IP-EN1-EB Instruction Manual
6
4.2 General Fault Control Output CN9
A general fault information to the fire detection system can be provided in four different
ways:
1. make a contact without surveillance
2. make a contact with surveillance
3. break a contact without surveillance
4. break a contact with surveillance
The corresponding settings in the setting software are described in the chapter 5.2 for the
VX-2000 system and in the chapter 6.3 of the SX-2000 system.
4.2.1 Make a contact without surveillance
Solder in a wire on position “R1”
Connect to pins 2 and 3 of CN9 to the FDS
4.2.2 Make a contact with surveillance
Solder in resistors R1 and R3
Connect to pins 2 and 3 of CN9 to the FDS
as required by the FDS
4.2.3 Break a contact without surveillance
Sol
der in a wire on position “R1”
Connect to pins 1 and 2 of CN9 to the FDS
4.2.4 Break a contact with surveillance
Solder in resistors R1 and R2
Connect to pins 1 and 2 of CN9 to the FDS
as required by the FDS
R1
1
2
3
To FDS
CN9
2
3
CN9
R1
1
2
3
To FDS
CN9
R3
R1
2
3
CN9
R3
R1
1
2
3
To FDS
CN9
1
2
CN9
R1
1
2
3
To FDS
CN9
R2
R1
1
2
CN9
R2