Tomoe T-DYNAMO 7E Скачать руководство пользователя страница 21

19

20

4-5 Solenoid valve

The unit is operated by an electric signal from a remote 
place in order to open or close an air supply valve.

Rc1/4

0.4~0.7MPa

-5~50°C

AC100/110V, AC200/220V, DC24V

50/60 Hz

AC: -10~10%, DC:-15~10%

G1/2 Conduit terminal

Double solenoid type and explosion-proof solenoid type are also available.

(1)  Install the sub plate onto this product using the 

sub-plate holding bolts and the two tapped holes 
for solenoid valve installation located on the front 
surface of this product. [Fig. 10]

(2)  The solenoid valve installation orientation 

depends on whether the valve is opened or 
closed when energized. To reverse the orienta-
tion, remove the solenoid valve holding bolts, 
reverse the solenoid valve orientation, and 
re-install the unit [Fig. 11].

PCS2406-K090-Z03-132-



PCD2406-K090-Z04-120-



(The figure shows mounting orientation for "Energized to open").

Manufactured by KANEKO SANGYO
MK15G-8-

-DMI

MK15DG-8-

-DM

Energized to open

Sub-plate
holding bolt

Solenoid valve holding bolt 

Standard specifications

Installation procedure

[Fig. 10]

 [Fig. 11]

[Fig. 13]

[Fig. 14] 

Standard specifications

(1)  Fasten the attachment part set (plate) to the sub 

plate with screws (short).

(2)  Sandwich the attachment part (plate) and the filter 

regulator with the attachment part (clamp).

(3)  Fasten the attachment part (clamp) with screws 

(long). [Fig. 12]

Installation procedure

P31EA22MMBNNP

Rc1/4

0.4~0.7MPa

Max 50°C

O-ring

Solenoid valve holding bolt

Attachment part set

[Fig. 12]

Solenoid valve unit

(non explosion-proof type)

Solenoid valve

(explosion-proof type)

(1)  Install the solenoid valve unit to this product using 

the solenoid valve holding bolts and the two 
tapped holes for solenoid valve installation located 
on cover 1 of this product. [Fig. 13]

(2)  The solenoid valve installation orientation 

depends on whether the valve is opened or closed 
when energized. To reverse the orientation, 
remove the solenoid valve holding bolts, reverse 
the solenoid valve orientation, and re-install the 
unit. [Fig. 14]

Installation procedure

O-ring

Energized
  to close

Energized
to close

Drain exhaust port
Make sure to put the filter regulator drain exhaust port downwards.

O-ring

Plate

O-ring

Screws (short) (4pcs)

Screws (long) (2pcs)

Clamp

Pressure gauge

O-ring

For pressure-closing 
single-acting type cylinders 
(7F), "Energized to open" 
is replaced with "Energized 
to close" in the figure.

Sub plate

Table 3 Solenoid valve (non explosion-proof type) standard specifications

Port size
Operating pressure range
Ambient temperature
Rated voltage
Frequency
Allowable voltage fluctuation
Wiring method

Filter regulator

(direct installation)

Filter regulator (FR) can be directly fitted to the non 
explosion-proof type solenoid valve unit.
FR is used to remove oil, moisture, and dust from 
operating air (air filter) in order to protect pneumatic 
equipment (solenoid valve, cylinder etc.), and to keep 
appropriate constant operation pressure (regulator).

Table 4 Filter regulator standard specifications

Type
Port size
Operating pressure range
Ambient temperature

For pressure-closing single-acting 
type cylinders (7F), "Energized to 
open" is replaced with "Energized 
to close" in the figure.

For double-acting/single-acting spring open

Tapped hole

Cover 1 

Filter

regulator

Содержание T-DYNAMO 7E

Страница 1: ...pe cylinder 3 2 Expanded view Single acting type cylinder 3 3 Output torque curves 3 4 Air consumption 4 CYLINDER SYSTEM CONFIGURATION 4 1 System configuration 4 2 Speed controller 4 3 Adjustment of v...

Страница 2: ...and inspection of this product If there are any questions please contact our sales department Reference values and limit values for operation maintenance and inspection specified in this instruction...

Страница 3: ...packing 2 The shaft penetrates the chamber of the case The yoke is fitted in the hole across the shaft in such a way that it allows it to slide in the hole The top of the yoke is connected with the p...

Страница 4: ...ting type cylinder 7F 7G 1 3 Type description 1 4 Standard specifications Double acting type cylinder 7E Single acting type cylinder 7F 7G T85 T 8 5 S The output torque of single acting type differs f...

Страница 5: ...2 1 3 Fail safe design When the unit is used for the point where fail safe design is required adopt a method where the system responds in a way that will cause no harm using a single acting type cylin...

Страница 6: ...ocation The following measures should be taken depending on the atmosphere of the location where this product is installed Locations which are exposed to gas containing salt corrosive gas chemical sol...

Страница 7: ...le paying attention to the following items If dents or scratches are made on impact to ensure safety stop using the product and replace the product This product attachments and pneumatic pipelines sho...

