1600XP/XPi Series Installation and Operation Manual – 60616-012
Display
Recorded
Meaning
Action
BOH
Y
Battery Overheat – Battery not
within specifications.
Call Toshiba for service.
BRPL
Y
Replace Battery – Battery at end
of life expectancy.
Replace battery immediately.
BSDV
N
Battery Shutdown Voltage – Bat
-
tery is discharged down to mini-
mum level.
UPS will shut down. Secure critical loads until
power can be restored.
BTSTFL
N
Battery Test Failed – Battery not
within specifications.
Call Toshiba for service.
BYPOV
N
Bypass Overvoltage – Bypass
voltage exceeds UPS specifica
-
tions.
UPS in Bypass Mode: UPS turns off bypass
power to the load until bypass power returns to
normal. Check bypass power.
BYPUV
N
Bypass Undervoltage – Bypass
voltage less than UPS specifica
-
tions.
UPS in Bypass Mode: UPS turns off bypass
power to the load until bypass power returns to
normal. Check bypass power.
CALL
Y
Service Call Required – Inspection
of the unit is advised.
Have inspection/service performed.
CHRGOV
Y
Charger Overvoltage – Battery
Charger not within specifications.
Call Toshiba for service.
CLMT
N
Current Limit – UPS not within
specifications.
Call Toshiba for service.
DCER
Y
Display Cable Error – Display
cable is disconnected.
Connect the display cable.
DCANERR
N
Communication Error between
Display and Main Controllers.
Call Toshiba for service.
EXTBC1
N
1.
BC1 Battery String 1, 2, or 3
Disconnected
2.
BC1 Over Temperature
3.
BC1 Lost Communications
with UPS
•
Recover without power cycle - Must Manually
Reset.
•
Reduce Load on BC, call factory Toshiba for
Service
•
Call Toshiba for Service
EXTBC2
N
1.
BC2 Battery String 1, 2, or 3
Disconnected
2.
BC2 Over Temperature
3.
BC2 Lost Communications
with UPS
•
Recover without power cycle - Must Manually
Reset.
•
Reduce Load on BC, call Toshiba for Service
•
Call Toshiba for Service
FBYPER
N
Bypass Frequency Error – Input
frequency outside of UPS specifi
-
cations.
UPS in Bypass Mode: UPS turns off bypass
power to the load until bypass frequency returns to
normal. Check bypass frequency.
FIER
N
Input Frequency Error – Input
frequency outside of 45 – 65 Hz
range.
UPS in On-Line Mode: UPS switches to BACKUP
mode until Input Frequency returns to normal.
LB
N
Low Battery – The battery level
has dropped low (about 90% or
less) during operation. Continued
operation in this mode will deplete
battery and cause output shut
down.
Immediately shut down the load equipment in an
orderly fashion and then press the STOP key.
Содержание 1600XP SERIES
Страница 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 114: ...C2 1600XP XPi Series Installation and Operation Manual 60616 012 3 6 6 kVA Dimensions w Optional MBS ...
Страница 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Страница 116: ...C4 1600XP XPi Series Installation and Operation Manual 60616 012 14 22 kVA Dimensions w Optional MBS ...
Страница 131: ...E1 1600XP XPi Series Installation and Operation Manual 60616 012 Appendix E External Battery Cabinets Matching Outlines ...
Страница 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 139: ......