IP-EN1-EB Instruction Manual
13
5.2 Settings in the VX-2000 Setting Software
5.2.1 Mandatory Indication
5.2.1.1 Fault Indications
No.* Indication of
VX-2000
connections/
assignment
Settings in Operation setting mode, button
[Failure Output]: use one Fault Output
Pattern per indication (one line in the list),
make a check in
4
General fault
Control output
3
T
ab “Equipment” if not noted otherwise:
1. all emergency and fireman microphones
2. external fault C
IN
connected to the
optional Ethernet Switch **
3. all EV-200M
4. VX-2000
5. all VX-2000SF
6. all amplifiers including the standby
amplifier
(tab “Power amplifier”)
7. all faults (short circuit, open circuit,
ground fault) for each loudspeaker line
(tab “Speaker”)
8. each VX-2000DS connection to VX-
2000SF
(tab “Power supply”)
5
CPU fault
CPU OFF
control output
Only connection, no setting
6
Power fault
Control output
5
T
ab “Power Supply”:
each existing VX-2000DS connection to
VX-2000SF
7
Fireman/
emergency
microphone fault
Control output
6
Tab “Equipment”:
all emergency and fireman microphones
8
Fuse fault
Control output
4
Tab “Power Amplifier”:
all amplifiers including the standby amplifier
9
Network fault
Control output
7
Tab “Equipment”:
external fault C
IN
connected to the Ethernet
Switch if used **
12
buzzer
Control output
8
Enable Failure Buzzer (Cout-8) ***
*:
number as on “Appearance Front Panel”, page 3
**:
refer to next page “Details to number 9”
***:
refer to “New function Enable Failure Buzzer”
[ ]: button of the main menu of the VX-2000 setting software