Страница 8: ...atic devices in which the pneumatic pipeline inlet of this product or the end of the plant pipeline is connected with a long pipeline air supply amount and air supply pressure may be insufficient for...

Страница 9: ...ion check that the manual gear is at the position of automatic operation and the bypass valve is closed They are not returned automatically 2 4 8 Others If air supply is stopped for a long period of t...

Страница 10: ...be checked that opening of the valve and the opening of this product are the same If the openings are not the same opening and closing operation is performed in the reverse way 2 5 6 Replacement of c...

Страница 11: ...ng washer cover 1 2 8 14 Bearing 2 1 T35 only 47 Hexagon socket head cap screw cover 1 2 8 15 Bearing 3 lower shaft 1 49 Hexagon socket head cap screw base plate 4 T35 2pcs 16 Bearing 4 upper shaft 1...

Страница 12: ...2 1 37 Stopper bolt 1 T750S only 8 Base plate 1 42 Spring 2 9 Bearing 2 43 Spring guide 2 11 Indicator plate 1 44 Hexagon bolt spring guide 2 13 Bearing 1 shaft piston 2 45 Spring washer spring guide...

Страница 13: ...e cylinder air consumption N VS Single acting type cylinder air consumption N A B Cylinder capacity P Operating pressure MPa N Operating frequencies in a given time 1 round trip 1 CD Double acting typ...

Страница 14: ...box This switch box is for remotely displaying the open close status of the valve Positioner unit E P Positioner and P P Positioner This unit features a function that allows total control of the valve...

Страница 15: ...ht knob and adjust the closing speed with the left knob For single acting type cylinders only the speed when operating air is discharged can be adjusted Adjust the speed only with the right knob For p...

Страница 16: ...sition becomes shallow Please refer to Table 1 for rotation angles Hexagon stop screw Hexagon stop screw Seal washer Position indicator For pressure closing single acting type cylinders 7F the opening...

Страница 17: ...red angle The hexagon stop screw is rotated clockwise and the valve full open position becomes shallow Please refer to Table 1 for rotation angles How to restore after adjustment 1 Hold the hexagon st...

Страница 18: ...w Knob Approx 10 mm Automatic operation Bypass valve closed Manual operation Bypass valve open Do not use a spanner a monkey wrench or the special lever in the following cases as it could result in a...

Страница 19: ...en the cross recessed head screw to lock the knob Reconnect the solenoid valve or the air pipeline When the manual gear and the manual screw handle are not installed Remove spanner monkey wrench or sp...

Страница 20: ...h the attachment part plate and the filter regulator with the attachment part clamp 3 Fasten the attachment part clamp with screws long Fig 12 Installation procedure P31EA22MMBNNP Rc1 4 0 4 0 7MPa Max...

Страница 21: ...ed on cover 1 of this product Fig 13 2 The solenoid valve installation orientation depends on whether the valve is opened or closed when energized To reverse the orientation remove the solenoid valve...

Страница 22: ...ous situation 1 Set the position to full close on this product 2 Loosen the cover holding bolts at the four corners of the limit switch box and remove the top cover Fig 15 3 Pull the top cover out upw...

Страница 23: ...tic pipelines and electric wiring from this product 2 Remove the bolts and spring washers that fasten this product to the valve then take out this product from the valve Removal of the unit from the v...

Страница 24: ...1 Q ty 2 pcs for each 4 pcs for each Type 35 T85 T750 T85S T750S 7 Take out the yoke and the bearing from the case Please note that the type and quantity of the bearing of T35 is different from those...

Страница 25: ...screw in the bolts to the length shown in Table 8 and tighten them Fig 23 Not required for T750S 7 Loosen the hexagon socket head cap screws and alternately When the cover and the bolts for disassem...

Страница 26: ...is a mounting direction for the yoke Assemble the unit so that the face stamped with UP mark of the yoke faces to the upper side of the cylinder Note If F mark is stamped on the yoke instead of UP ma...

Страница 27: ...sure the free movement of the piston Fig 33 Insert the connecting pin after making sure that the pin hole of the yoke and the pin hole of the shaft are aligned Insert the connecting pin into the tappe...

Страница 28: ...le 12 Grease application amount Thrust plate Case Stopper Shaft Thrust plate Base plate Hexagon socket head cap screws Spring washer For T35 Apply liquid gasket to the designated area on the base plat...

Страница 29: ...t wrong cover installation causes defective operation such as air leakage Forcible assembly of single acting type cylinders such as uneven tightening of the hexagon socket head cap screw to mount the...

Страница 30: ...hten the bolts for disassembly until the dimension A in the figure becomes the distance where the hexagon socket head cap screws which had been mounted to the product can engage the case And then inst...

Страница 31: ...e knob of the speed controller Supply pressure of compressed air etc is high Decrease the air supply pressure within the range of the specifications of this product Speed controller is closed too much...

Страница 32: ...aused by fire flood earthquakes fall of rocks and other acts of God 12 The failure was caused by other reasons which are not our responsibility In addition the forgoing warranty is only applicable to...

Отзывы: