT and DC Bus DC Control Configura tion C C and Display External D E devices SETTINGS Allows monitoring and or modification of UPS pa rameters Parameters that can be viewed or modified vary depending on the security level of the login password entered using keypad Records Displays the most re cent 32 Test Backup Faults Warning Operation and System c...

Страница 39: ...se letters as above The Space key is used to enter a space between alpha numeric characters Example By using the additional characters available with the shift key you can type in a device name Toshiba H3 instead of TOSHIBAH3 Return to the Upper Case format keypad by pressing Shift again Exit the keypad display by pressing either the Quit or Write key On Line DVCOH ASYN Main Monitor Settings Recor...

Страница 40: ... are set to User USER Administrator ADMIN 3 Typing in USER in the keypad will change the se curity level to User Enter the password using the alphanumeric keys 4 Press Write to store the password in the UPS If the password is accepted the text Successful will display at the bottom left of the touchpad as shown here If the password entered was not accepted the text Error15 Write Function or some si...

Страница 41: ...at you forget or need to reset the ADMIN password follow these steps Reset ADMIN Password 1 Ensure the Security Level key USR shows the unit is in USER mode 2 If necessary change to USER mode as shown on page 30 3 Press the Settings tab 4 Press the CTRL CFG key 5 Use the page and and record and keys to select Cmd 621 Reset Admin PWD 6 Press Reset 7 Press Write to store the default password in the ...

Страница 42: ...TE The touchscreen lockout key is disabled when the screen is in keypad mode The Lockout key will change to and the touch screen will not respond to any input except a touch to the lockout key Touching the lockout key again will toggle the lockout off the graphic will change to indicating the touch screen is active MAIN SCREEN On Line DVCOH ASYN 1600XP On Line UPS UPS Serial Number 20080112345 UPS...

Страница 43: ... power flowing The Monitor display below shows the UPS in Shutdown Mode Power is flowing to charge the battery but no power is going to the Bypass or Output Monitor Details Press the IN BYP OUT DC or BAT key on the mimic display to view the parameter details for that section of the UPS The MONITOR TAB figure on the following page shows the relationship of the various data displays Press the Home k...

Страница 44: ...rds 12 35 PM INV HOME USR BAT 1 1 501 Battery Voltage 503 Discharge Current 506 Charger Status 508 Cal Battery Vsd 547 Cal LB Level 200 Vdc 0 0 Adc Normal 172 Vdc 194 Vdc On Line DVCOH ASYN Main Monitor Settings Records 12 35 PM INV HOME USR OUT 1 2 201 Output Config 203 Output Voltage 204 Output Current 205 Output Frequency 206 Output Power W 207 Output Power VA 7 234 v 21 4 A 60 0 Hz 4590 W 4986...

Страница 45: ...ecords 12 35 PM INIT HOME USR 1 2 Backup Record Rec No 2 Date 04 15 09 Sin 240 60Hz Vin 24 Iout 84 Vbst 92 Backup 140 s Trigger source ViVU Time 10 17 29 Sout 240 60Hz Vout 98 Vdc 101 Vbend 92 On Line DVCOH ASYN Main Monitor Settings Records 12 35 PM INIT HOME USR 1 16 Fault Record Rec No 803 Date 04 14 09 Sin 240 60Hz Vin 99 Iout 89 Vbst 92 VOUV Time 12 54 17 Sout 240 60Hz Vout 98 Vdc 101 On Line...

Страница 46: ...utdown Voltage Batt Voltage 79 Warnings OL110 Overload Timer LB Low Battery Batt Voltage 90 BLFN Battery Life Pre alarm Batt exp in 6 mo BLFE Battery Life End CHRGOV Charger Over Voltage BTSTFL Battery Test Fail BOH Battery Overheat AOH Ambient Overheat CLMT Current Limit DCER Display Disconnected BDEPL Battery Depletion Touching Effective Item on Touchscreen The buzzer can be silenced by selectin...

Страница 47: ...utput voltage frequency current power over under voltage settings Bypass 300 399 Bypass data such as configuration voltage current power OV detection level DC Bus 400 499 Data such as Total voltage rated voltage Positive and Negative bus voltages Batt 500 599 Battery voltage charger status total discharges shutdown voltage Ctrl Cfg 600 699 Control and configuration list system and battery temperat...

Страница 48: ...l 141 Freq on FIERR 1 Line 240 V 274 V 264 V 50 0 Hz On Line DVCOH ASYN Main Monitor Settings Records 12 35 PM FLT HOME USR DC 1 1 404 Rated DC Bus 770 Vdc On Line DVCOH ASYN Main Monitor Settings Records 12 35 PM FLT HOME USR HIS 1 4 701 System Op Time 702 Inverter Op Time 703 Backup Op Time 704 UPS Lifetime 705 Hi System Temp 706 Hi Battery Temp 07031 Sec 0 Sec 0 Sec 6118 Hr0 28 C 8 C OUTPUT BLO...

Страница 49: ... range Press the Rated Vin parameter listing and enter the correct value in the Active Value box using the standard alphanumeric keypad Use the back arrow to delete an incorrect keystroke After changing the parameter value press Write to write the entered value to the UPS memory Example 3 Some parameters are informational some can be changed by the user and others can only be changed by a higher s...

Страница 50: ...y and factory authorized service providers only The table headings are Cmd ID Command ID number A three digit number between 000 and 999 Not all numbers have an associated parameter Description on LCD Display text often abbreviated Brief Description Brief description of the function of the parameter Location Map Tab Blk Gives the menu location for the parameter by Tab and Block The tabs are Main M...

Страница 51: ...7 The display will switch to the CALIBRATION SCREEN shown below 8 Gently press a stylus or similar fine pointed tool to the center of the X located at the top left hand side of the display 9 As soon as the information is read a second X will be displayed at the top right hand of the display Repeat Step 7 10 Repeat Step 7 for X displayed at the lower right hand side of the display 11 Repeat Step 7 ...

