B-15
1600XP/XPi Series Installation and Operation Manual – 60616-012
525
External Batt Cabinet Number of Battery Packs in Series
No Ex Bat(Series)
R
R/W
R/W
R/W
R/W
0
Number of external batteries in series string. (24 for one
or two battery cabinets)
Range: 0 – 48
526
External Batt. Cabinet Number of Battery Strings in Parallel
No Ex Bat(Paral)
R
R/W
R/W
R/W
R/W
0
Number of external battery strings in parallel Depends on UPS rating and Battery Cabinet
Type.
Typically One
external battery cabinet =3, two cabinet =6
Range: 0 – 24
527
External Battery Cabinet Rated Battery Capacity in Ampere-Hour
Ex Batt Rated
Ahr
R
R/W
R/W
R/W
R/W
0
External matching battery cabinets use same battery
as internal: 9
Ah. (same as 51
1. Non-matching may be
dif
ferent)
Range: 0 – 12
Units: Ahr
528
External Battery Cabinet Rated Battery Discharge C Rate
Ex Batt C Rate
R
R/W
R/W
R/W
R/W
0
Range: 0 – 12
(Informational only
. Not used in calculations.)
Units: C
529
External Battery Cabinet Installation Date
Ext Batt Ins Date
R
R/W
R/W
R/W
R/W
“20080101”
Format:
YYYYMMDD
(Informational only
. Not used in calculations.)
532
Battery V
oltage Gain
Vbat Gain
-
-
-
R/W
R/W
8298
Used this value to convert
AD value to actual unit.
Range: 1 – 32767
533
Battery V
oltage Of
fset
Vbat Of
fset
-
-
-
R/W
R/W
0
Feedback Of
fset adjustment due to hardware
components and software
AD converter
’s of
fset.
Range: -32768 – 32767
534
Battery V
oltage
AD
Amount
Vbat
AD
-
-
-
R
R
0
AD summation of 16 samples per half cycle.
544
Charger Reference (Normal Charging Mode)
Charger Ref(Norm)
-
-
-
R/W
R/W
55
Range: 0 – 320
545
Low Batery Level
Low Batt Level
R
R
R/W
R/W
R/W
90
% of battery nominal voltage.
Range: 0 – 100
Units: %
546
Charger Overvoltage Detection Delay
VChrgOV DeDelay
R
R
R/W
R/W
R/W
60
(Restart Required)
Range: 0 – 360
Units: Sec
547
Calculated Low Battery Level
in Vdc
Cal LB Level
R
R
R
R
R
0
Calculated from level setup Command 545.
Units: Vdc
Item
Brief Description
Description
On LCD
U
A
D
Svc/ QC
F
Default
Remark
Содержание 1600XP SERIES
Страница 2: ...b 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 6: ...f 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 10: ...iv 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 74: ...64 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 112: ...B 32 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 114: ...C2 1600XP XPi Series Installation and Operation Manual 60616 012 3 6 6 kVA Dimensions w Optional MBS ...
Страница 115: ...C3 1600XP XPi Series Installation and Operation Manual 60616 012 8 10 kVA Dimensions ...
Страница 116: ...C4 1600XP XPi Series Installation and Operation Manual 60616 012 14 22 kVA Dimensions w Optional MBS ...
Страница 131: ...E1 1600XP XPi Series Installation and Operation Manual 60616 012 Appendix E External Battery Cabinets Matching Outlines ...
Страница 132: ...E2 1600XP XPi Series Installation and Operation Manual 60616 012 ...
Страница 139: ......