IP-EN1-EB Instruction Manual
15
5.2.2 Control Input Settings for Emergency and Button Controls
The settings are to be made in the activation setting mode. Select th
e button “Control Input”
of the main menu.
Control input Function setting
Refer to
1, 2
Emergency pattern, Emergency reset, silence
Chapter 4.3
3
Failure output reset
-
6
Failure output receipt (no control output required)
-
5.2.3 Indication of Failures in Fire Alarm Areas (option of EN 54-16)
When using this option, then a failure of each fire area must be indicated. Consider that a
fire area may consist of several paging zones, i.e. a fire area can cover a group of zones.
The fire areas should be declared by the responsible party (e.g. fire brigade, fire expert)
who is aware of the emergency concept.
Failures in of up to 8 fire areas can be indicated. The control outputs 9-16 shall be used for
that.
Setting by the VX-2000 Setting Software
a. In operation mode, select the button [Failure Output].
b. Select a free line (make a new failure pattern) and
c. S
elect the tab “Speaker”.
d. Make a check into each box (short circuit, break, earth leakage) of each speaker zone
that belongs to that fire area.
e. Select the control output for the corresponding indication LED (refer to next table)
f. Proceed again from step 2 on for the other fire zones.
Relation of Control Output to indication LED of fire area (FA)
Indication LED
FA 1 FA 2 FA 3 FA 4 FA 5 FA 6 FA 7 FA 8
Control output no.
9
10
11
16
13
14
12
15