Страница 52: ...70 mA peak 30 Vac rms 42 Vac peak 50 mA rms 70 mA peak Pin Signal Function Logic In the UPS 1 Fault Signal Closed when fault detected 2 UPS stop common Backup stop when the level changes from Low 3 to 15 V to High 3 to 15 V 3 UPS stop signal input 4 Normal input power supply Closed with normal supply power 5 Signal common Common signal return 6 Bypass operation Closed during bypass operation 7 Bat...

Страница 53: ...ime to complete the LAN shutdown process default 10 minutes even if line power is restored during LAN shutdown LAN shutdown is treated as a restart after battery shutdown The restart of the LAN will be determined by the Restart After Battery Shutdown timer Connect only the UPS stop signal to the external contact interface for automatic processing so that the UPS output will not be turned off by mi...

Страница 54: ...k protocols The following diagram shows the flow of the Network Management Station 18 4 1 To install the RemotEye network card Follow the steps below 1 Turn the UPS off using the proper shutdown procedure 2 Remove the blank cover plate over the extension option slot 3 Slide the RemotEye printed circuit board into the extension option slot of the UPS 4 Secure the printed circuit board using the UPS...

Страница 55: ...onment humidity and other conditions via the RemotEye Network Card The EMD also provides two user defined dry contacts for additional monitoring These dry contacts can be used with devices that provide normally open or normally closed results such as door sensors smoke detectors motion detectors and liquid detectors ENVIRONMENTAL MONITORING MODULE EMD RG 45 PORT Intrusion Sensor Smoke Detector Mot...

Страница 56: ...ructions From Inverter Mode to Maintenance Bypass Mode 1 Turn the RUN STOP switch to the STOP position on the UPS 2 Turn the Maintenance Bypass Switch to the Bypass position The Bypass LED should be ON and the UPS LED should be OFF The LEDs are next to the Maintenance Bypass switch on the back of the UPS 3 Turn the MCCB input breaker on the UPS to the OFF position The UPS is now operating in Maint...

Страница 57: ...NOT use two legs of a three phase 208 120V utility to feed the 1600XP XPi as shown below if an external maintenance bypass is being used The phase shift between the output of the UPS and the util ity feed to the bypass could interrupt the power to to load DO NOT USE 3 PHASE INPUT WHEN USING AN EXTERNAL MAINTENANCE BYPASS MAIN OUTPUT UTILITY PANEL SINGLE Φ 240V L1 L2 N G LOAD PANEL L1 L2 N G UPS L1...

Страница 58: ...012 20 Optional TVSS Transient Voltage Surge Suppressor All models of the 1600XP and 1600XPi UPS ending in TVS are equipped with a TVSS Transient Voltage Surge Suppressor The TVSS is mounted on the back of the UPS and is factory wired to the input as shown below ...

Страница 59: ...tery cabinets are equipped with Anderson style keyed connectors that plug into the 1600XP 1600XPi UPS Non matching battery cabinets also come with an additional separate power cord for secondary recharging of the battery cabinet For UPS and Matching battery cabinet runtimes see Appendix D For Matching battery cabinet dimensions and weights see Appendix E For Non matching battery cabinet dimensions...

Страница 60: ... panel module There are different panels available depending on the UPS typeform Step 1 Remove the modular receptacle panel cover plate On the rear of the UPS locate the cover plate for the receptacle panel module interface See Figure 1 Remove the 6 mounting screws Remove the cover plate A square shaped plug will be exposed Step 2 Snap In Output Receptacle modular panel Carefully mate the square s...

Страница 61: ...peration Chopper and inverter are stopped Inverter OL Transfer to bypass Bypass OL Inverter chopper stopped Audible Alarm Yes Continuous buzzer See Audible Alarm Functions on page 33 Visible Alarm Red Fault LED on Inverter OL Fault lamp off Bypass OL Fault lamp on Relay Contact Alarm Fault relay closed Bypass relay closed Fault relay open Inverter OL Bypass relay closed Bypass OL Bypass relay open...

Страница 62: ...Message AOH DCOV DCOC Cause Fan failure High internal ambient temperature Chopper malfunction Inverter chopper fault Operation Mode After Fault Shutdown No output Bypass operation Chopper and inverter are stopped Inverter OL Transfer to bypass Audible Alarm Yes Continuous buzzer Visible Alarm Red Fault LED on Relay Contact Alarm Fault relay closed Bypass relay closed Auto retransfer No ...

Страница 63: ... condition occurred UPS is faulty Check the UPS operation conditions at time of fault Not advisable to restart the UPS Call Toshiba for service CLMT Y Current Limit Load on UPS out put exceeds unit specifications Reduce load on UPS output DCIB Y DC Bus Imbalance DC voltage imbalance occurred Possible causes are UPS fault are connection of half wave rectifier load Check load and try restart ing If ...

Страница 64: ...essages are generated when a noncritical abnormal operating condition occurs The following tables shows possible messages and their meaning When a Warning condition exists the amber LED on the UPS display panel will flash for the duration of the Warning condition All warnings will clear after the appropriate action has been taken Display Recorded Meaning Action AOH Y Ambient Overheat The unit is o...

Страница 65: ...thin specifications Call Toshiba for service DCER Y Display Cable Error Display cable is disconnected Connect the display cable DCANERR N Communication Error between Display and Main Controllers Call Toshiba for service EXTBC1 N 1 BC1 Battery String 1 2 or 3 Disconnected 2 BC1 Over Temperature 3 BC1 Lost Communications with UPS Recover without power cycle Must Manually Reset Reduce Load on BC call...

Страница 66: ...Check bypass power 23 5 System Mode Messages A UPS Mode message is generated when the UPS changes operating mode The following tables list the possible operating modes for the UPS Display Meaning Backup Backup Power comes from other than input BattTest Battery Test Battery test in progress Bypass Bypass UPS is offline power is being provided directly from UPS input On Line On Line Input converter ...

