172-65128MA-11 (FS3/FS5/FS5H + BD2) 10 Mar 2017
7
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
1. Before installation, be sure to remove all protective seals.
2. Before installing the product, blow out the inlet piping to remove any piping scraps,
dirt and oil. Close the inlet valve after blowdown.
3. Install the product so the arrow on the body is pointing in the direction of condensate
flow.
4. The connector body has no restrictions on installation orientation except for the
following conditions: the universal flange face (for connecting to the trap unit) must
be in the vertical plane, and the trap unit must be installed with the nameplate facing
upwards.
5. The trap unit must be installed with the nameplate facing upward, and should be
inclined no more than 5° in any plane. Use the two connector bolts to adjust the
angle of the trap unit.
6. Install a condensate outlet valve and outlet piping.
7. Open the inlet and outlet valves and check to make sure that the product functions
properly.
If there is a problem, determine the cause using the “Troubleshooting” section in this
manual.
Tolerance Angle for Installation - 5°
Install with the nameplate facing upwards and with the arrow on
the connector body pointing in the direction of condensate flow.
(UP seal: Not always included)