IP-EN1-EB Instruction Manual
12
5
Connections and Settings for the VX-2000 System
5.1 Connections to VX-2000
Rear right side (mandatory indications)
1
Connect CN1 to CTRL OUT 1-8 of the VX-2000
(use Cat5/5E/6 FTP or STP or SFTP (with shield)
2
Connect CN11 to CTRL IN 1-8 of the VX-2000
(use Cat5/5E/6 FTP or STP or SFTP (with shield)
3
Connect CN10 with power supply from VX-2000DS or VX-3000DS
(don’t connect to
regulated 24 VDC), + on pin 1, - on pin 2
4
Connect CN2 to the CPU OFF output of the VX-2000, connect to pins 2 and 3
5
CN15 provides the access to 4 control inputs of the VX-2000 that are not used by the
indication panel and can be used for other control purposes:
CN15 pin no.
1
2
3
4
5
6
VX-2000 control input no.
5
COM
4
7
COM
8
Rear left side (fault indications of fire areas or other fault indications)
6
Connect CN1 (of rear left side) to CTRL OUT 9-16 of the VX-2000
(use Cat5/5E/6 FTP or STP or SFTP (with shield)
CN7
CN15
CN9
CN12
CN18 CN13
CN10
R6
1
1
1
1
1
1
3 2 1
R2
R3
R1
CN20
CN6
CN8
CN19
CN1
CN5
CN11
CN3
+ -
20-40 VDC
CPU OFF
CTRL OUT 1-8
CTRL IN 1-8
1
CN12
2
3
4
5
CN2
CN7
CN2
1
1
1
CN1
CTRL OUT 9-16
6