Страница 67: ...nput power failure No action needed RMTSD Remote shutdown occurred Disconnect LAN signal to reset RO2EEERR ROM to EE Loading Error Call Toshiba for service SYNC Synchronous mode Input and output are synchronized TIMEDSD UPS is counting down prior to shutdown Immediately shut down the load equipment in an orderly fashion and then press the STOP key WRN A warning has occurred See Warning record 24 P...

Страница 68: ...ckup batteries packaged in sets of 6 batter ies per battery pack The two battery packs P N 51896 and P N 60995 are outwardly similar but dis tinctly different NOTICE Ensure the 1600XP 1600XPi battery packs are replaced with battery packs of the same part number Failure to do so may cause unexpected loss of backup power Battery Tray Plug for 3 6 6 8 14 and 18 kVA P N 51896 FS Battery Tray Plug for ...

Страница 69: ...andling of the battery pack may result in personal injury or damage to the UPS or battery pack Use two hand or two person lift to handle each battery pack Maintain horizontal orientation of the battery pack with setting it down 3 Slowly draw out each battery pack half way then support the bottom of the pack as the pack is drawn out of it s receptacle 4 Place the old battery pack aside 5 Lift the n...

Страница 70: ...S before replacing the cooling fans Open the UPS main circuit breaker disconnect external battery cabinets and partially slide out the top battery trays enough to open the internal DC power circuit 4 Batteries In order to maintain system reliability the UPS batteries should be replaced on a regular schedule To ensure reliable operation all of the batteries should be replaced at the same time Use t...

Страница 71: ...rams Pounds Kilograms 3 6 kVA 260 118 308 140 6 kVA 366 166 414 188 8 kVA 452 205 506 230 10 kVA 492 268 546 248 14 kVA 777 352 839 381 18 kVA 865 392 927 420 22 kVA 866 393 928 421 1 Subject to change without notice 25 3 Dimensional Data DIMENSIONAL DATA 3 6 kVA 6 kVA 8 kVA 10 kVA 14 kVA 18 kVA 22 kVA A 22 1 in 561 mm 27 5 in 698 mm 28 3 in 719 mm 28 3 in 719 mm 39 0 in 991 mm 39 0 in 991 mm 39 0...

Страница 72: ...0XP XPi Series Installation and Operation Manual 60616 012 External Layout for 3 6kVA and 6kVA units RemotEye 4 Slot RS232 Port Female Remote Contacts Port Male Terminal Block Cover MCCB 25 4 External Layout ...

Страница 73: ...63 1600XP XPi Series Installation and Operation Manual 60616 012 SNMP Port Remote Eye III Slot SNMP Port Remot Eye III Slot Remot Eye 4 Slot Remot Eye 4 Slot ...

Страница 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...

Страница 75: ...0 85 power factor 77 F 7 min 2 7 min 2 7 min 2 5 min 2 Recharge Time 24 hr full 12 hr 90 for internal batteries only3 Battery Voltage Nominal 144 Vdc 216 Vdc 288 Vdc Output Characteristics Output Voltage Single phase 240 208 120 V Output Voltage Regulation 3 Output Frequency 0 5 Hz 1 0 Hz 1 5 Hz factory or authorized service center selectable only AUTO MAN Frequency Factory or authorized service c...

Страница 76: ...ternal Temperature UPS gives indication of internal temperature alarm when high temp Event Data Storage Registers 32 Operation 32 Backup 32 Warnings 32 Faults 32 Test 32 System Applications Switches Generator compatible Bypass Switch Bypass Disable Static switch cycle 50 Hz 5 ms 60 Hz 4 16 ms Automatic Retransfer Factory or authorized service center selectable only Interface Communications Real Ti...

Страница 77: ... x 886 mm 28 4x 13 x 34 9 in 721 x 330 x 886 mm Paint System Powder coating Fan Panel2 Panel mounted on back of UPS to allow for easy replacement of fans Battery System Battery Replacement Slide out battery packs accessible from front of UPS Factory or authorized service center serviceable only Battery Packs Designed for battery acid leakage containment with six 6 batteries per pack Battery Pack S...

Страница 78: ...001 2004 RoHS Compliant Input Characteristics Input Voltage 1 Single phase 208 240 VAC 10 1 6 to 30 at typical 70 load Input Frequency 45 65 Hz auto sensing Input Capacity 14 kVA 18 kVA 22 kVA Input Max Input Current 208V 67 2 68 9 A 86 4 88 1 A 106 107 A Input Max Input Current 240V 58 2 59 7 A 74 9 76 3 A 92 0 93 0 A Input Power Factor 0 98 Typical 0 95 Minimum 100 Load1 Current THD linear load ...

Страница 79: ...ude 6600 ft 2000 m above sea level 2 Acoustical Noise 50 dB A maximum 1 meter from front panel Heat Generation Typical 6610 BTU Hr3 8499 BTU Hr3 10 387 BTU Hr3 Operation Diagnosis Battery Check Performed on start up by schedule on demand user configurable Input OV Protection Standard Battery Lifetime UPS calculates battery replacement time based upon battery ambient temperature LCD display LED and...

Страница 80: ... 36 1 in 991 x 445 x 917 mm Paint System Powder coating Fan Panel Panel mounted on back of UPS to allow for easy replacement of fans Battery System Battery Replacement Slide out battery packs accessible from front of UPS factory or authorized service center serviceable only Battery Packs Designed for battery acid leakage containment with 6 batteries per pack Battery Pack Size HxWxD max 5 0 x 7 3 x...

Страница 81: ... input output current and power factor It will default to 6 kVA rated value if kVA number is not pre defined values Also Latched in UPS Overall Status Bit Map Restart Required 003 UPS Serial Number Serial No R R R R W R W 080112345 YYMMSSSSS YY 2 digits of year MM 2 digits of month SSSSS 5 digits serial numbers 004 UPS Main Firmware Version Main FWare Ver R R R R R UH3MSV01000 UXXYFVMMRRR U UPS XX...

Страница 82: ...in Firmware Built Date Main FWare BDate R R R Format Mmm DD YYYY Ex Jan 04 2015 Automatically read by compiler 012 Main Firmware Built Time Main FWare BTime R R R Format HH MM SS Ex 18 45 45 Automatically read by compiler 013 EEPROM Version Main EEPROM Ver R R R R R W UH3MEE00000 UXXYEEMMRRR U UPS XX 2 Alpha Numeric UPS Product Line F3 H3 Y uC Projects M Main S Sub D Display EE EEPROM Version MM M...

Страница 83: ... R 0 Units 0 1 Arms 105 Input Frequency Total Input Frequency R R R R R 0 Units 0 1 Hz 106 Input Active Power Input Power W R R R R R 0 1 if input active power can not be calculated Units W 107 Input Apparent Power Input Power VA R R R R R 0 Units VA 108 Input Power Factor Input Pfactor R R R R R 0 1 if input power factor can not be calculated Units 0 01 111 Rated Input Voltage Total Rated Vin R R...

Страница 84: ...ection Level VIOV DeLevel R R R R W R W 274 Input Over Voltage Error detection level Range 100 500 Units Vrms 120 Input Overvoltage Warning Recovery Level VIOV ReLevel R R R R W R W 264 Input Over Voltage Error recovery level Range 100 500 Units Vrms 121 Input Voltage Gain Total Vin Gain R W R W 6720 Used this value to convert AD value to actual unit Range 1 32767 122 Input Voltage Offset Total Vi...

Страница 85: ... consecutively Range 0 600 Units 1 2 Cyc 132 Input Overvoltage Warning Recovery Delay VIOV ReDelay R W 8 Input Over Voltage Error recovery delay in consecutively Range 0 600 Units 1 2 Cyc 133 Input Frequency Warning Detection Delay FIERR DeDelay R W 4 Input Frequency Error detection delay in consecutively Range 0 300 Units 1 Cyc 134 Input Frequency Warning Recovery Delay FIERR ReDelay R W 8 Input ...

Страница 86: ...cording to DIP Switch or EEPROM setup Range 500 600 Units dHz 201 Output Power Supply Configuration Output Config R R R R R 0 unknown 0 199 1 200V 60Hz 200 207 2 200V 50Hz 200 207 3 208V 60Hz 208 229 4 208V 50Hz 208 229 5 230V 60Hz 230 239 6 230V 50Hz 230 239 7 240V 60Hz 240 32767 8 240V 50Hz 240 32767 9 220V 60Hz 10 220V 50Hz 11 120V 60Hz 12 120V 50Hz These numbers are stored in recording feature...

Страница 87: ...tch or EEPROM setup Units 0 1 Hz 218 Rated Output Active Power Rated Pout W R R R R R 0 UPS calculates at the startup according to typeform efficiency and rated power factor Units W 219 Rated Output Apparent Power Rated Pout VA R R R R R 0 UPS calculates at the startup according to typeform efficiency and rated power factor Units VA 220 Output Under Voltage Fault Detection Level VOUV DeLevel R R R...

Страница 88: ...ec 230 Output Overload Warning Recovery Level in Percentage OOL ReLevel R W R W 105 Range 90 120 Units 231 Output Overload Warning Recovery Delay OOL ReDelay R W R W 160 Range 120 1000 Units Sec 232 Output Voltage Compensation Vout Comp Step R W R W 20 Output voltage will be compensated according to this setup and current percentage Range 1 200 Units 1 Cyc 233 Output Voltage Gain Phase A or Total ...

Страница 89: ...54 Output Voltage Reference Amplitude Vref Amplitute R W R W 246 Calibrated at no Load output voltage Range 0 300 Units 128 255 Timer 3 Offset Remainder T3 Offset Remain R W 350 Range 0 1500 Units 128 256 DC to AC Efficiency DC AC Efficiency R W R W 81 Range 0 100 Units 257 Frequency Syn to Asyn Warning Detection Delay Freq Asyn DeDelay R W 4 Range 0 300 Units 1 Cyc 258 Frequency Asyn to Syn Recov...

Страница 90: ... 0 Cnv Xfmer Lmt R W R W 0 power calculation is limited by 1 input converter limited 0 output transformer limited default 269 Output Voltage before Tranformer Compensation Vout B4 Comp R W R W 0 Units V 270 Output Current before Tranformer Compensation Iout B4 Comp R W R W 0 Units 0 1 A 271 Inverter Mode A CompensationComp Ainv R W R W 2 Range 0 512 Units 128 272 Inverter Mode B Compensation Comp ...

Страница 91: ...These numbers are stored in recording features 302 Number of Bypass phases No Of Bypass Line R R R R W R W 1 303 Bypass Voltage Total Bypass Voltage R R R R R 0 Always the same as input voltage Units Vrms 304 Bypass Current Total Bypass Current R R R R R 0 Only valid at bypass mode and zero for other ups mode Units 0 1 A rms 305 Bypass Frequency Total Bypass Frequency R R R R R 0 Always the same a...

Страница 92: ...Delay VBypOV ReDelay R W 128 Range 0 600 Units 1 2 cyc 343 Bypass Frequency Error Detection Delay FBypERR DeDelay R W 4 Range 0 300 Units cyc 344 Bypass Undervoltage Detection Delay FBypERR ReDelay R W 128 Range 0 300 Units cyc 401 DC Bus Voltage Total DC Bus Total R R R R R 0 Units Vdc 402 DC Bus Voltage Positive DC Bus Positive R R R R R 0 Units Vdc 403 DC Bus Voltage Negative DC Bus Negative R ...

Страница 93: ...cycle 430 DC Bus Slew Rate DC Bus Slew Rate R W 5 Range 0 100 431 DC Bus Soft charging time SoftCharge Time R W R W 360 Range 0 1200 432 DC Bus Hard charging time HardCharge Time R W R W 120 Range 120 1200 436 Calibrated DC Bus Reference Calibrated DCRef R W R W 100 Starts from DC Bus reference and slowly ramp up to this final target value DC Bus and this value is inversely proportional 437 Presen...

Страница 94: ...ts Hr 511 Internal Battery Rated Capacity in Ampere Hour Rated Ahr R R W R W R W R W 9 Battery capacity Ampere Hour such as 7 AHr or 9 Ahr Range 1 15 Units Ahr 512 Number Internal Battery Packs In Series String No Batt Series R R W R W R W R W 18 Range 0 48 513 Number Internal Battery Strings in Parallel No Batt Paral R R W R W R W R W 1 Number of internal battery strings 3 6 14kVA 1 18 22kVA 2 Ra...

Страница 95: ...nge 0 12 Informational only Not used in calculations Units C 529 External Battery Cabinet Installation Date Ext Batt Ins Date R R W R W R W R W 20080101 Format YYYYMMDD Informational only Not used in calculations 532 Battery Voltage Gain Vbat Gain R W R W 8298 Used this value to convert AD value to actual unit Range 1 32767 533 Battery Voltage Offset Vbat Offset R W R W 0 Feedback Offset adjustmen...

Страница 96: ...Enable 555 Restart Charger controller Restart ChrgCtler R W R W 0 0 Disable 1 Enable 556 Batttery Current Multiplier Ibatt Multiplier R W R W 12 Range 1 255 557 Offset amp hour at 1 C discharge rate Offset AH Cap 1 R W R W 22 Range 0 255 558 Offset amp hour at 2 C discharge rate Offset AH Cap 2 R W R W 29 Range 0 255 559 Offset amp hour at 3 C discharge rate Offset AH Cap 3 R W R W 36 Range 0 255 ...

Страница 97: ... on UPS rating 580 Battery Cabinet 1 String 2 Current BC1 String2 I R R 0 Display this variable based on UPS rating 581 Battery Cabinet 1 String 3 Current BC1 String3 I R R 0 Display this variable based on UPS rating 582 Battery Cabinet 1 Status BC1 Status R R R R R 0 Display this variable based on UPS rating 585 Battery Cabinet 1 Ambient Temperature BC1 AmbientTemp R R R R R 0 Units C 586 Battery...

Страница 98: ...570 7 Battery Cabinet 1 Install Date Ins Date BC1 R R W R W R W R W 570 9 Battery Cabinet 2 Serial Number BC2 Serial No R R R R W R W 570 10 Battery Cabinet 2 Firmware Version BC2 Fware R R R R R 570 12 Battery Cabinet 2 Hardware Version BC2 Hardware R W R W 570 13 Battery Cabinet 2 EEPROM Version BC2 EEPROM R R R R R 570 14 Battery Cabinet 2 Install Date Ins Date BC2 R R W R W R W R W 571 2 Batte...

Страница 99: ...or 3 00 Amp current limit Range 0 4000 571 11 Number of Current Sense No Of I Sense R R R R W R W Set 2 if two strings are parallel in battery cabinet Set 3 if three strings are parallel in battery cabinet Range 0 4 571 12 Clear External Battery Cabinet Fault Clr Ext BC Fault R R W R W Range 0 5 572 2 Battery Cabinet 1 Input Voltage Calibration Factor BC1 IP V GCali R R W R W Ask Factory for Calib...

Страница 100: ...W R W Range 0 5000 572 12 Battery Cabinet 2 Output Voltage Calibration Factor BC2 OP V GCali R R W R W Range 0 5000 572 13 Battery Cabinet 2 Total Charge Current Calibration Factor BC2 Tot I GCali R R W R W Range 0 1000 572 14 Battery Cabinet 2 Input Voltage offset Calibration BC2 IP V Ocali R R W R W Range 1000 1000 572 15 Battery Cabinet 2 Output Voltage offset Calibration BC2 OP V Ocali R R W R...

Страница 101: ...ypass 7 Bypass Init show Bypass 8 Bypass Shutdown show Bypass 9 Startup show Startup 609 Operation Mode Transition State Requested Requested State R W R W R W R W R W 1 Shutdown Request 2 Bypass Request 3 Online Request 4 Battery Test Request 610 Operation Mode Transition Timer Timed Operation R W R W R W R W R W 0 Sec The timer upon whose expiration a mode transition will be attempted by the syst...

Страница 102: ...OTE Three communication chanels have their own security level variables 620 Manage Admin Password Manage Admin PW R W R W R W R W ADMIN Change Admin Password 621 Reset Admin Password Reset Admin PW R W R W R W R W R W 0 0 do nothing 1 reset administration password 623 Bypass Enable En Bypass R W R W 1 Enabled DIP Switch EEPROM s Enable CVCF and this value will decide the system s bypass availabili...

Страница 103: ...d document Hyper terminal HH MM SS 636 System Timestamp Timestamp R R R R R Current system timestamp 32 bits format 637 Enable Inverter Bypass command from REYE En Reye UPS Ctl R R W R W R W R W 1 Enabled RemotEye is allowed to switch UPS Inverter to From Bypass or not 0 Diable 1 Enable 639 Enable Startup Delay En Startup Delay R R W R W R W R W 0 Disabled Delay Timer enable or disable during Norm...

Страница 104: ...l external devices of the event Range 0 800 Units Sec 649 Remote Low Battery Delay Timer LB DContact Delay R R W R W R W R W 0 Delay timer between actual event occurrence and dry contact closure to signal external devices of the event Range 0 800 Units Sec 652 Enable Battery Test on UPS Startup En Batt Test Sup R R W R W R W R W 0 Disabled Forces a battery test when UPS starts after normal shutdow...

Страница 105: ...ice Port Baud Rate Settings Srv Port Baud R R W R W R W R W 3 no hardware control no parity 1 stop bit 8 bits of data and baud rate are Restart Required 0 9600 1 19200 2 38400 3 57600 680 All EEPROM Reload Reload All EE R W R W 0 0 do nothing 1 reload all EEPROM with ROM DEFAULT 2 reload CFG and STR types with ROM DEFAULT 681 SNMP Port Mode SNMP Port Mode R W R W 1 Protocol Rqrd 0 Terminal mode no...

Страница 106: ...R R W R W 0 Units Sec 704 UPS Lifetime Remaining UPS Lifetime R R R R W R W 61320 Range 0 61320 Units Hrs 705 Peak Highest system Temperature Hi System Temp R R R R W R W 0 Units C 706 Peak Highest battery Temperature Hi Battery Temp R R R R W R W 15 Range 15 0 Units C 707 No of Input Under Voltage Total VIUVs R R R R W R W 0 708 No of Overloads Total OLs R R R R W R W 0 709 No of Tests Total Test...

Страница 107: ...jects M Main S Sub D Display FV Firmware Version MM Major version RRR Minor version Note Only display can write Others read only 802 Display Firmware Built Date DFW BDate R W by Disp Only R W by Disp Only R W by Disp Only R W by Disp Only R W by Disp Only Mmm DD YYYY Ex Jan 04 2006 Automatically read by compiler Note Only display can write Others read only 803 Display Firmware Built Time DFW BTime...

Страница 108: ...ble 809 Buzzer Status Sbuzzer R W by Disp Only R W by Disp Only R W by Disp Only R W by Disp Only R W by Disp Only 0 Off 0 Off 1 On Note Only display can write Others read only 810 Enable Display Calibration Cali Disp R W R W R W R W R W 0 Disabled 0 Disabled 1 Enabled Note Only display can write Others read only 811 P1X Calibration Data P1X Cali W by Disp Only W by Disp Only W by Disp Only R W by...

Страница 109: ...isp Only 29286 Range 0 65535 818 P4Y Calibration Data P4Y Cali W by Disp Only W by Disp Only W by Disp Only R W by Disp Only R W by Disp Only 3028 Range 0 65535 819 1 Language Language R W R W R W R W R W Restart Required 821 1st time startup 1st Startup R W R W R W R W 1 822 Buzzer silent Buzzer Silent R W R W 0 823 Disp Watch Dog Disp Watch Kick R R 0 824 Enable Warning LED En Wrn LED Blink R W ...

Страница 110: ...Address RMTI Mask IP R W by SNMP Only R W by SNMP Only R R R Ex 255 0 0 0 Note Only SNMP can write Others read only 854 RemotEye Gateway Address RMTI Gway IP R W by SNMP Only R W by SNMP Only R R R Ex 10 128 33 1 Note Only SNMP can write Others read only 855 RemotEye Installation Status SRMTI R W by SNMP Only R W by SNMP Only R R R 0 Note Only SNMP can write Others read only 856 SNMP Port s Baud R...

Страница 111: ...R R 0 0 Unknown 1 Link Down 2 Link Up Note Only SNMP can write Others read only Changing parameter requires restarting Unit 1 Command Parameters 522 523 and 819 are only accessible to control board firmware version 1 05 and above If the commands are visible in the display but the user receives an error when trying to write the control board firmware is a version earlier version that does not suppo...

Страница 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...

Страница 113: ...C1 1600XP XPi Series Installation and Operation Manual 60616 012 Appendix C 1600XP 1600XPi Dimensions and Weights 3 6 6 kVA Dimensions ...

Страница 114: ...C2 1600XP XPi Series Installation and Operation Manual 60616 012 3 6 6 kVA Dimensions w Optional MBS ...

Страница 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...

Страница 116: ...C4 1600XP XPi Series Installation and Operation Manual 60616 012 14 22 kVA Dimensions w Optional MBS ...

Страница 117: ...ge Rated I Rated Load Output Watts Batt Strings Nominal Runtime 3 6 0 7 240 15 00 0 10 252 12 4 144 240 3 6 0 7 240 15 00 0 20 504 12 4 144 165 3 6 0 7 240 15 00 0 30 756 12 4 144 135 3 6 0 7 240 15 00 0 40 1008 12 4 144 105 3 6 0 7 240 15 00 0 50 1260 12 4 144 90 3 6 0 7 240 15 00 0 60 1512 12 4 144 82 3 6 0 7 240 15 00 0 70 1764 12 4 144 72 3 6 0 7 240 15 00 0 80 2016 12 4 144 65 3 6 0 7 240 15 ...

Страница 118: ... 85 240 15 00 0 10 306 12 4 144 240 3 6 0 85 240 15 00 0 20 612 12 4 144 150 3 6 0 85 240 15 00 0 30 918 12 4 144 112 3 6 0 85 240 15 00 0 40 1224 12 4 144 98 3 6 0 85 240 15 00 0 50 1530 12 4 144 82 3 6 0 85 240 15 00 0 60 1836 12 4 144 70 3 6 0 85 240 15 00 0 70 2142 12 4 144 60 3 6 0 85 240 15 00 0 80 2448 12 4 144 55 3 6 0 85 240 15 00 0 90 2754 12 4 144 50 3 6 0 85 240 15 00 1 00 3060 12 4 14...

Страница 119: ...tput Watts Batt Strings Nominal Runtime 6 0 7 240 25 00 0 10 420 18 3 216 180 6 0 7 240 25 00 0 20 840 18 3 216 135 6 0 7 240 25 00 0 30 1260 18 3 216 105 6 0 7 240 25 00 0 40 1680 18 3 216 86 6 0 7 240 25 00 0 50 2100 18 3 216 70 6 0 7 240 25 00 0 60 2520 18 3 216 60 6 0 7 240 25 00 0 70 2940 18 3 216 53 6 0 7 240 25 00 0 80 3360 18 3 216 46 6 0 7 240 25 00 0 90 3780 18 3 216 43 6 0 7 240 25 00 1...

Страница 120: ...time 6 0 85 240 25 00 0 10 510 18 3 216 180 6 0 85 240 25 00 0 20 1020 18 3 216 120 6 0 85 240 25 00 0 30 1530 18 3 216 90 6 0 85 240 25 00 0 40 2040 18 3 216 72 6 0 85 240 25 00 0 50 2550 18 3 216 60 6 0 85 240 25 00 0 60 3060 18 3 216 51 6 0 85 240 25 00 0 70 3570 18 3 216 45 6 0 85 240 25 00 0 80 4080 18 3 216 40 6 0 85 240 25 00 0 90 4590 18 3 216 35 6 0 85 240 25 00 1 00 5100 18 3 216 30 UPS ...

Страница 121: ...ut Watts Batt Strings Nominal Runtime 8 0 7 240 33 33 0 10 560 24 4 288 300 8 0 7 240 33 33 0 20 1120 24 4 288 180 8 0 7 240 33 33 0 30 1680 24 4 288 150 8 0 7 240 33 33 0 40 2240 24 4 288 120 8 0 7 240 33 33 0 50 2800 24 4 288 98 8 0 7 240 33 33 0 60 3360 24 4 288 86 8 0 7 240 33 33 0 70 3920 24 4 288 72 8 0 7 240 33 33 0 80 4480 24 4 288 65 8 0 7 240 33 33 0 90 5040 24 4 288 57 8 0 7 240 33 33 1...

Страница 122: ...me 8 0 85 240 33 33 0 10 680 24 4 288 300 8 0 85 240 33 33 0 20 1360 24 4 288 180 8 0 85 240 33 33 0 30 2040 24 4 288 120 8 0 85 240 33 33 0 40 2720 24 4 288 105 8 0 85 240 33 33 0 50 3400 24 4 288 82 8 0 85 240 33 33 0 60 4080 24 4 288 70 8 0 85 240 33 33 0 70 4760 24 4 288 60 8 0 85 240 33 33 0 80 5440 24 4 288 53 8 0 85 240 33 33 0 90 6120 24 4 288 48 8 0 85 240 33 33 1 00 6800 24 4 288 44 UPS ...

Страница 123: ...tts Batt Strings Nominal Runtime 10 0 7 240 41 67 0 10 700 24 4 288 300 10 0 7 240 41 67 0 20 1400 24 4 288 180 10 0 7 240 41 67 0 30 2100 24 4 288 120 10 0 7 240 41 67 0 40 2800 24 4 288 98 10 0 7 240 41 67 0 50 3500 24 4 288 82 10 0 7 240 41 67 0 60 4200 24 4 288 70 10 0 7 240 41 67 0 70 4900 24 4 288 60 10 0 7 240 41 67 0 80 5600 24 4 288 53 10 0 7 240 41 67 0 90 6300 24 4 288 48 10 0 7 240 41 ...

Страница 124: ...0 0 85 240 41 67 0 10 850 24 4 288 300 10 0 85 240 41 67 0 20 1700 24 4 288 150 10 0 85 240 41 67 0 30 2550 24 4 288 105 10 0 85 240 41 67 0 40 3400 24 4 288 82 10 0 85 240 41 67 0 50 4250 24 4 288 70 10 0 85 240 41 67 0 60 5100 24 4 288 57 10 0 85 240 41 67 0 70 5950 24 4 288 50 10 0 85 240 41 67 0 80 6800 24 4 288 44 10 0 85 240 41 67 0 90 7650 24 4 288 40 10 0 85 240 41 67 1 00 8500 24 4 288 35...

Страница 125: ...Watts Batt Strings Nominal Runtime 14 0 7 240 58 33 0 10 980 24 5 288 300 14 0 7 240 58 33 0 20 1960 24 5 288 165 14 0 7 240 58 33 0 30 2940 24 5 288 120 14 0 7 240 58 33 0 40 3920 24 5 288 90 14 0 7 240 58 33 0 50 4900 24 5 288 82 14 0 7 240 58 33 0 60 5880 24 5 288 63 14 0 7 240 58 33 0 70 6860 24 5 288 55 14 0 7 240 58 33 0 80 7840 24 5 288 48 14 0 7 240 58 33 0 90 8820 24 5 288 43 14 0 7 240 5...

Страница 126: ... 14 0 85 240 58 33 0 10 1190 24 5 288 300 14 0 85 240 58 33 0 20 2380 24 5 288 150 14 0 85 240 58 33 0 30 3570 24 5 288 98 14 0 85 240 58 33 0 40 4760 24 5 288 78 14 0 85 240 58 33 0 50 5950 24 5 288 63 14 0 85 240 58 33 0 60 7140 24 5 288 53 14 0 85 240 58 33 0 70 8330 24 5 288 45 14 0 85 240 58 33 0 80 9520 24 5 288 40 14 0 85 240 58 33 0 90 10710 24 5 288 35 14 0 85 240 58 33 1 00 11900 24 5 28...

Страница 127: ...atts Batt Strings Nominal Runtime 18 0 7 240 75 00 0 10 1260 24 5 288 300 18 0 7 240 75 00 0 20 2520 24 5 288 135 18 0 7 240 75 00 0 30 3780 24 5 288 98 18 0 7 240 75 00 0 40 5040 24 5 288 72 18 0 7 240 75 00 0 50 6300 24 5 288 60 18 0 7 240 75 00 0 60 7560 24 5 288 50 18 0 7 240 75 00 0 70 8820 24 5 288 44 18 0 7 240 75 00 0 80 10080 24 5 288 37 18 0 7 240 75 00 0 90 11340 24 5 288 32 18 0 7 240 ...

Страница 128: ...8 0 85 240 75 00 0 10 1530 24 5 288 240 18 0 85 240 75 00 0 20 3060 24 5 288 112 18 0 85 240 75 00 0 30 4590 24 5 288 82 18 0 85 240 75 00 0 40 6120 24 5 288 60 18 0 85 240 75 00 0 50 7650 24 5 288 50 18 0 85 240 75 00 0 60 9180 24 5 288 42 18 0 85 240 75 00 0 70 10710 24 5 288 35 18 0 85 240 75 00 0 80 12240 24 5 288 28 18 0 85 240 75 00 0 90 13770 24 5 288 24 18 0 85 240 75 00 1 00 15300 24 5 28...

Страница 129: ...tts Batt Strings Nominal Runtime 22 0 7 240 91 67 0 10 1540 24 5 288 240 22 0 7 240 91 67 0 20 3080 24 5 288 112 22 0 7 240 91 67 0 30 4620 24 5 288 82 22 0 7 240 91 67 0 40 6160 24 5 288 60 22 0 7 240 91 67 0 50 7700 24 5 288 50 22 0 7 240 91 67 0 60 9240 24 5 288 42 22 0 7 240 91 67 0 70 10780 24 5 288 35 22 0 7 240 91 67 0 80 12320 24 5 288 28 22 0 7 240 91 67 0 90 13860 24 5 288 24 22 0 7 240 ...

Страница 130: ... 0 85 240 91 67 0 10 1870 24 5 288 165 22 0 85 240 91 67 0 20 3740 24 5 288 98 22 0 85 240 91 67 0 30 5610 24 5 288 65 22 0 85 240 91 67 0 40 7480 24 5 288 51 22 0 85 240 91 67 0 50 9350 24 5 288 42 22 0 85 240 91 67 0 60 11220 24 5 288 32 22 0 85 240 91 67 0 70 13090 24 5 288 26 22 0 85 240 91 67 0 80 14960 24 5 288 21 22 0 85 240 91 67 0 90 16830 24 5 288 18 22 0 85 240 91 67 1 00 18700 24 5 288...

Страница 131: ...E1 1600XP XPi Series Installation and Operation Manual 60616 012 Appendix E External Battery Cabinets Matching Outlines ...

Страница 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...

Страница 133: ...40A 19 1 1775 6 UE3 BC 060120 120 1 25T 40A 13 1 1520 UE3 BC 060240 240 1 39T 50A 25 1 2523 8 UE3 BC 080120 120 1 25T 40A 13 1 1880 UE3 BC 080240 240 1 39T 50A 25 1 3183 10 UE3 BC 100120 120 1 25T 50A 14 0 2360 UE3 BC 100180 180 1 39T 60A 24 4 3183 UE3 BC 100240 240 2 25T 60A 33 3 4288 14 UE3 BC 140120 120 1 39T 60A 19 1 3183 UE3 BC 140180 180 2 25T 60A 33 5 4720 UE3 BC 140270 270 2 39T 60A 46 8 6...

Страница 134: ...ual 60616 012 F 2 Battery Cabinet Outlines TABLE F 2 NON MATCHING BATTERY CABINET DIMENSIONS Battery Cabinet Width Depth Height 25T 29 in 31 5 in 59 in 39T 36 in 29 5 in 70 7 in 25T 39T Figure F 1 Relative Sizes of External Non matching Battery Cabinets ...

Страница 135: ...g 18 19 replacement 5 58 A5 voltage drop 14 16 41 Battery Cabinet 13 48 Buzzer volume A5 Bypass disable A5 mode 15 31 overload capacity A5 switch A5 C Cable size 13 capacitors 58 clearance 60 Common mode noise 14 A4 Communication interface 41 Conduit Knock out sizes 59 Cooling fan 58 D Data See Data Display Screens Data Setting Screens DB9 Connector female pinouts 42 male pinouts 41 Dimensional 60...

Страница 136: ...tion 7 Installation Precautions 8 Interface communications 41 42 43 receptacle panel module 49 RS232 ASCII A6 Inverter Overload Capacity A5 K Keypad controls 28 password 29 30 Keys 25 Knock out sizes 59 L labels warning 3 Lifetime battery 58 A5 capacitors Aluminum electrolytic 58 fan cooling 58 fuses 58 Liquid Crystal Display LCD Functions 23 Low Voltage Tolerance 17 M MAIN tab 27 Maintenance Bypa...

Страница 137: ...le Panels 49 Recharge Time 18 A4 RECORDS tab Fault messages 52 Mode messages 55 Status messages 55 Warning messages 53 remote contacts interface 41 Remote Switch 13 Restrictions on UPS use 10 RS 232C 42 Run 23 S Safety instructions 1 5 Schedule Operation A5 Security access 29 passwords 29 30 Security access 20 39 Shipping Weight 59 Shutdown voltage 17 Signal Function RS 232C 41 Signal Words 2 size...

Страница 138: ...ns 25 keypad 28 menu tree 27 mimic display 32 passwords 29 screen disable 31 U UPS Discharge Process 16 17 UPS Connections 11 UPS functional overview 14 UPS stop signal input 41 V ventilation 10 Voltage Transient A4 Volume Buzzer See Buzzer Volume W warning labels 3 Warranty c d 7 Weights shipping 59 Weights UPS 59 width 60 ...

Страница 139: ......

Страница 140: ...CTRONICS DIVISION 13131 West Little York Road Houston Texas 77041 Tel 713 466 0277 Fax 713 466 8773 US 800 231 1412 Canada 800 872 2192 Mexico 01 800 527 1204 https www toshiba com tic industrial uninterruptible power systems Printed in the U S A ...

Отзывы: